Responds to NRC Re Violations Noted in Insp Rept 50-346/84-20.Corrective Action:Sign Placed on Auxiliary Feedwater Pump Room Water Tight Door Notifying Personnel Not to Leave Door Open or Unattended
ML20100J143
Person / Time
Site: Davis Besse 
Issue date: 11/30/1984
From: Crouse R
TOLEDO EDISON CO.
To: Norelius C
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20100J131 List:
References
1-482, NUDOCS 8412100229
Download: ML20100J143 (3)


Text

n m

, $p. cys...,

Docket No. 50-346 TOLEDO

!!EI!!I(I!N License No. NPF-3 RicHARO P. CnousE Serial No. 1-482

w. e,,s.m NKWF (419:2s9-5225 November 30, 1984 Mr. C. E. Norelius, Director Division of Reactor Projects United States Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Norelius:

Toledo Edison acknowledges receipt of your November 2, 1984 letter (Log No. 1-1053), and enclosures, Appendix A, Notice of Violation, and Inspec-tion Report No. 50-346/84-20(DRP).

Following an examination of the items of concern, Toledo Edison herein offers information regarding these items:

1.

Violation:

Technical Specification 6.8.1 states, in part,

{

" written procedures shall be establishea, imple,

mented and maintained covering the activities referenced in Appendix "A" of Regulatory Guide 1.33, November, 1972.

Section 1 of Appendix A of Regulatory Guide 1.33, November, 1972 is Administrative Procedures.

Contrary to the above, Administrative Procedures were not adhered to in that:

a.

The inoperability of the #2 Control Room Emergency Ventilation System (CREVS) Freon compressor was not reported to the shift supervisor during the performance of TP 641.00 as required by Administrative Procedure AD 1839.00.

b.

The shift supervisor was not informed of the fact that the pressure door connecting the two Auxiliary Feedwater Pump rooms was left open and unattended, potentially rendering both AFW pumps inoperable as re-quired by Administrative Procedure AD 1839.

THE Tot FDO EDISON COMPANY EDISON PLAZA 300 MADISON AVENUE TOLFDO, OHIO 43652 8412100229 841206 PDR ADOCK 05000346 G

PDR DEC 6 564 L

-. yW o.

Docket.No. 50-346

~ License No. NPF-3 LSerial No. 1-482-November 30, 1984 Page 2-c.

A Test Leader for the performance of test procedure TP 641.00 was not assigned as required by Administrative Procedure AD 1801.00.

d.

A chronological log was not maintained to document test activities during the per-formance of test TP 641.00 as required by Administrative Procedure AD 1801.00.

e.

Proper administrative control of the' " Control

. Copy" of test procedure TP 641.00 was not maintained as required by Administrative Procedure AD 1801 in that the test procedure was removed from the station for a period of four days, f.

A deviation report identifying procedural violations was not generated as required by AD 1807.00.

This is a Severity Level IV violation (Supplement I).

Response: (1) Corrective action taken and results achieved.

a.

The No. 2 Control Room Emergency Ventilation System was declared inoperable on August-11, 984, when operating in the water cooled condenser mode. Since the air cooled condenser mode provides 100% cooling capability, the train itself was not rendered inoper-able.

b.

A sign was placed on the Auxiliary Feedwater Pump Room water tight door notifying personnel that the door is not to be left open and unattended as this would render the Auxiliary Feedwater Pumps inoperable.

c, d, e.

A Test Le auer was assigned to TP 641.00 and the individual was trained in his responsibilities wi.h respect to test performance. Additionally, a chrono-logical log and control copy of the test procedure is being maintained for TP 641.00 as required by procedure AD 1801.00, ftation Modification Acecptance Test Program. The Station Instrument and Control Shop personnel and Maintenance staff were instructed on the specific requirements of procadura AD 1801.00. They were additionally instructed on the necessity for informing the Shif t-Supervisor of test deficiencies m

m

.1

-.m m-J

y

..w 74 b %#74 o J y'j '

i \\=

cDock:t No. 50-346 p *, y~.;

,}

~

- License No. NPF-3 c

~ h, Serial No. 1-482 J

.i (November 30, 1984

'?

s ' f,

.('

Page 3

,'OL A

'~

I, and operability considerations per procedure AD N

1839.00, Station Operations, and the reportability requirements of AD. 1807.00, Control of Conditions y

Adverse to Quality.

!],

.. ~..

f.

DVR 84-166 was generated on Nov' mber 5,1984. identi-- d e

' fying the procedural violations. 4 1,, 3

'\\

f(2) Corrective action taken to avoid further noncompliance.

~.

A " listing will be prepared for all test procedures that have been J,dentified as requiring acceptance testing during-thel 198C refueling outage. Each test procedure will be -

f reviewed to ensure that a-cognizant individual has been

~

assigned as test leader, and that this individual under-stands the requirements of AD 1801.00, AD 1807.00, and AD 1839.00.

Additional training for the Station staff on the above mentioned administrative procedures will be provided as longer term corrective action.-

(3) Date full compliance will be achieved.

The longer term training will be conoucted by July 1,1985.

Very truly yours, c#

te RPC:SGW:JAF:nif cc: DB-1 NRC Resident Inspector

~