ML20100H546

From kanterella
Jump to navigation Jump to search
Updates Initial Response to IE Bulletin 84-03 Re Reactor Cavity Seal.Seal Deflection Measurements Previously Proposed Determined Inconclusive Per Impell Corp 850207 & 08 Tests. Vertical Offset Measurements Show Less than 1/4-inch Offset
ML20100H546
Person / Time
Site: Ginna 
Issue date: 03/29/1985
From: Kober R
ROCHESTER GAS & ELECTRIC CORP.
To: Murley T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
IEB-84-03, IEB-84-3, NUDOCS 8504090230
Download: ML20100H546 (1)


Text

.--

- =..

g@

, eg

_...g3 R6bkf L

.s i

ROCHESTER GAS AND ELECTRIC CORPORATION e 89 EAST AVENUE, ROCHESTER, N.Y. 14649-0001 %mQ e par ny ratamost ELEcTasc a, STEAM PROOUCTION ARE A CODE Tis 546 2700 March-29, 1985 L

j Dr. Thomas E. Murley, Regional Administrator U.S.' Nuclear Regulatory Commission Region I 631 Park Avenue King of Prussia, Pennsylvania 19406 l

Dear Dr. Murley:

The' following is an update to our initial response to I/E j

Bulletin-84-03.

As a result of recent reactor cavity seal testing performed at IMPELL Corporation on 2/7/85 and 2/8/85, it was determined that seal deflection ~ measurements, as proposed in our initial response to Bulletin 84-03, would prove inconclusive.

During the i

testing, it was observed that final seating of the' cavity seal does not occur until a significant head of water- ~(approx. ten feet)

~

covers the cavity seal.

This observation was discussed with Mr. Lee Bettenhausen and Mr. Henry VanKessel of NRC Region I.

It was agreed that Rochester Gas and= Electric would attempt to obtain vertical offset measurements as requested by Mr. VanKessel instead of the seal deflection measurements.

This was contingent upon acceptable. radiological dose rates '(in the work area).

These measurements were subsequently obtained with the results indicating less than a 1/4" offset existed between the reactor vessel flange and the refueling cavity.

A copy of the test matrix and the experimental results

.obtained from the IMPELL test have been transmitted'to Mr. VanKessel.

If any further information is necessary, please contact-Mr. Joseph Widay at the R.E. Ginna Plant.

Please -consider this as our final closeout to I/E Bulletin j

84-03 i

V truly yours,-

p h

y fj

~y

(

G 3

j.

R er W. Kober i

Subscribed and sworn to me t/p xc: U. S. -Nuclear Regulatcry Commission (

day []of March 1985 on this 29t

\\./

Document Control Desk W

NNl.HAUCK Washington, D. C.

20555 I

//lA /. /

l

/j

' + mete of EU, Monroe County My Commission Empires March 30,19M

(

~!