ML20100G655

From kanterella
Jump to navigation Jump to search
Clarifies 840716 Request for Addl Info Re NUREG-0737,Item II.K.3.28 Re Qualification of Accumulators on Automatic Depressurization Sys Valves.Existing Check Valves Replaced W/Environmentally & Seismically Qualified Valves
ML20100G655
Person / Time
Site: FitzPatrick 
Issue date: 04/01/1985
From: Bayne J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To: Vassallo D
Office of Nuclear Reactor Regulation
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.K.3.28, TASK-TM JPN-85-24, NUDOCS 8504080346
Download: ML20100G655 (2)


Text

-

hr

.b.

123 Main S' tieet -

1

, y4-

~ White Plains,-NuwWrk 10601

~

~ 914 681.6800 m

f M er Nik"tTxU57c.eresioe "e'o-'**=o"*e'

& Authority April 1, 1985

'JPN-85-24 Director of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.

20555 Attention:. Mr. ' Dontenic B. Vassallo, Chief Operating Reactors Branch No. 2 Division of Licensing,

Subject:

James A. FitzPatrick Nuclear Power Plant Docket No. 50-333 NUREG-0737 Item II.K.3.28 Qualification of Accumulators on Automatic Depressurization System Valves

~

1.

NYPA letter, J. P. Bayne to D. B. Vassallo,

References:

dated September 4, 1984~(JPN-84-58).

2.

NRC letter, D. B. Vassallo to J. P. Bayne, dated July. 16 1984.

Dear Sir:

This letter clarifies the Authority's response (Reference 1) to the.NRC's Request for Additional Information (Reference 2).

4 NUREG-0737 - Item II.~K.3.'28 requires that the ADS valves, accumulators and associated equipment and instrumentation be capable of performing their functions during and following exposure to-hostile environments for periods up to 100 days without taking credit for non-safety related equipment or instrumentation.

The Authority has confirmed that the ADS valves, accumulators and 4

piping, with the exception of the accumulator check valves, are i ='

environmentally and seismically adequate.

The existing check valves will be replaced with environmentally and seismically qualified valves during the current outage.

In accordance with the NRC staff evaluation (Reference 2), this is sufficient to meet the short tern ADS operability requirements.

4' s

a 8504080346 850401 db PDR ADOCK 05000333 1/d t -

p PDR

g

.+.

During the 1986 refueling outage, the Authority will upgrade the ADS accumulator system to remain functional for periods up to 100

-days following a postulated accident.

This will be accomplished either by providing-an environmentally and seismically qualified back-up~ system to recharge _the accumulators for long term operation or by providing redundant, safety-related pneumatic sources to actuate the ADS valves.

The most effective modification to meet NUREG-0737 - Item II.K.3.28, long tern ADS operability requirement, will be selected upon conclusion of an engineering study scheduled to be completed in 1985.

After completion of the modifications chosen, _the FitzPatrick plant will meet-all the requirements'of NUREG-0737 - Item II.K.3.28.

If_you have any questions. please contact Mr. J. A. Gray, Jr. of my staff.

Very truly yours, J.

yN F.irst Execu ive Vice President Chief Operations Officer cc: Office of the Resident. Inspector