Text
_ ~ _
'b sq S uth C:rtline E12ctric & Gas Comp:ny John L. Gxttds
~
. Jenkinsviha, SC 29065.
Vce Presidsnt P.O. Box 88 Nuclear operations f:
(803) 345 4040 SCEAG August 11, 1992 Mr. William R.-Krecker Environmental Quality' Manager
~
Water Quality Assessment & Enforcement
~ Division.
South Carolina Department of Health
& Environmental Control 2600 Bull Street-
~
Columbia,--South Carolina 29201
Dear Mr. Krecker:
Subject:
~ VIRGIL C.
SUM! DER-NUCLEAR STATIOli DISCHARGE BAY FISH _ KILL (ONO 920059)
-AUGUST 5, 1992 L
South : Carolina _ Electric &_ Gas Company. (SCE&G) herewith submits a report concerning-a recent _ fish kill which _ occurred in -the circulating water discharge bay of the Virgil C.
Summer Nuclear Station ' ' (VCSNS).
_The enclosed report describes the event and
. probable cause.
SCE&G ' will: continue __ to ' monitor temperature and. flow conditions-within the_ area as previously discussed with DHEC and the South-Carolina Department of Wildlife and Marine-Resources.
In accordance ~with the VCSNS Operating License NPF-12, Appendix B, a copy ~of this report is being provided to the Nuclear Regulatory Commission.
Additionally, a copy of the report will be provided~ to the South Carolina-Department of Wildlife and Marine Resources-per the request of-Mr.-H.-J. Logan, Chief of Fisheries.
If_you have any questions please call Mr. Charles-McKinney at 345-14723.
Very truly yourg I
c-John L. Skolds-cjm-
.-Enclosure-
- c:
W.. M.
Lide, Jr.
R.-J.
White W. R./Baehr Dick Christie s
'R. R. Mahan?
NSRC IDocume' nt.ControllDesk:-
RTS (ONO 920059)
NRC Resident' Inspector File (809.06-1 & 818.05)
A. G. Alvarez/D. C.. Blanks /S. E.
Summer / File L
G. J. Bullwinkel/W. E. Moore /R. M. Webb/H.
L. Wolfe l:
Central-Midlands District g
Jg g NUCLEAR-EXCELLENCE'- A SUMMER TRAD3 TION!
l j
L 920e27oo12 920e21 m
^
[DR ADOCK 05000395 v>a-
-.~
4 FISH KILL REPORT AUGUST'5, 1992 A fish kill involving approximately 2500 fish was dis,: overed in the circulating water discharge area (see Figure 1) of the Virgil C.
Summer Nuclear Station (VCSNS) on August 5,- 1992.
The fish, due to the state of decompositior, appeared to - have died during the previous night.
Data suggest that the fish kill was caused by thermal-stress related to VCSNS circulating water discharge temperatures and Monticello Reservoir drawdown (see Figure 2). The apparent mechanism responsible for the fish kill eppears similar to
- previous kills in this area.
Table I lists the species of fish _ involved in the kill along with size information.
Figure 3 shows size classes of white catfish killed.
Approximately 90% of the dead fish were catfish.
This is consistent with other kills In this area and supports the theory that the fish move into the discharge bay from the discharge canal (see Figure _1) during full reservoir conditions and are trapped in the bay area by reservoir drawdown.
Table 2 presents Monticello Reservoir level, VCSNS circulating water discharge temperature, and discharge bay bottom temperature (one foot from the bottom).
There were_ no unusual discharges from VCSNS to Monticello Reservoir and water quality in the reservoir, as measured at the UGSG monitor at Fairfield Pumped Storage Facility, appeared normal. VCSNS power level remained at 100% for'the period preceding the fish-kill except for approximately four hours on August 2, 1992, when power
. level was reduced to 90%.
It is not known why this fish kill was more extensive than previous k ' '. l s in this. area._ It may be '. hat a period of relatisely high a,ervoir levels combined with a minor reduction in power level at VCSNS influenced recruitment into the bay, but _ the data are inconclusive.
It -is still believed that shoal removal in the discharge bay (Spring _1991) has-reduced.the number of fish kill.
events.-
Under the conditions associated with 1989 and 1990' fish kills, before shoal -removal, an additional thirteen fish kills (defined'as ten fish or greater) would be predicted for-July 8, 1992, -through August 3,
1992.
Temperature monitoring in the
- discharge bay and canal will continue, as will daily fish kill checks, while conditions'are favorable for fish kills this summer.
h/u.~/
Stephen E. Summer Environmental Services
.iy
-r,--.-
--4yw
-g.
r-c,
.-. +
- FIGURE 1 4
P-h MONTICELLO RESERVOIR
.q,
4 w
e.,
e-t.
p J
DISCHARGE CANAL SERVICE WATER POND 4
i,t +
j i:7 '
k Y
t'f :
O
?,..
i j
.= 3 i 2, ::it
. i.:
./
et
.g ly.
y[: <
'A 4;;S k:t.
g.f5 61"- M l.,#j
~
l DISCHARGE BAY M r;
./
\\
i P; l-pit prf:np !!ilF
~
- !R
, a ;n.a31.2.., m.; -,s.
Puoy *1 38 f t deep
/ AREA 0F FISH KILL
._'a m
,e,,
3: s ^
Temperotwe sensors:
- l. b ' g =7 L
~
r
~
x M
i fA :u i..
J i
4 n1,
+
m.
f DISCHARGE c
h' i a
n
p.
. - g FIGURE 2. DISHCARGE BAYTEMPERA1URE/ RESERVOIR LEVEL 30 JULY - 5 AUGUST 1992 110 426 b
FISil KILL iid 4
1 4 25-(
-y-
\\
w x 100
\\.
p-p\\Y:
Q
\\'
},\\
\\
'9
- 424 '
I
\\
g
\\);
l
,t >
E
\\
s Q/
Q' W l\\
/
d 90
-f 423 'd a-U b
' 'A
' ~
_ 477 x
~ ~ '
D d
H p
80 tu.
1 j
421 A7 y'
ry -
H
- 01 AUGi,
'4 AUO 2200 IIRS
~"
420 70 30 JULY S' AUGUST 1992
- U MONTICELLO RESERVOIR LEVEL BUOY I - 1 FT FROM BO'ITOM
~ ~.
~
VCSNS DISCHARGE A A GU T 41992 FISH KILL 350 300 250 E
m 200 150 100 lh...iih=
50 i 0
60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 SIZE CLASS IN MILLIMETERS
TABLE I
' SPECIES NUMBER KILLED SIZE (mm) white' catfish 2197 60 - 320*
channel catfish 64 80 - 375 bluegill.
184 80 - 140 gizzard-shad 8
62 - 229 black crappie ~
4 105 - 150 warmouth 1
125 unidentified catfish 18 not meestund unidentified shad =
8 60 -
95 unidentified fish 60 not neasmmd
- 1See figure 3-
!)~.
l-F:
TABLE 2.
e VCSNS DISCHARGE MONTICELLO CIRCULATING WATER BAY t-RESERVOIR DISCHARGE BOTTOM LEVEL TEMPERATURE TEMPERATURE Date-
-Time (feet) of
'F
============================================================_.
==
08/01/92-00:00 422.1 107.6 100.2 08/01/92-01:00 422.5 137.3 99.0 08/01/92 02:00 422.9 107.2 98.0
-08/01/92 03:00 423.2 107.1 96.8 00/01/92 04:00 423.7 106.8 95.8 08/01/92 05:00 424.0 106.6 94.4 08/01/92 06:00 424.4 106.6 93.4 08/01/92 07:00 424.8 106.6 93.2 08/01/92 08:00 425.0 106.6 93.2
'08/01/92 09:00 425.0 106.7 93.2 08/01/92 10:00 425.0 106.9 93.2 08/01/92 11:00 425.0 107.2 92.8 08/01/92 12:00 425.0 107.8 91.8 08/01/92
- 13:00 425.0 108.5
.91.2 08/01/92 14:00 425.0 109.0 91.2
-08/01/92 15:00 425.0 109.3 91.2 08/01/92
_16:00 425.0 109.6 91.2 08/01/92_
17:00 424.9 109.6 91.4 08/01/92 18:00 424.9 109.3 91.4
-.08/01/92
~19:00 424.8 109.3 91.6 08/01/92 20:00 424.7 109.4 91.8
_08/01/92 21:00 424.6 109.3 92.0 08/01/92 22:00 424.5 109.6 92.2
'08/01/92-23:00 424.5 109.6 92.4 l
__m. _ _ _ _ _ _ _ _ _ _ _ - - _. - _ - _ - - - -
TABLE 2.
(Continued)
VCSNS DISCHARGE MONTICELI;J CIRCULATING WATER BAY RESERVOIR DISCHARGE BOTTOM LEVEL TEMPERATURE TEMPERATURE Date Time (feet) oF
- F
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
08/02/92 00:00 424.4 108.5 92.8 08/02/92 01:00 424.4 108.0 93.0 08/02/92 02:00 424.4 109.0 93.2 08/02/92 03:00 424.4 109.4 93.4 08/02/92 04:00 424.4 109.5 93.4 08/02/92 05:00 424.4 109.6 93.0 08/02/92 06:00 424.5 109.6 93.2 08/02/92 07:00 424.5 109.5 93.4 08/02/92 08:00 424.5 109.3 93.2 08/02/92 09:00 424.5 109.1 93.6 08/02/92 10:00 424.5 108.9 93.8 08/02/92 11:00 424.5 108.7 94.0 08/02/92 12:00 424.5 109.0 94.4 08/02/92 13:00 424.5 109.5 94.2 03/02/92 14:00 424.5 109.8 93.8 08/02/92 15:00 424.5 109.9 94.0 08/02/92 16:00 424.5 109.7 94.4 08/02/92 17:00 424.5 109.4 94.4 08/02/92 18:00 424.5 109.5 94.2 08/02/92 19:00 424.5 109.5 94.4 s
08/02/92 20:00 424.5 109.2 94.2 2
08/02/92 21:00 424.5 109.0 94.0 08/02/92 22:00 424.5 108.7 93.8 08/02/92 23:00 424.5 108.7 93.2 xx--
_____wc_-
=.-.
. L' } ' g TABLE 2.
(Continued)
VCSNS-DISCHARGE MONTICELLO CIRCULATING WATER BAY RESERVOIR DISCHARGE BOTTOM LEVEL TEMPERATURE TEMPERATURE Date Time (feet)
- F
- F
======================_==================================
08/03/92-.
00:00 424.5 108.5-93.0
' 09/03/92 01:00 424.5 108.6 93.0 08/03/92 02:00 424.6 108.6 92.8' 08/03/92 03:00 424.6 138.5 92.6 08/03/92_-
04:00 424.7 108.5 92.4
- 08/03/92 05:00, 424.8 108.4 92.6 08/03/92-06:00 424.9 108.1 92.0 08/03/92--
07:00 424.9 107.9 92.2 08/03/92_
08:00 425.0 107.7 92.2 08/03/92
-09:00 425.0 107.6 92.2
-i 08/03/92
_10:00 425.0 107.5 92.6 08/03/92 11:00 425.0 107.5 92.6 1
-08/03/92-
_12:00 425.0 107.4 93.0 08/03/92_
13:00
'424.9 N/A 93.2 LO8/03/92 14:00 424.7 N/A 93.4 08/03/92
~15:00 424.6 107.5 93.4 08/03/92
.16:00 424.3 107.7 93.6
-08/03/92 17:00' 424.0 107.7 93.8 0.8/03/92
-18:00 423.7 107.5 94.4
~ 08/03/92 19:00 423.4 107.5 94.6 08/03/92 20:00 423.2 107.5 95.0 08/03/92_
21:00 423.0 107.5 95.2 08/03/92
_22:00 423.0 107.5 95.8 08/03/92 23:00 423.1 107.5 95.0.
5 '
4 m
m
+7 TABLE 2.
(Continued)
VCSNS DISCHARGE
. MONTICELLO CIRCULATING WATER DAY
- RESERVOIR DISCHARGE BOTTOM LEVEL TEMPERATURE TEMPERATURE-Date Time (feet) oF
' F-
-.====================================================================
08/04/92 00:00 423.3 107.5 95.8 08/04/92 01:00 423.6 107.4 95.4 08/04/92-02:00 423.8 107.0 94.6 08/04/92 03:00-424.1 106.9 93.6
.08/04/92 704: 00 424.4-106.8 92.6 308/04/92_-
05:00 424.7 106.8 92.4 08/04/92-06'00-425.0 106.8 -
91J6 08/04/92 07,00 425.0 106.8 91.4 08/04/92 08:c?
425.0
_106.8 91.2 08/04/92 09:00 425.0 106.8 91.2 08/04/92.
10:00 425.0 106.9 91.2 08/04/92 11:00 425.0 107.1 91.6 108/04/92 12:00 424.9 107.5 91.6 08/04/92 13:00 424.3 107.7 91.8
~08/04/92-
-14:00 423.8 108.1
,. 0:
.08/04/92 15:00
-423.2 108.5 92.4 08/04/92 16:00 422.7 108.9 92.8 08/04/92:
-17:00 422.'2 109.5 93.6 08/04/92-18:00 421.6 109.5 95.4 08/04/92 119:00 421.1 109.8 97.4 08/04/92-20:00 420.7 109.8 99.6 08/04/92 21:00 420.8 109.7 102.3-08/04/92-22:00 420.8 109.8 104.3 08/04/92 23:00 420.8 110.0 104.7 Y
s
f.
TABLE 2.
(Continued)
VCSNS DISCHARGE MONTICELLO CIRCULATING WATER BAY
-RESERVOIR DISCHARGE BOTTOM LEVEL TEMPERATURE TEMPERATURE Date-
_ Time-(feet)
'F
'F-
= = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = - - = = = = = = = = _ = = = = = = = = = = = = = = = = = = =
-08/05/92 00:00' 421.1 110.0 103.1 08/05/92
-01:00 421.5 109.8 102.1
-08/05/92 02:00_
422.0 109.6 101.9 08/05/92_
03:00-422.5 109.1 101.5
- 08/05/92 04:00 423.0 108.6 100.2 08/05/92 05:00 423.5 108.2 98.4
-08/05/92 06:00-423.9 108.0 96.6 08/05/92 07:00-424.2 107.9 95.4 08/05/92 08:00 424.6 107.7 94.8 H