je

~

CONTAINMENT SYSTEMS 3/4.6.4 COMBUSTIBLE GAS CONTROL

. HYDROGEN ANALYZERS i

LIMITING CONDITION FOR OPERATION 4

3.6.4.1 Two independent containment hydrogen analyzers shall be

~

OPERABLE.

APPLICABILITY: MODES 1 and 2.

ACTION:

With one hydrogen monitor inoperable, restore the inoperable l

a.

analyzer to OPERABLE status within 30 days or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, With both hydrogen monitors inoperable, restore at least one monitor b.

to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />.

SURVEILLANCE REQUIREMENTS 4.6.4.1 Each hydrogen analyzer shall be demonstrated OPERABLE at least once per 92 days on a STAGGERED TEST BASIS by performing a CHANNEL CALIBRATION using sample gases containing:

a. Ten volume percent hydrogen, balance nitrogen, for zero check.
b. Ten volume percent hydrogen, balance nitrogen, mixed with compressed air, for span check.

FARLEY-UNIT 2 3/4 6-19 Amendnient No. 38 Corrected Page h$DO O