Omaha Public Power District 444 South 16th Street Mall July 29, 1992 Omaha. Nebraska 68102-2247 LIC-92-225R 402/636-2000 U. S. Nuclc - Pegulatory Commission ATTN: Document Control Desk Mail Station Pl-137 Washington, DC 20555

Reference:

Docket No. 50-285 Gentlemen:

SUBJECT:

Omaha Public Power District (OPPD) Response to NRC Bulletin No. 92-01, " Failure Of Thermo-Lag 330 Fire Barrier System To Maintain Cabling In Wide Cable Trays And Small Conduits Free From Fire Damage" NRC Bulletin No. 92-01 requested that licensees provide a written notification statin whether or not Thermo-Lag 330 fire barrier systems are installed in their facili ies.

The Fort Calhoun Station (FCS) Safe Shutdown Analysis (EA-FC-89-055, Revision 1) was reviewed to identify areas where credit is taken for 1-hour or 3-hour fire wrap systems.

EA-FC-89-055 takes credit only for a single 1-hour fire wrap system located in the lower electrical penetration room (Fire Area 34A).

Documentation associated with the modification that installed the 1-hour fire wrap in Fire Area 34A identifies it as a 3M brand Interam E50A flexible wrap system. Thus, no loermo-Lag 330 fire barriers are installed at FCS and therefore the compensatory actions requested by NRC Bulletin No. 92-01 are not applicable to GPPD.

If tou should have any questions, please contact me.

Sincerely,

()/ryht h. G. Gates

/

'h Division Manager Nuclear Operations WGG/sel c:

LeBoeuf, law,, Leiby & MacRae J. L. MilLoan, mRC Regional Administratc,, Region IV R. P. Mullikin, NRC Seniv Resident Inspector S. D. Bloom, NRC Acting eroject Manager 1

/

t

/f 9208030180 920729

/

PDR ADOCK 05000285

\\ O fp PDR

.s sa

%g an pe c o-y s

.