l Mr. Riyce W. Grier Offics of Inspectio,1 am! Enforcement Region 1 i
United States Nuclear Regulatory Consission 631 Park Avenue King'of Prussia, PA 19406' r-SUBJEC1: RBORTABt.E OCCURRENCE - PENFT WJTIFICATION 8,
Confirming C. E. Andersen's conversation witt M. Greenaan, Region I, l
United States Kuclear Regulatory Cousission on 1/31/79.
l (i
i
Reference:
Docket No. 050-277/78 1
Peach Botton Units 2.us 3 Technical Specification
Reference:
3.14.A.7
)
Report No. 2-79-7/IP Occurrence Date: 1/31/79 i
Identificationyf Occurrence:
SGTSofire protection systen out of senice for approx astely 8 days.
Q,nditions Pr.or.to Occurrence:
Both units operating at 160 percent pow'r.
Apparent Cause:
I Personnel error t
_ Malysis of Occurrence:
Cn 1/23/79, the SGTS fire syster. was blocked to perform surveillwce tests on snake detestors. A permit was issued for this work. Due to
)
g p oblems involved with the surveillance testing, the job could not be
- J tw ccupletal at that tint and the permit was cleared. The problem occurred
(\\j when the permit was inyroperly cleared and the main valve feeding the N
fire systes for this tres was sistakenly left closed. Qi 1/31/79, it
.g f was again requested that the fire system for pa:t of the 505 be blocke:
i j
0--
for surveillance testing. The person applying this permit discovered i
that the mala valve was closed when he arrived in the area. This vala k
was immediately ngxi and the incident reported to shift supervisits.
l t
L\\
anths the perled of & dar.1 uhen the fire systes was det J
- ?ff' N r ?L + fl'. m,.. n?e
", ' L' h Y b { & g - f^h h? h Nl'?f ?.. ~ ~
f
.Q$Y Q
^
f' f
q.,._
y:
- x
9 n
1
,a
~.
. p CLg "
s inopernhie, the fire detection system for this area was fully (perable and nmrous people were in and out of this area on a routine basis.
Fcr these reasons, the safety significance of this event is minimal.
CorrectiveJtetion:
The r2re system was placed back in service insediately upos discovery of this event..
The persarc 4'irectly involved hith the error is un-blocking the original permit was instructed in the proper method to be used when i:learing permits to assure that the system is properly returned to s.orvice.
Further corrective action vill be taken when the investigation of this event is completed.
~
?revie.ts Failures:
Reportrios.2-79-2/IPand2-79-6/AP.
Verytrulyyours, f.f.d Y