Clarifies Info Provided in Re Resolution of W-2 Switch Deficiency at Facilities,Per IE Bulletin 80-20 & Deficiency Rept 80-01.Exclusion of Switches from Replacement Program Justified,Per Listed Conditions
ML20096F967
Person / Time
Site: Byron, Braidwood, 05000000
Issue date: 08/29/1984
From: George Alexander
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
80-01, 80-1, 9124N, IEB-80-20, NUDOCS 8409100292
Download: ML20096F967 (5)


Text

/

C monwealth Edison

/

) One First National Plaza. Chicago. Ithnors k7 Address Reply to: Post Office Box 767

\\

Chicago. Illinois 60690 August 29, 1984 Mr. James G.'Keppler Regional Administrator U.S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137

Subject:

Byron Station Units 1 and 2 Braidwood Station Units 1 and 2 Intermittent Contact Operation of Type W-2 Switch IE Bulletin 80-20 and 50.55(e) 80-01 NRC Docket Nos. 50-454/455/456/457 References (a):

April 10, 1981 letter from T. R. Tramm to J. G. Keppler (b):

April'30, 1981 letter from T. R. Tramm to J. G. Keppler

Dear Mr. Keppler:

This is to clarify information provided in reference (b) regarding the resolution of the W-2 switch 50.55.e) deficiency at

(

Byron and Braidwood.

Reference (b) indicated that all safety related W-2 switches would be replaced with switches manufactured to revised assembly and electroplating procedures.

A further

-limitation on this statement should have been included.

The limitation should have stipulated that all safety related W-2 switches would be replaced unless justification could be provided to demonstrate that replacement of.the control switches was not required in response to IE'Bulletin 80-20.

We believe that the exclusion of switches from the replacement program can be justified by any of the following conditions:

1.

The switch is of the maintained contact type, not the

" spring return of neutral" type described in IE Bulletin Number 80-20.

2.

A failure of the " neutral" position contact will not affect

-the operation of safety-related equipment-because the contact is not used in a control circuit.

3.

The switch does not perform a safety-related control function (i.e. ammeter switch, voltmeter switch, etc.).

L @b

&Il \\

y 8409180292840829gonsacnowoopgg g

3

a

~ 4.

The switch is used'for testing purposes only (i.e. not normal control).

5.

The switch is located on a switchgear cubicle and is functional'only when the breaker is in the test position.

Attached is a three page list of safety-related switches which were not replaced.

The list'contains the switch designation, justification for exclusion, and switch location.

To the best of my knowledge and belief the statements contained above true and correct.

In some respects these statements are:not based on my personal knowledge but upon information furnished by other Commonwealth Edison employees, consultants, and contractors.- Such information has been reviewed in accordance with Company practice and I believe it to be reliable.

Please address any questions regarding this matter to this office.

Very truly yours,

%.t.

4 G. L. Alexander Nucler Licensing Administrator Attachment' cc:

US NRC, Document Control Desk Washington, DC 20555 Director of Inspection and Enforcement Resident Inspector - By/Bw 9124N'

m

^

f f

W2 Switches Excluded.from Replacement Program

~ l-1 Commonwealth-Edison Company Byron /Braidwood Station Units'1 and 2

~ Switch Designation ~

Justification Location-43ACl 1, 2 Diesel Gen. PanelL1(2)PLO7J 43AC2-1,. 2 Diesel Gen. Panel.l(2)PLO7J

~

43QH 1, 2 Diesel Gen. Panel 1(2)PLO7J

'I

.43QPP 1, 2 Diesel-Gen.' Panel 1(2)PLO7J.

43JWH-1,. 2 Diesel Gen. Panel l(2)PLO7J 43JWCP 1, - 2 Diesel Gen. Panel 1(2)PLO7J

.43AD1 1, 2 Diesel Gen. Panel 1(2)PLO83-43AD2 1, 2 Diesel ~ Gen. Panel 1(2)PLO8J 43QH' 1, 2 Diesel Gen. Panel 1(2)PLO8J 43QPP 1, 2 Diesel Gen. Panel 1(2)PLO8J 143JWH'.

'1, 2

Diesel 1 Gen.-Panel 31(2)PLO8J

433WCP.

1, 2 Diesel Gen. Panel 1(2)PLO8J 43CM

'l Diesel Gen. Panel 1(2)PLO7J 43RM-1 Diesel Gen. Panel.l(2)PLO7J 430P 1

Diesel Gen.' Panel 1(2)PLO7J 43CF 1

Diesel Gen ~.~ Panel >1(2)PLO7J 43SC1 2

Diesel Gen. Panel ~tl(2)PLO7J

.43VC.

2 Diesel Gen. Panel 1(2)PLO7J 43A 1

-Diesel Gen. Panel-1(2)PLO7J 43V 1, 3 Diesel Gen. Pane 1Ll(2)PLO7J 43CM 1

Diesel Gen. Panel 1(2)PLO8J-43RM' 1

Diesel Gen. Panel 1(2)PLO8J 43UP 1.

Diesel Gen. Panel 1(2)PLO8J 43CH 1

Diesel Gen. Panel 1(2)PLO8J

-43CF-1-

Diesel Gen. Panel 1(2)PLO8J

?43SC 2-Diesel Gen. Panel'l(2)PLO8J 43VC-1!

Diesel-Gen. Panel ~1(2)PLO8J.

43A 1

Diesel. Gen. Panel 1(2)PLO8J

43V' 1,c3 Diesel Gen. Panel 1(2)PLO8J 1HS-D0003(43F01) 1, 2 Diesel Gen. Panel 1(2)PLO7J' clHS-D0004(43F01):

1, 2 Diesel Gen. Panel 1(2)PLO8J 1HS-D0005(43F02) 1,;21 Diesel Gen. Panel 1(2)PLO7J 1HS-D0006(43F02) 1, 2 Diesel Gen. Panel 1(2)PLO8J LlHSeD0039(43F07) 1

. Diesel Gen. Panel 1(2)PLO7J 1HS-D0040(43F07) 1.

Diesel Gen. Panel 1(2)PLO8J-CSlA.

1, 4 Seg. & Act'. Cabinet.1(2) PAIL 3J CS2A 1, 4 Seg. & Act. Cabinet'l(2) PAI13J

'CSlB 1,J4 Seg. & Act. Cabinet 1(2) PAI14J-CS2B 1, 4 Seg. & Act. Cabinet-1(2) PAIL 4J 43SW l

Diesel Gen. Panel 1(2) PLO7J

. 43SW l

Diesel Gen. Panel 1(2) PLO8J 162 Volt Switch 1, 3 125V DC Dist. Center 1(2)DC05E LW2 Volt Switch 1, 3 125V DC Dist. Center 1(2)DC06E l

i

Commonwealth Edison Company Byron /Braidwood Station Units 1 and 2-Switch Designation Justification Location LSC 2, 5 Switchgear 1(2)AP05EA LSC 2, 5 Switchgear 1(2)AP05EB LSC 2, 5 Switchgear 1(2)AP05EC LSC 2, 5 Switchgear 1(2)AP05ED LSC 2, 5 Switchgear 1(2)AP05EF LSC 2, 5 Switchgear 1(2)AP05EG LSC 2, 5 Switchgear 1(2)AP05EH LSC 2, 5 Switchgear 1(2)AP05EJ LSC 2, 5 Switchgear 1(2)AP05EK LSC 2, 5 Switchgear 1(2)AP05EL LSC 2, 5 Switchgear 1(2)AP05EM LSC 2, 5 Switchgear 1(2)AP05EN LSC 2, 5 Switchgear 1(2)AP05EP LSC 2, 5 Switchgear 1(2)AP05ER LSC 2, 5 Switchgear 1(2)AP05ES LSC 2, 5 Switchgear 1(2)AP05ET LSC 2, 5 Switchgear 1(2)AP05EU LSC 2, 5 Switchgear 1(2)AP05EV LSC 2, 5 Switchgear 1(2)AP06EA LSC 2, 5 Switchgear 1(2)AP06EB LSC 2, 5 Switchgear 1(2)AP06EC LSC 2, 5 Switchgear 1(2)AP06ED LSC 2,

5 Switchgear 1(2)AP06EF LSC 2, 5 Switchgear 1(2)AP06EG LSC 2, 5 Switchgear 1(2)AP06EH LSC 2, 5 Switchgear 1(2)AP06EJ LSC 2, 5 Switchgear 1(2)AP06EK LSC 2, 5 Switchgear 1(2)AP06EL LSC 2, 5 Switchgear 1(2)AP06EM LSC 2, 5 Switchgear 1(2)AP06EN LSC 2, 5 Switchgear 1(2)AP06EP '

LSC 2, 5 Switchgear 1(2)AP06EQ LSC 2, 5 Switchgear 1(2)AP06ES LSC 2, 5 Switchgear 1(2)AP06ET LSC 2, 5 Switchgear 1(2)AP06EU L43 1, 5 Switchgear 1(2)AP05EA L43 1, 5 Switchgear 1(2)AP05EB L43 1, 5 Switchgear 1(2)AP05EC L43 1, 5 Switchgear 1(2)AP05E0 L43 1, 5 Switchgear 1(2)AP05EF L43 1, 5 Switchgear 1(2)AP05EG L43 1, 5 Switchgear 1(2)AP05EH

Commonwealth Edison Company Byron /Braidwood Station Units 1 and 2 Switch Designation

. Justification Location L43 1, 5 -

Switchgear 1(2)AP05EJ L43-1, 5 Switchgear 1(2)AP05EK L43 1, 5 Switchgear 1(2)AP05EL L43 1, 5 Switchgear 1(2)AP05EM L43 1, 5 Switchgear 1(2)AP05EN L43 1, 5 Switchgear 1(2)AP05EP L43 1, 5 Switchgear 1(2)AP05ER L43 1, 5 Switchgear 1(2)AP05ES L43' 1, 5 Switchgear 1(2)AP05ET L43 1, 5 Switchgear 1(2)AP05EU L43 1, 5 Switchgear 1(2)AP05EV L43 1, 5 Switchgear 1(2)AP06EA L43 1, 5 Switchgear 1(2)AP06EB L43 1, 5 Switchgear 1(2)AP06EC L43 1, : 5 Switchgear 1(2)AP06ED L43 1, 5 Switchgear 1(2)AP06EF L43 1, 5

_Switchgear 1(2)AP06EG L43 1, 5 Switchgear-1(2)AP06EH L43 1, 5-Switchgear 1(2)AP06EJ L43 1, 5 Switchgear 1(2)AP06EK L43 1, 5 Switchgear 1(2)AP06EL.

L43 1, 5 Switchgear 1(2)AP06EM L43 1, 5 Switchgear.1(2)AP06EN L43 1, 5 Switchgear 1(2)AP06EP L43 1, 5 Switchgear 1(2)AP06EQ L43 1, 5 Switchgear 1(2)AP06ES L43 1; 5

'Switchgear 1(2)AP06ET L43 1, 5 Switchgear 1(2)AP06EU 9124N