l L. _ -

Commonwealth Edloon l

LaSa!!e County Nuclear Station l

2601 N. 21st. Rd.

l-Marseillet, Illinois 61341

, Telephone 815/357-6761 May 14, 1992 l

t Mr. A. B. Davis Region III Administrator U.S. Nuclear-Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Dear Sir This Special Report is submitted in accordance with LaSalle Unit 1 Operating License NPF-11, Technical Specification 3.8.1.1 and 6.6,C regarding the Unit 1, B Diesel Generator (DG,1E23S001)

On April 14, 1992, with Lash 11e Unit 1 in mode 1 (RLrN),.the IB Diesel Generator.

tripped on reverse Power when the output breaker (ACB~1433) was opened. The cause of this event was attributed to the performance of a Nuclear Station Operator (WSO) trainee who was operating the ID DG.

An attempt was made to open the output breaker with 1000Kvars and 200Kwatte of load still being a

supplied by the IB D,G.

E en the output breaker opened the IB DG exper16. iced-large swings.in voltage which in turn tripped the engine on reverse power.

The IB DG was started end loadod again per LaSalle Operating Surveillance-Diesel Generator-Monthly 3 (LOS-DG-M3).

When offlooded this time the vars and watts were. lowered to 200Kvars and 200Kwatts before the output breaker was opened successfully. A revialon will be initiated for LOP-DO-03, 06, 09 " Shutdown of all Diesel Generators" to lower Kvara before opening the output breaker. Action Item Record #373-251-92-00065 will track the completion of this revision.

3 At the time of the event, the IB DG was being tested - for it.

mthly 1

oporational load run (LOS-DG-M3) and was immediately reteste-per thin.

pro 6adure.

9 a /f,/,f v 8

G. J.'Diederich

. ft/ Station Manager LaSallo/ County Station GJD/JR/tsh cc: Nuclear Licensing Admini;.trator NRC Resident Inspector NRC Document Control Dork

(-

INPO - Records Center' t

IDNS Resident-Inspector

-200053 c

g(

9205210079 920514 PDR ADOCK 05000373 8

PDR