l L. _ - -

Commonwealth Edloon l LaSa!!e County Nuclear Station l 2601 N. 21st. Rd.

l- Marseillet, Illinois 61341

, Telephone 815/357-6761 May 14, 1992 l

t Mr. A. B. Davis Region III Administrator U.S. Nuclear-Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137 Dear Sir This Special Report is submitted in accordance with LaSalle Unit 1 Operating License NPF-11, Technical Specification 3.8.1.1 and 6.6,C regarding the Unit 1, B Diesel Generator (DG,1E23S001)

On April 14, 1992, with Lash 11e Unit 1 in mode 1 (RLrN),.the IB Diesel Generator.

tripped on reverse Power when the output breaker (ACB~1433) was opened. The cause of this event was attributed to the performance of a Nuclear Station Operator (WSO) trainee who was operating the ID DG. An attempt was made to open the output breaker with 1000Kvars and 200Kwatte of load still being a supplied by the IB D,G. E en the output breaker opened the IB DG exper16. iced-large swings .in voltage which in turn tripped the engine on reverse power.

The IB DG was started end loadod again per LaSalle Operating Surveillance-Diesel Generator-Monthly 3 (LOS-DG-M3). When offlooded this time the vars and watts were . lowered to 200Kvars and 200Kwatts before the output breaker was opened successfully. A revialon will be initiated for LOP-DO-03, 06, 09 " Shutdown of all Diesel Generators" to lower Kvara before opening the output breaker. Action Item Record #373-251-92-00065 will track the completion of this revision.

3 At the time of the event, the IB DG was being tested - for it . mthly 1 oporational load run (LOS-DG-M3) and was immediately reteste- per thin.

pro 6adure.

a /f,/,f v 9 8 G. J.'Diederich

. ft/ Station Manager LaSallo/ County Station GJD/JR/tsh cc: Nuclear Licensing Admini;.trator '

NRC Resident Inspector NRC Document Control Dork

(- INPO - Records Center' t IDNS Resident-Inspector

-200053 c