ML20095L383

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept,Item 120 Re NPS Industries,Inc Pipe Support Components W/Same Part Number.Initially Reported on 840319.NPS Industries Changed Physical Dimensions of Parts, But Parts Retained Same Part Number
ML20095L383
Person / Time
Site: Fermi 
Issue date: 08/15/1984
From: Jens W
DETROIT EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
120, EF2-69289, NUDOCS 8408300223
Download: ML20095L383 (2)


Text

{{#Wiki_filter:- s 8 Wayne H. Jens h V5ce Premdent i Nxh3r Opsations Detroit Edison =400 North Dix e H,ghay 6 =e'"* "" ^eeust 15, 1984 l EF2-69289 Mr. James G. Keppler Regional Administrator Region III U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

Reference:

(1) Fermi 2 NRC Docket No. 50-341 (2) Letter, W. H. Jens to J. G.

Keppler, April 19, 1984, EF2-60253

Subject:

Final Evaluation of 10CFR50. 55(e) Item 120 "NPS Industries Inc. Pipe Support Components With the Same Part Number" Detroit Edison has completed its investigation of Item 120 and has determined that it is not reportable under 10CFR 50. 55 ( e ). This item concerned NPS Industries, Inc. (NPSI) supplying different sizes of pipe support components which utilized the same part number. Item 120 was origin-ally reported as a potential deficiency on March 19, 1984, and was subsequently documented in Reference (2). This situation was discovered during installation of two NPSI sway strut rear brackets. Two support assembly brackets had the same part number but different dimensions. The plate dimension (the part fastened to the structure) for one bracket was 10" x 10" and the plate for the other bracket (a new part) was 7" x 9". It was subsequently learned that NPSI had changed the physical dimensions of other parts, issued new data sheets, and shipped the support assemblies to customers. The parts retained the same part number, but the parts' size, thickness, etc. may have changed. j 8408300223 840815 PDR ADOCK 05000341 S PDR i l AUG 2 0 198e 9;0 o o

= m -; g. > 6.-(* p.k A , Keppler Mr. James G. ' August 15, 1984 EF2-69289 Page 2' . Detroit Edison-purchased both old and new support assemblies ~ 'from NPSI. -Although the size or thickness of a component ~ within a support assembly had changed, these changes did not reduce the rated capacity of the. support assemblies. These changes would routinely have been-made-under.NPSI's quality assurance'pr'o' ram which'had;be'en reviewed and accepted by ~ g ~ -Detroit Edison. -Der.roit. Edison has! concluded that this situation', were it to have remained uncorrected, would not -.have adversely.affected-the-safe operation of-the plant. t. This is Detroit Edison's~ final report on this item. If you-have questions concerning this matter, ple'ase contact Mr. Lewis'P. Bregni,-(313).586-5083. - Sincerely, / Mr.-P. M. Byron f, $L[ I Mr. R. C. DeYoung Mr. R. C. Knop / 4 4 'l I .l H 'CW-f e =w9}}