Beaver Valley Power Station Sh p ng PA 15077-0004 (412) 643-8069 FAX GEORGE S. THOMAS Division Vice President Nuclear Services Nuclear Power Ovvialon December 4,1995 U. S. Nuclear Regulatory Commission Attention: Document Control Desk Washington, DC 20555-0001 j

Subject:

Beaver Valley Power Station, Unit No. I and No. 2 BV-1 Docket No. 50-334, License No. DPR-66 BV-2 Docket No. 50-412, License No. NPF-73 Typed Pages for Technical Specification Change Request Nos. 221 and 90 Typed, final technical specification pages for Technical Specification Change Request Nos. 221 and 90 are enclosed as Attachments B-1 and B-2, respectively. Also, summary descriptions of non-intent editorial changes _which have been incorporated into the specifications are provided in Attachments A-1 (Unit No.1) and A-2 (Unit No. 2).

The enclosed technical specification pages have been amended to reflect non-intent editorial changes. The changes denoted in Attachments A-1 and A-2 are the result of a conference call, conducted on October 12,1995, between the NRC and members of my staff, concerning the change request noted above. This submittal represents the revised proposed wording to resolve tle NRC reviewer's concern on the original proposed wording submitted on July 20,1991 In addition, minor non-substitutive format changes have been incorporated in this submittal that have no affect on the intent of the technical specification requirements.

If you have any questions regarding the attached information, please contact Mr. G.

S. Sovick at (412) 393-5211.

Sincerely, j Yms Ge rge S. Thomas Attachments c:

Mr. L. W. Rossbach, Sr. Resident Inspector Mr. T. T. Martin, NRC Region I Administrator

[M0 Mr. D. S. Brinkman, Sr. Project Manager s

t\\

1

)

.~~.-

9512110085 951204 PDR ADOCK 05000334

-. _L_

PDR _,

AFFIDAVIT FOR APPLICATION OF AMENDMENT COMMONWEALTH OF PENNSYLVANIA)

) SS:

COUNTY OF BEAVER

)

Subject:

Beaver Valley Power Station, Unit No.1 and No. 2 BV-1 Docket No. 50-334, License No. DPR-66 BV-2 Docket No. 50-412, License No. NPF-73 Typed Pages for Technical Specification Change Request Nos. 221 and 90 Before me, the undersigned notary public, in and for the County and Commonwealth aforesaid, this day personally appeared George S. Thomas, to me known, who being duly sworn according to law, deposes and says that he is Division Vice President, Nuclear Services of the Nuclear Power Division, Duquesne Light Company, he is duly authorized to execute and file the foregoing submittal on behalf of said Company, and the statements set fonh in the submittal are true and correct to the best of his knowledge, information and belief.

  • v -C*4* d N n.s George S. Thomas Subscribed and sworn to before me on thisf day of 46L/7L[24,/996

\\

AW4 Zbit yhsj piihlic i

I tuarusoal vo Beaver sc-we m va

    • .cm.eerroyevaria% g %

ATTACHMENT A-1 Unit 1 Non-Intent Changes PAGE(S)

CHANGE DESCRIPTION 3/48-3 1.

Revise action "d" by adding "and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />." following the words "the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />."

3/4 8-4, and 2.

Revise footnote (3) to read as follows:

(3) The values for voltage and frequency are analysis values.

3/4 8-4a These value bands shall be appropriately reduced to account i

for measurement uncertainties.

3/4 8-4a 3.

Revise footnote (6) to read as follows:

(6) The frequency limits apply for the diesel generator at full accident loading. An engineering evaluation of the test data at lower loads can be performed to demonstrate operability.

i B 3/4 8-3 4.

Add to Bases:

Footnote (6) pennits an engineering evaluation to be performed if the frequency limits of SR 4.8.1.1.2.b.3.b are not met.

The frequency limits prescribed in SR 4.8.1.1.2.b.3.b are based on full load conditions. Since SR 4.8.1.1.2.b.3.b is normally performed at less than full loading conditions, the resultant generator frequency may exceed the required frequency value rar;;c J.m to the design of the diesel generator governor, especially during lower loading. Under lase conditions, it is acceptable to examine the frequency

]

response vs. loading and by an engineering evaluation, determine that the governor is responding properly and would fall within the required frequency band while at full accident loading.

The engineering evaluation consists of l

comparing previous voltage, frequency and power plots with the current plots of these same parameters. By comparing the above data, proper governor response can be verified.

Based on governor response and the current governor droop setting, the frequency value obtained during performance of SR 4.8.1.1.2.b.3.b can be evaluated to ensure the frequency limits of SR 4.8.1.1.2.b.3.b at full accident loading would be met.

J i

y-e.

ATTACIIMENT A-2 Unit 2 Non-Intent Changes PAGE(S)

CIIANGE DESCRIPTION 3/48-3 1.

Revise action "d" by adding "and in COLD SHUTDOWN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />." following the words "the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />."

3/48-4,3/48-5, 2.

Revise footnote (3) to read as follows:

and 3/4 8-5b (3) The values for voltage and frequency are analysis values.

These value bands shall be appropriately reduced to account for measurement uncertainties.