ML20094S396

From kanterella
Jump to navigation Jump to search
Forwards Rev 7 to Sar.Rev Resulted from Need to Make Certain Minor Changes in Descriptions of Resins Used in Primary Coolant Sys Demineralizer & Makeup Water Sys Demineralizer
ML20094S396
Person / Time
Site: 05000083
Issue date: 04/03/1992
From: Vernetson W
FLORIDA, UNIV. OF, GAINESVILLE, FL
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
Shared Package
ML20094S399 List:
References
NUDOCS 9204150014
Download: ML20094S396 (2)


Text

.

NUCLEAR ENGINEERIND SCIENCES DEPARTMENT Nuclear Reactor Focility University of Florido I I t:e.v.=* a.o m ew 2"'.",$M*

..no.. i... um April 3,1992 UFIR Safety Analysis Report Revision 7,4/92 U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Attn: Document Control Desk Re:

University of Florida Training Reactor Facility Ucense: R 56, Docket No. 50-83 Gentlemen:

- The enclosed package contains Revision 7 pages for the UFTR Safety Analysis Report dated January,1981 submitted as part of our relicensing effort. Revision 7 consists of changes to two pages. The revision has resolted from the need to make certain minor changes in the descriptions of the resins used in the primary coolant system demineralizer and makeup water system demineralizer as well as the need to make a change in the secondary cooling system pump. All changes have been reviewed by UFTR management and the UFTR Safety Review Subcommittee and are not considered to involve any unreviewed safety question or to impact the UFTR Safety Analysis as outlined below; all text changes are denoted by vertical lines in the right hand margin of the attached affected replacement pages. Reasons for all text changes are explained in the following paragraphs.

The first change is included on Page 5 8 to allow the use of an equivalent deep well pump per the slightly changed description in Section 5.2 describing the UFTR Secondny Cooling System. This change to a more efficient. pump was necessitated by the failure of the previous pump in February,1992 and the unavailability of an exact replacement; it was evaluated and determined not to involve any unreviewed safety questions per 10 CFR 50.59 Number 92-01.

The second change is included on Page 9-6 because the Amberlite IRN 150, nuclear-grade resins specified for use in the Demineralized Water Makeup System and the primary coolant.

Purification System are no longer available. These systems were converted to utilizing equivalent Purolite NRW-37 resins in January,1991; however, the changes in Section 9.2.3 and Section 9.2.4 are included to allow the use of any equivalent resin. In this way any future substitution can be made following an in-house evaluation of equivalency. This change was evaluated and determined not to involve any unreviewed safety question per 10 CFR 50.59 Number 91-01, i '. P. U '

6 gh p>n8n usa),4

,\\

PDR

I U. S. Nuclear Regulatory Commission Wasidngton, D.C. 20555 April 3,1992 Page 2 As indicated, these Revision 7 changes have been fully reviewed by UFTR Management and the Reactor Safety Review Subcommittee to involve no unreviewed safety question per 10 CFR 50.59 cvaluations and determinations and so are not considered to relax tlm requirements for assuring protection of the health and safety of the public and of the reactor facility. The changes simply update the SAR.

The entire enclosure consists of one(1) signed originalletter of transmittal with enclosure plus ten (10) copies of the entire package. If further infortnation is required, please advise.

Sincerely, 6,/

William G. Vernetson Associate Engineer and Director of Nuclear Facilities WGV/p Enclosures cc:

U.S. NRC Region II R. Piciullo Reactor Safety Review Subcommittee 0., Y)L w vkku Notary

(~

IYate' 7

s I

.