ML20094P735
| ML20094P735 | |
| Person / Time | |
|---|---|
| Site: | Byron |
| Issue date: | 11/21/1995 |
| From: | Wozniak D COMMONWEALTH EDISON CO. |
| To: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| BYRON-95-5157, NUDOCS 9511300081 | |
| Download: ML20094P735 (2) | |
Text
_.
i Comnutnwealth }Miwan Comp.iny g ';
-f II) ton Generating Station is O[
4150 North German Church Road i
}
11yron, !!.6101D9791 Tc[ 815 234 5 6 il November 21,1995
~PRIOTtITY P,00 TING
{ sed I Fi t LTR: BYRON-95-5157 FILE: 3.11.0530 S'h h.:-
1.%
N;LM vg+ /
.2fioS [n:t _ _..
ul M
n" -
Mr. Hubert i Miller EJi_
Regional Administrator DRMA 1.l.__.[._.___
U.S. Nuclear Regt.latory Commission (Region Ill) 801 Warrenville Road iN ~_@$'i_... _
1 Lisle, Illinois 60532-4351 i
SUBJECT:
Byron Station Unit 1 Application of Steam Generator F* Criteria Byron Unit 1 Mid-Cycle Outage (October-November 1995)
Dear Mr. Miller:
This letter is to inform the Commission of Steam Generator tubes that were left in service as a result of applying the F* repair criteria during the Byron Unit 1 Cycle 7 mid-cycle eddy current inspection. This information is being reported pursuant to Facility Operating License NPF-37, Appendix A, Technical Specification 3/4.4.5.5.e.
In accordance with Specification 3/4.4.5.5.e, the F* report shall include:
- 1) Identification of F* Tubes, and
- 2) Location and size of the degradation.
A total of two (2) tubes in all four steam generators had the F* repair criteria applied.
They are as follows:
Location From SG Row-Column Too of Tubesheet Size
- C-11 - 54
-3.36 inches 2.01 volts C
35 - 71
-3.14 inches 2.32 volts The size of the degradation was reported from the rotating pancake coil operating at a frequency of 300 kHz.
g
' b-O /
9511300001 951121 PDR ADOCK 05000454
/
G P D_R _ _.,
p:\\sec\\byritr\\95-5157. doc f40V 2 41995 A limcom Company J
- ;h 4. <-
s; if'
- Shduld ou have_ any questions regarding this matter, please contact Mr. J. R.1 Smith at.
'(815) 234-5441, extension 2604.
D. B. Wozniak U.
" Site Engineering Manager
. Byron Nuclear Power Station
' DBW/cb cc:
- G. Dick, Byron Project Manager - NRR H. Peterson, Senior Resident inspector - By on Document Control Desk - NRR
= Office of Nuclear Facility Safety -IDNS
- K. Graesser.
K. Passmore
'J. Blomgren -
M. Lesniak --
'L' Zech Site Engineering File pi\\sec\\byrttr\\95-5157.do.: