Special Rept Spr 84-011:on 840703 & 11,invalid Failures Experienced on Diesel Generator XEG-0001A,unit A.Caused by High Jacket Water Temp Resulting from Control Valve Malfunction.Cooling Sys Drained,Disassembled & Cleaned
ML20094G514
Person / Time
Site: Summer South Carolina Electric & Gas Company icon.png
Issue date: 08/02/1984
From: Dixon O
SOUTH CAROLINA ELECTRIC & GAS CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
SPR-84-011, SPR-84-11, NUDOCS 8408130340
Download: ML20094G514 (3)


Text

.

..O SOUTH CAROLINA ELECTRIC & GAS COMPANY

,Ost OFFICE 7e4 COLUMBIA. SOUTH CApouNA 29218

'I n9: I1

%T,*,,' *:,i"-

August 2, 19E4 uucu.. o,...no~.

Mr. James P.

O' Reilly Regional Administrator U.S. Nuclear Regulatory Commission Suite 2900 101 Marietta Street, NW Atlanta, GA 30323

SUBJECT:

Virgil C. Summer Nuclear Station Docket No. 50/395 Operating License No. NPF-12 Special Report (SPR 84-011)

Dear Sir:

Please find attached a Special Report for The Virgil C.

Summer Nuclear. Station.. This Report is being submitted pursuant to Regulatory Guide 1.108, " Periodic Testing of Diesel Generator Unit,"

Revision 1, August 1977, Section C.3.b.

Should there be any questions, please call us at your convenience.

Very truly yours, O. W.

xon, r

RJB:OWD/lcd Attachment K.

E. Nodland cc:

V.- C. Summer T.

C. Nichols, Jr./O. W. Dixon, Jr.

R. A.

Stough G. Percival

'E.

H. Crews, Jr.

C. W. Hehl E. C. Roberts J.

B. Knotts, Jr.

W. A. Williams, Jr.

I&E Washington D. A. Nauman Document Management Branch Group Managers INPO Records Center O. S. Bradham C. A.

Price ANI Library NPCF.

D. A.

Lavigne J..F. Heilman File C. L. Ligon (NSRC) t

-8408130340 840802 OFFICIAL Copy PDR ADOCK 05000395 PDR G

SW3/ %

F s>

y;

~

Mr. James P. O'_ Reilly

~

SPR 84-011-Page Two

August-2,7 1984'

'On July.3, 1984, during scheduled surveillance activity, and July.ll, 1984, during post maintenance surveillance, testing, the Licensee experienced : invalid failures on Diesel-Generator' Unit " A",

XEG-0001A.'.Both invalid failures 'were because of High Jacket. Water

. Temperature resulting from the malfunctioning of the jacket water temperature control valve.

Following_the. unit shutdown on July 3, 1984, the jacket. water cooling. system was drained; the temperature control valve was disassembled, cleaned, and reassembled.

The-jacket water cooling system was filled.and vented, the unit was satisfactorily tested and declared operable at 1240 hours0.0144 days <br />0.344 hours <br />0.00205 weeks <br />4.7182e-4 months <br />, July 3,1984, total time inoperable ~- 9 hours1.041667e-4 days <br />0.0025 hours <br />1.488095e-5 weeks <br />3.4245e-6 months <br /> 33 minutes.

Th'a Licensee voluntarily entered the Limiting Condition for

-_ Operation as_noted in Action Statement (s) of Technical Specification 3.' 8.'1,

" A. C.: Systems," at 0530 hours0.00613 days <br />0.147 hours <br />8.763227e-4 weeks <br />2.01665e-4 months <br />, July ll, 1984 for. maintenance on Diesel Generator." A", (replacement of No. 1 injector nozzle).

At approximately 1630 hours0.0189 days <br />0.453 hours <br />0.0027 weeks <br />6.20215e-4 months <br />, the same'date,-the unit-was started for post maintenance testing.

The unit shutdown at approximately:1640 hours because of High Jacket Water Temperature.

The_ jacket water cooling system was. drained and t flushed, 'the temperature Leontrol valve internals were replaced, the unit was tested and declared operable at 2315 hours0.0268 days <br />0.643 hours <br />0.00383 weeks <br />8.808575e-4 months <br />, July 11, 1984,

. total time inoperable - 17 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br /> 45 minutes.

fj On June 14,-1984, the Licensee submitted Special Report 84-007 b

.which identified a failure of the. jacket water temperature control valve on June 1, 1984.- It is suspected that the temperature excursion caused by fouling damaged the _ valve internals and

.contributedEto_the invalid failures described herein.

i b

The Licensee has had zero valid failures on the subject unit,- and I

the current surveillance test interval is every 31 days.

p i.

4 1

I,..

6

~

t-ENGINEERS Serial Engineer eos TECHNICAL WORK RECORD Date 7/.rr/sy

~

Project Title tvAc pd.) R,o 4 gv-os Tab (

Page f of a capct tw.t a o.c..

s k l-M.'f %h\\- Mslev Ternf.

v<r;FoL%%

d AJs u Is k

  • ) ) kywkr. encers Eora

>N enress of' I rrY has 6.c-Aova so /,mp Mc 4/,-mo1Ahu wM eIswk ( goustq'nIh)

,,4 ).b~ TeH

c. jew Thermothk Cowhol klve. (Ad Ned STC) x) Tuth

's s c.ov sidt d 4 0 4 8 b s cwwu.

dmAivy,a

  • n3 9 s J s/y ow t i

~,I p m s, _ e -

l eug,# ou r=pc& w'.rl kg eg,ve..

l\\lo c0rnorrd o*- der # 'O~d cqu 36 md oa b.I CI I n.).t& &lm e( t w o.6 rA,mesAk. W h/ Ales, e of luk'.svy iysk,

cass d

[N,

~

l i

Verification Approval Type of Verification Verifier Signature /Date Signature /Date

-