- p WAEHINGTON. D C. 20666 VIRGINIA ELECTRIC AND POWER COMPANY
-DOCKET NO. 50-280 SVRRY-POWER STATION. UNIT NO. 1 AMENDMENT TO FACIllTY OPERATING LICENSE Amendment No.166 License No. DPR-32 1.
The Nuclear Regulatory Commission (the Comission) has found that:
A.
The application for amendment by Virginia Electric and Power Company
-(thelicensee) dated. December 19, 1991, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter-1; B.. The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance (1) that the activities authorized by this amendment can be conducted without endangering the health and o
safety of the public, and-(ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be-inimical to the connon
- defense and security or to the health and safety of the public; and E.
The issuance:of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
l-9202130069 920207 DR -ADOCK 0500 0
n
4,
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.8 of facility Operating License No. OPR-32 is hereby amended to read as follows:
(B) Technic _al Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No.166
, are hereby incorporated in the license.
The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days.
FOR THE NUCLEAR REGULATORY COMMISSION f
e lHe[b f)
- Berkow, tor Project Direct'> rate 11-2 Divibion of Reactor Projects - 1/11 OfficT of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications L
Date of Issuance: February 7, 1992 l
0 8 %
6 S
UNITED STATES 5
- j NUCLEAR REGULATORY COMMISSION WASHINGTON. D C. 20t46 g
VIRGINIA ELECTRIC AND POWER COMPANY QQCKET NO. 50-281 SURRY POWER STATION. UNIT NO. 2 6ti@DMENT TO FACILITY OPERATING LKIR$1 Amendment No.165 License No. OPR-37 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment by Virginis. Electric and Power Company (thelicensee dated December 19, 1991, complies with the standards-and requiremen)ts of the Atomic Energy Act of 1954, as amended (the Act) and the Commission's rules and regulations set forth in 10 CFR Chapter it-B.
The~ facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.-
There is reasonable assurance (i) that the activities authorized by-this amendment can be conducted without endangering the health and safety _ of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations;
-0.
The issuance of this amendment will not'be' inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.-
t w
-.--*.-,,.-m,
--,.,,,e,.y
,m..
.w~,y...-
-,,,...a~,-
,,_-.----.-e r.-,.-
rr,*
r.-
e r
.r. -.,
w-
2-2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.0 of iacility Operating License No. OPR-37 is hereby amended to read as follows:
(B) Technical Soecificationi The Technical Specifications contained in Appendix A, as revised through Amendment No.165, are hereby incorporated in the license.
The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of its date of issuance and shall be implemented within 30 days.
FOR THE NUCLEAR REGULATORY COMMISSION ProjectDi'krkdw
~
et irector ectorate 11-2 Division ' Reactor Projects - 1/I!
Office of clear Reactor Regulation
Attachment:
Changes to the Technical l
Specifications Date of Issuance:
February 7, 1992 1
l
l a < ' Us.
%ie
=-
l L"
KL[
':c -
}
ATTACHMENT-TOLICENSEAMENDFLMI A
AMENDMENT NO. 166=
TO FACILITY OPERATINC, LICENSE NO. DPR-32 3
AMENDMENT NO. 165:-- iTot FACILITY-OPERATING' LICENSE NO. OPR-37 DOCKET NOS. 280 AND 50;;181 LRevise:AppendixAasfollows:
s Remove Paae Insert Paag n,
TS 3.21-2 TS 3.21-2 J
~.
N
+
f Y;i If s
5
--(
- 3,5
[
u G
c n
e..
6
TS 3.212 3.
Sorav and Sorinkter System - that provido protection for the cable tunnel and cable vault shall be operable 4.
Low Pressure CO9 Storaae Tank shall be operable with a minimum level of 75% and a minimum pressure of 275 psig.
5.
Low Pressure CO9_Sylte shall be operable to the extent that when raulpment in t' e N,w listed areas is required to be operable,. m. ppressicn van be provided upon demand, a.
Cable tray rooms b.
Cable tunnels c.
Cable vaults d.
Safety related charcoal filter banks 3A and 3B e.
Emergency diesel generator rooms 6.
Hiah Pressure CO2_ System shall be oper !ble to the extent that wilen equipment in the below listed areas is required to be operable, fire suppression can be provided upon demand. The minimum level of High Pressure CO2 system shall be 90% by weight.
a.
Fuel oil storage tank room for emergency service water pumps b.
Fuel oil transfer pump rooms for emergency diesel generators 7.
Halon Systems - shall be operable for the Emergency Switchgear Rooms. The storage tanks shall be at least 95% of full charge weight and 90% of full charge pressure.
8.
Fire Hose Stations the hose stations listed in Table 3.21-2 shall be operable when equipment ir the areas served by the hose stations is required to be operable.
Amendment Mos.166 and 165