1 r-

,o i

John D. O'Toole v<e nescent Consondated Edison Cortpany of Nen York, int 4 trying P! ace, New York, NY 10003 Teteohone (212) 460-2533 July 30, 1984 Re Indian Point Unit No. 2 Docket No. 50-247 Dr. Thomas E. Murley, Regional Administrator Region I U. S. Nuclear Pegulatory Commission 631 Park Avenue King of Prussia, Pa.

19406

Dear Dr. Murley:

This letter is in response to IE Bulletin No. 84-02 "Failuren of General Electric Type HFA Relays In Use in Class lE Safety Systems."

We have reviewed the relays in use at Indian Point Unit No. 2 and have determined that there are no GE Type HFA relays in safety related applications.

In addition, we have reviewed the general concerna described in the bulletin.

We have concitaded that they do not apply to Indian Point 2 mince we previously modified relays having these general concerns, including relay coil burnout (coil style 1271C50G01 in relayn 5072A49-C-XX).

The modification includes improved baked coils, coil style 1293C51G01 with improved insulating material, to prevent binding of the relay plunger in the coll.

These relays do not have the problems discussed in the bulletin, nor have they failed at Indian Point.

Additional replacements and a replacement schedule are not recuired an the performance han been found to be satisfactory.

Should you or your staff have any questions, please contact us.

Very truly yours,

)V ]

ff (,

Signed and sworn to before his 3 / day of Jul,

84.

t

, h Nota ilic 4AAO-TR> ada Notefy Public Stata of New York No. 30 4022875 Terms espires March 30,19df

)O Qualified in Nas.tu County

.l [obb7

C CJ, '

.A' p i

cc U. 8. Nuclear pegulatory Commission Document Control Desk q

Neshington, D.C. 20555 Senior Resident Inspector U. 5. Nuclear pegulatory Comunission P. O. Box 38 suchanan, New York 10511

}