Submits Final Response to IE Bulletin 83-06 Re Nonconforming Matls Supplied by Tube-Line Corp.Investigation Performed by Bechtel Determined Three Vendors Supplied Tube-Line Matl.All Tube-Line Matls Removed from Log
ML20094B783
Person / Time
Site: Midland
Issue date: 07/11/1984
From: Jackie Cook
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
29825, IEB-83-06, IEB-83-6, NUDOCS 8408070227
Download: ML20094B783 (3)


Text

,

~5 SMA E % '-

2 Consunlets-Power Jsmes W Cook h

hf Vice President - Projects, Engineering lL,

and Construction i

ggg 19h' gh General offices: 1945 West Parnett Road, Jackson, MI 49201 e (517) 788-0453 July 11, 1984:

y

$5

' go ess

,c

'hD G31 Gb 0

'1G 9%

/Mr J G Keppler, Administrator gggh US: Nuclear Regulatory Commission Region III-799 Roosevelt Road

. Glen Ellyn, IL 60137 MIDLAND ENERGY CENTER MIDLAND DOCKET NOS 50-329, 50-330 LIE BULLETIN 83-06: NONCONFORMING MATERIALS SUPPLIED BY TUBE-LINE CORPORATION FILE 0505.12 SERIAL 29825

REFERENCE:

(1) B&W 10 CFR PART 21 REPORT DATED JANUARY 10, 1983 (2) B&W LETTER TO R C DEYOUNG' DATED JUNE 17, 1983 (3) CP CO 50.55(E) REPORT (82-06) TO J G KEPPLER DATED FEBRUARY 28, 1983 (4) CP C0 50.55(E) REPORT (82-06) TO J G KEPPLER DATED MAY'31, 1983 (5)- CP CO-INTERIM IE BULLETIN 83-06 RESPONSE TO J G KEPPLER DATED NOVEMBER 17, 1983 (6) CP C0 SECOND INTERIM IE BULLETIN 83-06 RESPONSE TO J G KEPPLER

. DATED MARCH 12, 1984 s

In accordance with the directive given in IE Bulletin 83-06, this report identifies'the activities that have been completed to resolve the issue of nonconforming material supplied by the Tube-Line Corporation (T-L).

An investigation has been performed by Bechtel San Francisco Central Supplier Quality (SFHO) Department to determine if any sub-suppliers have supplied Tube-Line material to the Midland Plant. The following is a summary of this investigation and of the corrective actions taken:

51.

To.date, of the 413 letters mailed from SFHO, 85 letters went to vendors that supplied material to the Midland Project. Bechtel Ann Arbor has received 85 (100%) of the Midland responses.

2.

Of the 85 responses, 82 vendors have responded that'no Tube-Line material was furnished to Midland. The three vendors that have furnished Midland Tube-Line material are Guyon Alloys, Liberty Equipment and W J Wooley.

1M gg oc0784-0887a100 8408070227 840711 l

l PDR ADOCK 05000329

(

G PDR T6//

197.

]

~

r

+e

.:w

2 3.1-All Tube-Line material identified as being furnished to Midland has been entered on nonconformance reports.

~ )- Nonconformance Report C-00355; identifies 50 fittings received from a

Guyon Alloy and Liberty Equipment, 17 fittings were located in Warehouse No'1 in the separated hold area with Lold tags attached.

This NCR was dispositioned on May 3, 1984 by indicating that the 17

-fittings were to be returned to the suppliers.

b)UNonconformanceReportC-00961;identifiesninefittingsfromGuyon (Alloy and Liberty Equipment that have been incorporated into Q systems. All nine fittings will be removed and returned to the

. supplier. This NCR was dispositioned on May 2, 1984.

c)'LNonconformance Report 6022* identifies two 10" caps from W J Wooley that have been incorporated into ASME Class 2 Air Tank OT-921. NCR 6022 has been dispositioned by requiring removal of the caps.

x* Note that-two NCRs 6022 and C-0915 were opened on this subject. NCR C-0915 E

-was voided on May 31, 1984 to eliminate the duplication.

LA' total o'f.52 Tube-Line fittings have been received at the site for use in safety-related systems. Of these', 11 were installed and 17 were located in

(

37 Lthe warehouse. As stated above, these 28 fittings were identified on nonconformance reports and will;be removed from the site. The remaining 24

' fittings ~are not installed in safety-related systems, based on a review of all pertinent documentation at the jobsite. -The remaining 24 have either been installed in non-safety related systems or have been scrapped.

'The controlled heat log at the site identifies all heats acceptable for w/ '

installation in safety-related systems. All Tube-Line materials have been

< removed from the log..This will ensure that no nonconformance Tube-Line materials'will-be installed in the future.

sThe St'affiis' requested to contact us should any questions or comments arise

-regarding this response.

In lieu of Staff inquiry, no further response to this bulletin:is planned for the Midland Project.

1./. M 6

(JWC/WFK/fme '

-p

' ~

lCC 1DSHood, NRR Project Mana'ger, Washington Midland, Project Manager, Region III

~ Midland Project Section Chief, Region III Midland Resident Inspector,' Midland foc0784-0887a100

E

,o o

CONSUMERS POWER COMPANY Midland Units 1 and 2 Docket No 50-329, 50-330 Letter Serial 29825 Dated July 11, 1984 At the request of the Commission and pursuant to the Atomic Energy Act of 1954, and the Energy Reorganization Act of 1974, as amended and the Commission's Rules and Regulations thereunder, Consumers Power Company submits a_ final response to IE Bulletin 83-06 regarding nonconforming materials

. supplied by Tube-Line Corporation.

CONSUMERS POWER COMPANY By fJames9 Cook,VicePresident

~

Prgjects, Engineering and Construction Sworn and subscribed before me this Jo day of

_,/f//.

~-

Notary Public Jackson County, Michigan My Commission Expires _

M //p//

f r

oc0784-0887a100