ML20093M448

From kanterella
Jump to navigation Jump to search
Forwards Revised FSAR Question 430.81 Re Protective Coatings of Interior & Exterior Surfaces of Fuel Oil Storage Tank Against Corrosion,Per Draft SER
ML20093M448
Person / Time
Site: Hope Creek PSEG icon.png
Issue date: 10/18/1984
From: Mittl R
Public Service Enterprise Group
To: Schwencer A
Office of Nuclear Reactor Regulation
References
NUDOCS 8410220130
Download: ML20093M448 (3)


Text

r 3

0-t l'

Pubhc Service f}

Electnc and Gas Company 80 Park Plaza, Newark, NJ 07101/ 201430-8217 MAILING ADDRESS / P.O. Box 570, Newark, NJ 07101 Robert L. Mitti General Manager Nuclear Assurance and Regulation October 18, 1984 Director of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission 7920 Norfolk Avenue Bethesda, MD 20814 Attention:

Mr. Albert Schwencer, Chief Licensing Branch 2 Division of Licensing Gentlemen:

HOPE CREEK GENERATING STATION DOCKET NO. 50-354 DRAFT SAFETY EVALUATION REPORT FSAR QUESTION 430.81 Attached is a copy of revised FSAR Ouestion 430.81 previ-ously transmitted on September 28, 1984.

Should you have a.ny questions or require any additional information on these items, please contact us.

Very truly yours,

,/.

Attachment C

D.

H. Wagner USNRC Licensing Project Manager (w/ attach.)

W. H.

Bateman USNRC Senior Resident Inspector (w/ attach.)

8410220130 Adin<a M

{DRADOCK 05606 5

/

g The Energy People g[

,,uman n i

l L-

)

n ATTACHMENT

T HCGS'FSAR A

(JI QUESTION 430.81 (SECTION 9.5.4)

In Section 9.5.4.2.1 of the FSAR you state that "The interior and exterior surfaces of the [ fuel oil storage] tank are corrosion i

i protected by carboline carbo zine 11 coatings.

I&E circular 77-15 discusses the incompatibility between diesel fuel oil and zinc.

The reaction results in a substance resembling soap which when heated becomes insoluble and this. substance could I

render diesel generators inoperable due to blocked fuel lines, injectors, etc.

This is not acceptable.

It is our position that fuel oil storage tanks be provided with, internal corrosion protection.

Therefore provide the results of tests which show that over the lifetime of the plant that the carboline carbo zine 11 coating used is compatible with the type of diesel fuel oil that will be used at your plant and that the condition described in the circular will not occur or replace the internal coating with a non-zine base type that is compatible with diesel fuel oil.

(SRP 9.5.4, Part II)

RESPONSE

1 Hope Creek will remove the existing inorganic zine coating from the diesel generator fuel oil tanks.

The tanks will be blasted to the white =etal criteria of SSPC-SPS.

Two coats of A=ercoat 1

No. 90 or ecuivalent will be applied to the tank interior, 9

4 E