Text
{{#Wiki_filter:7 ',. POW 34 i F VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION _ MONTHLY OPERATING REPORT REPORT NO. 84-09 APPROVED BY: [h STATION MANAGER I 1 8410120134 840831 t gDRADOCK05000 't.i ',( n
i o. 1 i Section Page Operating Data Report - Unit #1 1 Operating Data Report - Unit #2 2 Unit Shutdowns and power Reductions - Unit #1 3 Unit Shutdowns and Power Reductions - Unit #2 45 Load Reductions Due to Environmental Restrictions - Unit #1 6 Load Reductions Due to Environmental Restrictions - Unit #2 7 Average Daily Unit Power Level-Unit #1 g Average Daily Unit Power Level-Unit #2 g Summary of Operating Experience 10-12 Amendments to Facility License or Technical Specifications Facility Changes Requiring NRC Approval g Facility Changes 'Ihat Did Not Require NRC Approval Tests and Experiments Requiring NRC Approval 15 Tests and Experiments That Did Not Require NRC Approval 15 Other Changes, Tests d Experiments 16 Chemistry Report 17 Description of AllInstances Where Thermal Discharge Limits Were Exceeded 18 Fuel Handling 19-20 Procedure Revisions That Changed the Operating Mode Described in the FSAR 21 Description of Periodic Tests Which Were Not Completed Within the Time Limits Specified in Technical Specifications 22
11 g Section Page Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #1 - Mechanical Maintenance 24-26 Maintenance of Safety Related Systeins During Outage or Reduced Power Periods - Unit #2 - Mechanical Maintenance 28 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit #1 - Electrical Maintenance 30 Maintenance of Safety Related Systems During Outage or Reduced Power Periods - Unit # 2 - Electrical Maintenance 32 Maintenance of Safety Related Systems During Outage or 34 Reduced Power Periods-Unit #1-Instrument Maintenance Maintenance of Safety Related Systems During Outage or 36 Reduced Power Periods - Unit #2 -Instrument Maintenance 37 Health Physics Summary Procedure Deviations reviewed by Station Nuclear Safety and 38 Operating Committee after Time Limits Specified in T.S. l
an Pa9e 1 bf 38 e-OPERATICC DATA RT?0?T TCO*.': T ?'C. 50-220 MTE 06 S'? 84 C0"PLE'rP ny.Vivian Jones TELEPRnTF B01.-357-3164 C_DE_P_A_T_I__TC_ S_TATUS
- 1. U:!IT '!A!Z -
SURRY UNIT 1
- 2. REPO?"It?G FFPIOD RO184 "O B3194
- 3. LICEi: SED.""-!EF'!AL PO!.TR (%'T) 2441 l~
~~ ~"~~~l 4 !.'A'TPLATF RATICC iGPOSS 'tT) 847. 5 l ':0TES l 5 DFFIGE ELEC~RICAL RATI?G ("FT !?E) 788-
- 6. !'AXI':'!" DTPE :PA?LE CAPACITY (G9f'S2 l312) ?11
-7 "AXI'"!" DEFE"DA?LE CA??CI"! (XE' int) 7*15
- 8. I' GACEF GCCI'F IN C/DACITY RATICnS
??/A (ITE' S 3 TUR0!!GE 7) SING LAST FIDD="", GIV" ?IAS0? S
- 9. DC'TR LEVFL TO L'?ICH CESTRIr'ED, IF AE! ';/4 (ITT *iT)
- 10. REAS0!!S FOR ?ESTRICTIONF, IF A?:Y N/A TEIS !'0!!""! YP-TO-DATE CTP'i1LATIIT
- 11. 90!!?? I! PEPORTING PERIOD 744.0 5855.0 102503.0
- 12. ? W' REP CF N07PS REACTOR VAS CRITICAL 744.0 4540.8 63633.7
- 13. REAC*0F RFSERVE SEUTDok7: HOURS
- 0. 0
- 9. 3 3774.5 14 200RS GENE?.ATO? 011-LI?:E 744.0 4477.8 62 345,0
- 15. UPIT PESERTT SHUTDOWN HOURS
- 0. 0
- 0. 0 3736.2
- 16. GROSS TPEPl!AL EXERGY GE!% RATED (!&'?)
1421403.7 9837650.6 144763954.9
- 17. GPOSS ELECTRICAL E::ERGY GENERATED !?T')
u37625.0 3143785.0 46 463628.0
- 18. ATT ELECTRICAL ENERGY GFNFRATED (!&F) 408268.0 2971195.0 44048931.0-
- 19. U::IT SERVICE FACTOR 100.O e/*
76.6 e/o ' 6028 * /e 2'0. UNIT AVAILA?ILITY FACTOR 1C0.0 o/o 76.5 e/e 64.5e/o
- 21. UNIT CAPACITY FACTOR (UEI!:G "DC !!ET) 70.9 e/e 65.5 e/e 55.4 e/o
- 22. U!!!T CAPACITY FACTOR (USI?:S DER NET) 69.7 e/o 64.4 * /*
54.5 e/o
- 23. U?IT FORCED OUTAGE RATE 0.0 e/*
4.5 ele 9.0 e/o 24 SHUTD07':S SC::EDULEE CIT? CEXT 6 !'0?:THc PEFUELING 9-28 75 DAYS (TYPE,DATE,AND DURATICT 0? EAC'!)
- 25. IF S"*!T DOV!? AT E!!D OF REPORT PERIOD, ESTI?' ATE DATE OF STA.%"!?
- 26. U!!!TE I!: TEST STA."'US FORECAST ACF!IEtTD (PRIOC TO C0""ERCIAL OPERATION)
I!!ITIAL CRITICALITY I??ITIAL ELECTRICITY C0!'"ERCIAL OPEPMIO" l 1 3
Page 2 of 38 a I 0? ERA'IE7 DA'A REPCRT DOCVET ??O. 291 ' DATE 06 SFP 84 C0"DLETEF ny Vivian Jones TELE *?C"E 804-357-3184 OP_ER_A_T_I_!'G S_TA_T__!!S 1.- U!!IT ??A!T SURRY U?;IT 2 2.~RE?ORTING PEFiOD B01B4 TO 63184
- 3. LICENSED THERVAL POkTR ( AfrT) 2441 l~~~~~~~~~~~l 4.- NA'5 PLATE RATING (G?OSS !NE) 847.5 l??CTES l
- 5. DESIG!: ELEC*RICAL RATICG (!TT %T) 788
- 6. ?:AXI!::c.' DF?El?DA?LE CA=ACITY (GROSS !PE) 811
. 7. J(AXI!T" DEFE!:DA"LF CA?ACITY (NET ?5T) 775
- 8. IF CHARGES OCCUP IC CADACITY-RATI?:CS
?:/A ( TTE!!S 3 THROUG" 7) S!? CE LAST REPORT, GIE RFA50?:S
- 9. POLTP LEl'EL TO ;!NICH RESTRICTFD, I? A? Y F/A
(!!ET '5T)
- 10. REAS0!!S FOR RESTRICTIO!?S, I? A???
N/A THIS !!O?!'" YF-TD-DATE CU!ULATIt'E
- 11. "OU?S I?: REPORTI??C PE?l0?
744.0 5855.0 99303.0
- 12. ?RP'RER OF HOURS REACTOR V2S CRITICAL 729.3 5087.6 63658.5
- 13. REACTOR RESERVE Cr!!TX"r!'l HOURS
- 0. 0 0.0 328.1 14, nrygg GEritpATop on-LINF 727.0 5031.6 62607.6
- 15. U?;IT RESERVE SHUTDOW? 200RS
- 0. 0
- 0. 0
- 0. 0
- 16. GROSS THER!'AL EnTRGY GENEFATED (!yM) 1746844.0 11896464.1 146612337.0
- 17. GROSS ELECTRICAL ENERGY CENERATED (!3??)
5467e0.0 3785;785.0 47580 644.0 1*. NE." ELECTRICAL ElTEGY GENERATED (!NU) 517816.0 3586 561.0 45093 621.D
- 19. UNIT SERVICE FACTOR 97.7 e/o
'85.9e /o 63.0 e/o
- 20. U?IT AVAILAPILIT! PACTOR 97.7 olo 85,9e f e 63.0 * /*
- 21. U?iIT CAPACITY FAC"0? (USI."C '!DC ??E')
89.8 */o 79.0 e/o 50.5 e/o
- 22. L7?IT CAPACITY FACTOR (UFI:10 DER NET) 88.3 */*
77.7 e/o 57.6 e/o
- 23. UNIT FORCEC OUTAGE RATE 2.3 */*
14.1 e/o 14.8 e/o 24 SHUTDOF7?S SCHEDULED 01TR NEXT 6 ?'0?TuS 11-9-84 to 11-19-84 iTYPE.DATE.A1D DURATIC" 0F EAC"1 10 DAYS
- 25. IF SHUT P0h'?! AT END OF REPORT PERIOD, ESTI!' ATE DATE OF STA?"UP
- 26. U?iITS I!: TEST STATUS FDPECART ACHIEVED
(??10R TO C0!"!EPCIAL CPEPATIO!!) INITIAL CRITICALITY INITIAL ELECT?lCITY CC'CTRCIAL 0DEPA*IO!: m -- m m .-m
e a 50-280 DOCKET NU. UNIT sil01tioWNs ant > ROWER RElllM'110Ng IINII~ NAME Surry 1 0%O7-84 HA1E COMrl.E1EH IIy V. H. Jones REI ORT MONill thig.ust,1984 1El.FriloNE 804-357-3164__ i
- t.
!E 'h E b l.ltenice [g UL rsuse A Coseettive
- k. is A,,go,,,
i -{ g gj g ]gj Nie. Date II,ent n7 fj$3
- -4 Repen,
av r.e.e,. R,c.... ns e i-oa ~ TIIE 1E WERE NO LINIT SIIUTDOWNS OR POW i:R REDUCTIOb S GRETTER TII AI I 20% DURING Tills REPORTING PERii )D. / l i 8 0 3 4 1 2 Mellonl: Emlill,it G - Instruttisms u t : l'inseJ Reason: 1.Manusi fu, Peepasselon <>f pata o 5: Silicif ulcel A regulpinent ralluie (Emplain) Hi II Maintenance ni leil 7 Mannst Sesans. Entry $licets fo I.lcernee 3 Autunutic Sesam. Event Itepmt (l.EIO file INilitt G. w i C Hefuellog f D flegulatiny Restiltilon 4 Otlice (limplain) 0161) s E-Opessteis Tosining A liccuse Enaminstion l 5 F.Ailminlitisilve F11:11:18 I - Same Soust e i G Opcestimeal l'esies (f splain) l*p/17) II Ollies (thplain) i b
-.. -. - ~ 50-281 i DCKET NO. tifffT SitUII) OWNS AND FolVER RI.Dt)C110NS t##TNAME Surry II (co_.DJ.) U9-U#~84 <pATE 004frLETEI) Ry V. H. J_on_cs MlirORf MONill Anm>=t inna 1ELEFIN##E 804-352-3184 3 ~ Ij l.li ensee l e, Conse A Coeeective 3g 3 } y, oc Asihm tu j] No., Dste { Event gg g= j. f*sevent Recussence o[ j gg iterint ir vi te E m 84-20 08-07-84 F 17.0 A 3 84 013 The unit received a turbine runback to 300 M W's, then two minutes later, received a reactor trip. The cause of the runback was a NIS runback from N-43 when the control power fuse blew while inst. techs. were trouble shooting a failure of the flux meter. The blown fuse was caused by using an un,Jrounded ) = cord on test meter. Inst. Dept. has i discussed this problem with all tech's. to prevent reoccurence. The unit aise received three OT6T runbacks and then a OPAT trip. These were caused by a l decreasing setpoint. The reason for the lI decreasing setpoint is still under investigation. i l f N 3 4 S I I 2 Methnit: E nMiill G. insteurthms u i F: Fmced Reason: l Manuel ros riepseschm ni psis g S: Scheduleil A Eigulpment rollwe(Emplein) 2 Manuel Screm. I:ntry Sheets for t.lcensee 6 ti II Melotensnce of Test 3 Auloensile Scre.n. Event Repnet (l.ER) File (NilitI(;- o. j C. Refueling D Regulatory Restilction 4 Oileet (Emplain) DI(.1) E-Upessene heining A IJcense Eneminethm j F Adniinististive E=hihlt I - Ssme Source G Openeihmst I:ssos (Eaplain) 1 j l'l/77) II Othet (Eaplain) I
1 e 8I iMKKF T NO 1pNiisaltlitsowH5 ANilFOWFR REltilCIH)NS gg W-07-84 elPA1E 00Mrl.E1Elp ny V.11. Jones REFORT MONIll Anoust 19&d irI.Fril0NE._8.04-357-3184 h ~ u l.k ensee [*,,
- L Cause A Cossective
{g "k } Ej Attleen tu g jne IIvent glf l W., liste ( gI he,e I Ret.nence jg Repuel er vi o g t-j n t i 8 & 21 08-15-84 S 0.0 11 4 The unit was reduced to 78% power (570 MW's) to allow removal and cleaning of " A" waterbox. 84-22 08-18-P4 F 0.0 A 4 The unit was reduced to 67 % power I (485 MW's) due to the loss of four circulators at the low level intake. The l circulators tripped off on high water l level in pit caused by gross leakage from s 1-CW-P-ID. The pump was removed from service and is being repaired. l 84-23 08-21-84 S 0.0 11 4 The unit was reduced to 76% power (580 MW's) to allow removal and cleaning of "A" waterbox. s
- o3 1
0 4 f 3 I 2 Meehs=l: F alill,Il C. Instinctluns ui F renteil Messim: l Manwel Ios reepsistiam ull)sts o l 5: Selwiluleil A Figulgmwnt f sifure(limplain) 2-Manust Seesm. Entry Slicets fue I.leensee 3 Maintenance os lest 1Antimulle Sessm. I:vens ReporIlt.l R) l' ele INilHIG. w* O.Itefoeling 4 Utlwe Ilimplaiol Dir.1l l} Regelstney Restilrtimi ET)peestos Tisining A license Essneinathm 5 F Ailministostive ItieMelt I Sainw Sowe(c G Opceselimst f esus (l'agelsin) rif7il II Other IFsplaini 1
Pace 6 of 38 LOAD PSUCTIONS D'*E TO ENIRONEN~A1. RES~iICTIONS UNIT NO.1 MONTH: August, 1984 DATE TIME HOURS LOAD, %' EDUCTIONS. E' M~Id REASON NCE DURING THIS REPuKdNG PERIOD. l t i =e t 9 4 e t i MONTIC.Y TOTid. ~,- av., -...+n.-- --n .- - + -c.~ e
Page 7 of -. 38 LOAD REDUCTIONS DUE TO EhTIR0tFhiAL RES"T.ICTIONS UNIT NO.2 MONTE: August, 1984 DATE TI1E HOURS LOAD, Mk' REDUCTIONS, ML' M7d REASON tGE DURING IHIS REPutu143 PERIOD. i 4 4 i e i MO:,IELY TOTAL m 2
Page 8 of 38 DOCEE* NO 50-280 UTIT SURRY I DATE 9-1~84 COMPLETED By V H. Jones ATTRAGE DAILY UNIT POYEP LEVEL M0i:THt ' AUGUST 84 AVEPAGE DAILY POWER LEVEL AVERACE DAILY POWER LEVEL DAI ( PFE-PET) DAY ( MT-!.TT) T 1 432.9 17 552.8 2 500.6 18 546.0 3 565.9 19 549.0 4 564.7 20 549.8 5 553.7 21 546.5 6 560.4 22 538.0 7 549.6 23 555.8 8 544.0 24 560.4 9 556.0 25 I 9. 9 10 555.4 26 535.8 11 550.8 27 P 4.1 12 550.4 28 566.7 13 550.1 29 566.8 14 550.6 30 566.4 15 548.3 31 563.1 16 551.6 ' DAILY UtiIT PO?!ER LEVEL TOR'? INSTRUCTIONS O!? "71IS FOR'l, LIST THE AVERAGE DAIL? UNIT POWER LEVEL I!! WE-NET FOR EACH DAY IN THE PZPORTING !.*0'!TH. T5!ESE FIGURES VILL PE USED TO PLOT A GRAPH FOR EACH PEPORT-ING M!!TH. NOTE THAT PY USING PAXIM1" DEPENDAPLE CAPACITY POR THE NET ELECTRICAL CATI? 0 0F THE UNIT, THERE ?tAY BE CCCASIO!)S VMEN T4E DAILY AVERAGE POWER EXCEEDS NE 100 */* LINE (OR THE PESTRICTED POVER LEVEL LINE). IN SUCH CASES, 57 AVERAGE DAILY UNIT POWER CUTPUT SHEET SHOULD BE FOOTNOTED TO EXPLAIN THE APPARENT ANO"ALY.
7 Page 9 of 38 DOCEET ?!O 50-281 UNIT SURRY II DA TE 9-1-64 C0!'vLETED ?? V. H. Jones AVERACE DAILY UNIT POW"R LEVEL ' f'OrTHa, AUGUST 84 AVERAGE DAILY POVER LEWL AVERAGE DAILY POYER LEWL DAY (WE-NET) DAY (MWE-NET) 1 72C.5 17 712.4 2 725.5 19 671.P 3 720.1 19 716.0 4 720.8 20 717.0 5 717.4 21 683.4 6 709.8 22 725.7 7 429.0 23 725.5 6 405.7 24 724.5 S 717.1 25 726.8 10 721.4 26 723.5 11 718.2 27 730.6 12 714.7 28 731.1 13 706.2 29 730.0 14 703.0 30 715.2 15 662.9 31 730.1 16 714.0 DAILE UNIT POWER LEVEL FOR!'INETRUCTIONS 0?! THIS FORti, LIST THE AVERACE CAILY UtlIT POWER LEVEL I'? WE-NET FOR EACH DAY IN 2??E CEPORTING PDUTH.^ TPESE FIGURES VILL BE USED TO PLOT A GRAPH FOR EACH REPORT-ING ?!053. NOTE TVAT BY USING !!AXIMU'! DEPENDABLE CAPACITY FOR THE NET ELECTRICAL RATING OF THE UNIT, THERE MAY BE OCCASIONS WHEN THE DAILY AVERAGE POWER EXCEEDS THE 800 */* LINE (OR T'fE RESTRICTED P0YER LEVEL LINE). IN SUCH CASES, THE AVERACE DAILY UNIT POWEP CUTPUT SHEET SHOULD BE TOOTNCTED TO EXPLAIN THE APPARENT ANOMALY.
m Pcg 10 of 38
SUMMARY
OF OPERATING EXPERIENCE MONTH / YEAR August,1984 Listed below in chronological sequence by unit is a summary of operating experiences for this month which required load reductions or resulted in significant non-1 cad related incidents. UNIT ONE 08-01-84 0000 This reporting period begins with the unit at 65% power (470 MW's) holding due to 1-FW-P-1A out of service. 02-84 0840 1-F W-P-1A returned to service, commenced increasing power at 3%/ hour. 1340 Holding power at 80% (600 MW's), unit is limited to 80% power due to rod B-6 being stuck. 08-08-84 0949 Unit power rapidly reduced to 62% (440 MW's) due to a loss of 1-FW-P-1A. 1004 1-FW-P-1A returned to service, commenced power increase at 150 MW/hr. 1130 Unit at 80% power (600 MW's). 08-09-84 1052 Two men fatally injured caused by electrocution when one man drilled into a 4160 volt cable from "C" RSS. The other man was killed during his : escue attempt. 08-22-84 0 011 Commenced power decrease for removal of "1D" waterbox from service for cleaning. 0045 Holding power at 70% (500 MW's). 0402 Commenced power increase at 3%/ hour. 0701 Unit at 80% power (600 MW's). 08-24-84 2344 Commenced power decrease for removal of "1D" waterbox from service for cleaning. 08-25-84 0150 Holding power at 76% (530 MW's). 0622 Commenced power increase at 3%/ hour. 0 918 Unit at 80% power (600 MW's). 08-31-84 2400 This reporting period ends with the unit at 80% power (600 MW's). l ^ L
Ptg> H of 38
SUMMARY
OF OPERATING EXPERIENCE MONTH / YEAR August.1984 1 Listed below in chronological sequence by unit is a summary of operating experiences for this month which required load reductions or resulted in significant non-load related incidents. UNIT TWO 08-01-84 0000 This reporting period begins with the unit at 100% power (770 MW's). 08-07-84 1423 Turbine runback caused by NIS rod drop signal from N-43 when control power fuse blew while instrument technicians were trouble shooting failure of flux meter. 1425 . Reactor trip caused by a two out of three OPAT signal, this was initiated because the setpoint was automatically reduced or pen alized following Turbine runback. 08-08-84 0510 Reactor critical. 0723 Generator on the line, commencing a 150 MW/ hour power increase. 1600 Reactor at 100% (760 MW's). 08-14-84 2300 Commenced power decrease for removal of *2A' waterbox from service for cleaning. 08-15-84 0132 Holding at 78% power (570 MW's). 0150 Commenced power increase at 150 MW's/ hour. 0650 Unit at 100% power (760 MW's). ~ 08-18-84 1226 Commenced power decrease due to loss of four circulating water pumps at the low levelintake. 1300 Holding power at 67% (485 MW's). l 1408 Commenced power increase at 150 MW's/ hour, circulators returned to service. 1720 Unit at 100% power (760 MW's). 08-20-84 2250 Commenced power decrease for removal of '2A' waterbox from service for cleaning. 2350 Holding power at 76% (580 MW's). 08-21-84 0502 Commenced power increase at 150 MW's/ hour. 0706 Unit at 100% (770 MW's). 08-30-84 0345 Commenced power decrease for removal of '2A" waterbox from service for cleaning.
Page 12 of 38 UNIT TWO (Continued) 08-30-84 0450. Holding power at 84% (640 MW's). 0645 Commenced power increase at 150 MW's/ hour. 0800 Unit at'100% power (770 MW's). 08-31-84 2400 This reporting period ends with the unit at 100% power (770 MW's).
Page 13 of 38 AMENDMENTS TO FACILTTY LICENSE OR TECHNICAL SPECIFICATIONS MONTH / YEAR August,1984 i The Nuclear Regulatory Commission issued on 6-19-84 Ammendment number (s) 97 and 96 to the Operating License for Surry Power Station, Unit No,'s 1 & 2. This Ammendment is a result of the proposed Technical Specification Change Request No.(s)127 and Changes Radiological Effluent Technical Specifications. T i I r e I u_
Page 14 of 38 FACILITY CHANGES REQUIRING NRC APPROVAL Anaust, 1984 NCEE DURING 'IHIS REKranCa PERIOD. FACILITY CHANGES THAT DID NOT REQUIRE NRC APPROVAL Naaust, 1984 NCEE DLRING THIS REPCRTING PERICD. B 4 4 e -9 ,,m .~,-.,m m. ,..~n
r. Page 15 of 38 TESTS AND EXPERIMENTS REQUIRING NRC APPROVAL Aucust, 1984 NCNE DURING 'IHIS i<EFun'n9G PERIOD. TESTS AND EXPERIMENTS THAT DID NOT REQUIRE NRC APPROVAL Aucrast, 1984 NCNE DURING 'IHIS i<EFudu4G PERICO.
.e- ..M4 u. s,. e ~a . ~ ae s 4 4 m Page 16 of 38 ~ f OTHER CHANGES, TES'f5 AND EXPERIMENTS i Aucrust. 1984 t NCNE IL' RING 'INIS REPOfEING PERIOD. I l -f I I l I t I 1 1 l 1 4 I J f l 5 n 4 a 4 J - -,.-,,.....,,..,,... __.,.,-,,,...- ~,. ...c.,-,,.-,,
POR 28-06 Page 17 of 38 VIRGINIA ELECTRIC AND POWER CO.UANY SURRY POWER STATION CHEMISTRY REPORT August 19 84 PRIK CODI. ANT UNIT NO. 1 UNIT NO. 2 -ANALYSIS MAXIMUM' MINIMUM AVIPJGE MAXIMUM MINIMUM AVERAGE -1 -2 -2 Gross Radioact., uCi/ml 1.65 0.92 1.35 1.38E 1.79E 7.31 Suspended Solids, pom 0.0 0.0 0.0 0.0 0.0 0.0 -2 -2 -2 -1 -1 -1 Gross Tri-lum, nCi/ml 3.95E 3.23E 3.53E 2.25E 1.15E 1.68E -2 -2 -2 -4 -5 -4 Iodine 131., uCi/ml 3.00E 1.22E 2.31E 5.17E 7.29E 1.94E 131 133 I /I 0.41 0.14 0.26 0.23 0.04 0.12 Hvdrocen, ec/kg 38.9 21.0 29.9 49.7 27.2 35.0 l Lithium, ppm (A) 0.67 0.44 0.57 1.26 0.78 0.96 Boron-10. ppm
- 41.6 20.6 26.6 109.4 73.7 83.8 1
~
- Oxycen, (D.O.), ppm 50.005 50.005 s0.005 50.005 so.005 50.005 l
Chloride, epm so.02 so.02 so.02 so.02 so.02 so.02 pH 8 25'C 7.00 6.77 6.91 6.69 6.49 6.55 i
- Beron-10 = Total Boron x 0.196 NON-RADIOACTIVE CHEMICAL RELEASES, POUNDS I
T.S. 4.13.A.6 (B) j Phosphate Boron. 55 ~ Sulfate Chromate nn 4 $0% NaOH Chlorine i j REMARKS: (A) Lithite additima m=Aa to unit 42; 690 runn on 9-7; ARO,wne on 9-9; 210 cimm on 8-IPs 100 as on 8-30 Cation bed elaced in service on unit #1 on 8-13, cation bed p1W in service on unit #2 on 8-13 and 8-27 for lithium reroval. (B) The levels of these chicals should create no adverse environmental imact. 4 f ,._____.._..~,._,_.-.~.m..,.-
) Page 18 of 38 DESCRIPTION OF ALLINSTANCES WHERE THERMAL DISCHARGE LIMITS WERE EXCEEDED Aucust, 1984 NCNE DURING 'IHIS REPORTING PERIOD. i )
Page 19 of 3E FUEL H AND'_ING 1 UNIT # MONTH / YEAR August,1984 DATE NO. OF ANSI NO. NEW OR SPENT FUEL SHIPPED / RECEIVED ASSEMBLIES PER S!!IPMENT INITIAL ENRICHMENT SHIPPING CASK ACTIVITY LE%TL NONE DURING THIS RE PORTING PERIOD. e e ,.-_.y. ....e,
Page 20 of 38 FUEL HANDL!NG U UNIT $ MONTH / YEAR August,1984 DATE NO. OF ANS: No. NEW OR SPENT FUEL SE!PPED/RECE!VEO ASSEMBLIES PER 5$ PMENT INITIAL ENRICHMENT SEIPPING CASF. ACTIVITY LEVEL NONE DURING THIS REPORTING PERIOD. l I
Page 21 of 3g 'I PROCEDURE REVISIONS THAT CHANGED THE OPERATING MODE DESCRIBED IN THE PSAR Auaust, 1984 NCNE DURING THIS REPCRTING PERIOD. l 1 1 1 _____ae__---_,-----.--_a- -_---__.__----------_a--------
Page 22 of 38 DESCRIPTION OF PERIODIC TESTS WHICH WERE NOT COMPLETED WITHIN THE TIME LIMITS SPECIFIED IN TECHNICAL SPECIFICATIONS Auaust, 1984 M NU N E T* i
r 1 Page 23 of 36 +- e l M AINTEN ANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO.1 MECHANICAL MAINTENANCE 4 l
VEPCO SMETY RELATED DLRING REDU::Eb F0WER SORTED BY UNIT AND KPARTENT Ff:00RM WDT09060 09/10/84 13:06 FROM 08/01/84 TEU 06/31/84 LMIT 01 SLERY Page 24 of 38 RETIMED TO WO KPT SERVICE HARK NUMBER HUMIER WO TITLE HISTORY SLMtARY 08/16/84 01-CC -E -1D 003650 CLEAN D CC HX CLEAED OUT 1D EAT EXCHMOER GOT 1 BAG OF TRASH OUT R03 06/27/94 01-CH -P -2D 003658 FUPF SE/L LEES BADLY OVERHALLED OLD TYM Pt#F AND REFtAC ED Pl#F.REFLACED IPPELLER SHAFT SLE EVE SEAL DIL SEAL APG SHAFT. REPLACE D STL7 TING BOX.HAD TO SHIM LP Q.D T YPE Pt9F WITH A 1 1/2 PLATE. R03 06/30/94 01-CC - -130 004270 BASEFLATE BOLT LOOSE--EEDS TO TOROUE NUT TO 140 FT LB AS PER PERCEDURE R03 06/09/94 01-SW -P -1C 003444 FUMP IS INOPEPABLE DE TO IM-DIVERS aIAED SUCTION PIPE OPS CECKED OK R03 06/13/84 01-MS -SOV -102A 003038 VALVE LIES BY SEAT CAUSING FC REPLACED GASKETS IN VALVE.TD BODY TO 90PeET BOLTS TO 165 FT LW GASKET SET SET STOCK NLMBER 1740362 TOOLS:TOROUE WRENCH 1311 R03 06/15/84 01-MS -SOV -1029 003039 VALVE LEAKS BY SEAT CAUSING PU REPLACED BODY TO 90PeET GA9KET AND GASKETS IN VALVE TQ BODY TO 90PeET BOLTS TO 165 FT LDS INSTALLED EW G ASKETS AND TOREED VALVE BOP 4ET TO 165 FT LDS R03 06/17/84 01-CH -P -2A 002916 REPLACE FASTDERS ON INGLLATION COVER ORIGINALLY KSIGK D TO K ELD T00ETER BY FINGER TIG HT BOLTS.BOLN HAVE MEN REFLACED. R03 06/20/84 01-EG -C -2 003749 AIR COPPRESSOR RtMS CDP (TINT)- OPDED CECK VALVE PWtf AND FOUND F LUID OPDED LP EAD MD FOLMD INCOR RECT KTEEN 9 PACER AND CYLINER OP EN W EAD FOUPS K0hN MAD GASKET REPLsGD LP/W GASKETS MD IRAIPED R03 06/20/84 01-MS -#RV -101C 003741 FtRMMITE PACKING LEAK IN,ECTED PACKING (LAND WITH FlRMMI TE NLnIAR (RADE FIBER CART LOT 101 2 Wt NO.045024 SUBMITTED TO RETURN TO ORIGINAL j R03 06/22/64 01-BS -HSS -NA 002166 DISASSD9LE AND INSKCT SNUBK INSPECTED SWBKR AND RETIRED SmWr R03 06/22/94 01-BS -HSS -NA 002167 DISASSOGLE MD INSPECT SNUBE IN9rtCTED SP4JBER AND AETIRED Snubber R03 06/22/84 01-3S -HOS -NA 002168 DISASSD9LE AND INSPECT 9NUBE DISA89DOLD NS INSKCTED SWBER MD Retired Snubber R03 08/22/84 01-95 -HSS -la 002169 DISASSO 9LE AND INSPECT SPAD E DISA89 DOLED MD INSPECTED SNUBER MD RETIRED Snubber R03 08/22/94 01-BS -HS$ -NA 002170 DISASSO9LE AND INSPECT SNUBK LISAS909LE AND INBPECTED SWBKR AND RETIRED Snubber R03 08/22/84 01-CC -E -1A 003557 TUK LEAK REMOVED END KLL.1 TUK RtPT1 RED,Ft UDOED SAE.MAK EW GASKET CLEAED NUTS MD BOLTS MD LUBRICATED.INSTA LLED END KLL AND CLOSED MANWAY R03 06/22/84 01-CV -P -1A 003602 Pt9F RLMS NOISY REPLACED PtBF WITH SPARE MBF R03 06/22/84 01-EG -C -2 003436 REPAIR FITTING ON $1 K OF REFtAED EAD GAGETS AND REED VALV E ON COPPE300R R03 08/22/94 01-IA -C -1 003120 REMOVE /E INSTALL BELTS FOR MOT EINSTALL MLTS MS N.10N Mi1EY ' '~ + ,,.y .2-_,
VEPCO SAFITY RELATD DURI'D Rmrrn P0hER 90RTD BY UNIT AND KF'ARTNENT PROGRM WT09860 09/10/94 15t06 FROM OS/01/64 Tietu 06/31/64 UNIT 01 SURRY Fago 25 cf 38 RETthED TO WD DEPT ERVICE M K NUMER MMER WO TITLE HISTORY
SUMMARY
R03 06/22/64* C1-SW -P -19 003410 REMJ1LD PUPF LOW DISCHEGE FLO REMOVED PUMP DISASSEMBLED SUCTION BELL AND IPPELLER REPUED KLL WITN EW.REASSEMBLID WITN.011 IN. CLEARANCE IPPELLER TO DELL. SUCTION STRAIER CLOGOG.REPLACD W/LAR0ER R03 06/22/94 01-VS -E -4A 002857 CHILLER TRIPS ON LOW SUCTION PLUDGED 8 CON KNK R TUIES MAKING A TOTAL OF 11 TU KS PLUGOED DRIED M01 STURE OUT OF REFRIGERANT SYSTEM REC HAR0ED MD STETD UNIT R03 08/23/94 01-M -HSS -m 002719 DISASSDeLE/ INSPECT SWfPKR (S DISAS9EMKED MD INSPECTD SNUDER AND FETIE ' Snubber-R03 06/25/89 01-CH -MOV -1381 003928 PACKING EEDS ADJUSTING OR ADASTD PACK!NG 3 FLATS R03 06/27/94 01-VS -F -T9 003856 KLTS OR Fu1IYS MKING EXCES-ADASTEC KLTS R03 06/26/94 01-CV -P -1$ 004312 LMCOLFLE/RECOUPLE FOR ELECT. VOID!LISTEED TO PLbF RtN. NO AbN0h MAL N0!$E NEMtD. TE MIK TOU MAY KAR IS NORMAL. R03 08/29/94 01-M6 - -196 003495 VALW IIAKS T)ftU G.0K MVE VO!D! WORK TO K C0FFtET D ON WO 9003390 R03 06/29/94 01-MS -PCV -102A 004169 VALVES LEM BY FU 1ED DONNET ON VALVE REPLACED GAShETS AND TO BODY TO 90>eCT BOLTS TO 165 FT LDS RO'3 06/29/84 01-MG -PCV -102) 004160 M VE LEMS BY PULLED DON ET ON VALVE.PEFtACED GASKETS MD TO 90DY 10 DONDET BOLTS TO 165 FT LDS i R03 06/30/94 01-M -H6S -m 002704 DISASSD ELE IrG TCT SNUB ER INSFECTD SNUDKR MD RETIRED Snubber R03 08/30/04 01-M -HBS -NA 002705 DISASSO9LE SNUDKR IN9FECT IN9PECTD $ NUDER MD RET!O Snubber C3 06/30/94 01-DS -HBS -M 002706 D!$ASSDOLE SNUDER INS 8tCT IN9PECTD SNUDER MD RETIRED $nutber R03 08/30/94 01-M -HSS -M 002707 DISASSDRE SMlDKk INSPECT IN9FTCTD SNUDtut M RETIRD $nubber R03 08/30/94 01-M -NES -NA 002700 D!SA8SDSLE IN9PECT SNUDKR IN9TCitD SMJDKR M RETIRED Snobber R03 08/30/94 01 M -NB3 -M 002709 DISA6KMblE INSFTCT SNUPKR IN9FTCTD SNUDKR MD KT!KD $nubber RC3 08/30/94 01-M -HBS -m 002T10 D!iAS3 DELE !N9PECT SNUDKrt DISASSDRED M IN9PTCTD 96KR MD KTIED Snubber
Page 26 of 38 VEFC0 SAFETY RELATED DURING REDLCED POWER SDRTED BY UNIT AND DEPARTMENT FS:0 GRAM L*T09360 09/10/84 15:06 FR0rt 08/01/B4 THRU 08/31/B4 LPi1T 01 SURRY RETLRNED TO WO DEPT SERVICE Wie NuribER NUMBER WO TITLE HISTORY
SUMMARY
R03 08/30/84 01-35.HSS -NA 002711 DISASSESLE INSPECT SNUBBER INSPECTED SNUBBER AND RETIRED Snubber 1 I R03 08/30/84 01-PS -HSS -NA 002712 DISASCEMBLE INSPECT SNUBBER DISASSEMBLE SNUBBER AND RETIRED Snubber R03 08/30/B4 01-BS -HSS -NA 002713 DISASSEMBLE INSPECT SNUBBER INSPECTED SNUBBER AND RETIRED Snubber R03 08/30/84 01-PS -HSS -HA 002714 DISASSEMBLE INS ~ICT SNUEBER DISASSEMBLED SNUBBER INSFECTED AND RETIRED SNUBBER R03 08/30/84 01-PS -HSS -HA 002715 LISASSDL%E INSFECT SNUBBER DISASSEMBLED AND INSDECTED SNUBBER AND RETIRED Snubler R03 08/30/84 01-BS -HSS -NA 002716 DISASSEMBLE / INSPECT SNUBBER (S DISASSEMBLED AND INCDECTED SNUBBER AND RETIRED 5nuble r R03 08/30/84 01-BS -HSS -NA 002717 DISASSEMBLE / INSPECT SNUBBER (S DISASSEMBLED AND INSPECTED SN'JBBER AND RETIRED Snubber R03 03/30/g4 01.PS -HSS -NA 002718 DISASSEMBLE / INSPECT SNUBBER (S DISASSEMBLED AND INSPECTE SNUBBER AND RETIRED Snubber R03 034 0/84 01-CH -RV -1203 003006 REI:UILD SPARE RELIEF VALVE D'KRHAULED VALVE REPLACED SPINDLE GUIIE, GASKETS. DISC. CLEANED LAPFED P ERFORMED PT 12.2 FOUND DISC DAMAGED SPINDLE BENT K03 08/30/84 01-EE -RV -104 002412 EWR B4-179 EXISTING RV DOES NO TEST NEW UALVE AS FER PT-12.2 THE4 REFLACE OLD VALVE WITH NEW VALVE AS PER EWR-84-179 R03 c.8/30/84 01-EE -RV -106 002413 EWR B4-179 EXISTING RV DOES NO TESTED VALVE AS PER PT-12.2 REPLACED VALVE TOOLS: PIPE WRENCH 12"10" CRECENT R03 .M/30/84 01-EE -RV -107 002415 EWR B4-179 EXISTING RV ICES NO TEST NEW RELIEF VALVE AS PER PT-12. 2 AND REPLACED OLD UALVE WITH NEW TESTED VALVE AS PER EWR-84-179 R03 eG/30/84 01-EE -RV -108 002414 EWR 84-179 EXISTING RV DOES NO TESTED VALVE AS FER PT-12.2 REPLACED VALVE i R03 N/31/84 01-CC -E -1A 004442 1-CC-E-1A HAS TUBE LEAKS PLEAS CECKED 1-CC-E-1A FOR TUBE LEAK F00 ND NO TUBE LEAK HAD OFS VERIFY PCTE DEWITT AND LOU JONES 403 N/31/84 01-CH -P -1B 002620 OIL LEAK BELOW BULL EYE REFuCED BULLS EYE O rv -.
Page 27 of 38 I MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 MECHANICAL MAINTENANCE l l i l i 1
Page 28 of 38 VEPCO' SAFETY RELATED DLRING REDUCED POWER SORTED BY UNIT AND DEFARTMENT PROGRAM WPT09860 09/10/84 15 06 FROM 08/01/34 Ts u 08/31/84 UNIT 02 SURRY FETURNED TO WO DEPT SERVICE MARK NUMBER NLMBER WO TITLE HISTORY
SUMMARY
R03 08/13/84 02-CH -FCV -2114B 003579 CHECK TRAVEL OF VALVE WENT TO TE BORIC ACID FLATS AND IS OLATED TE AIR TO THE VALVE.WE THEN BLED TE AIR OFF DOME TO CECK SEE IF UALVE WOLLD MOVE IT DIDN'T.VLV IS LEAKING Tsu MECH PROBLEM R03 08/20/84 02-MS -TV -201A 003740 FURMANITE RIGHT SIDE - PACKING DRILL AND TAP PACKING GLAND AND INJ ECTED WITH FURMANITE COMFOUND NUCLE AR GRAIE FIBER CART LOT 1012 WR NO.045026 SUBMITTED TO RETURN TO ORIGINAL R03 09/22/84 02-CH -FCV -2114B 003578 ADJUST STROKE REPLACED DIAFWAGM IN VALVE FOUND N OTHING WRONG WITH OLD DIAFtiRAGM l R03 08/22/84 02-SHF-HSS -17 0035F2 LOW LEVEL IN ESERVOIR CECK SNUBBER RESERVOIR.BEFORE l FILLING 75% FILL TO 95X t l R03 08/27/04 02-MS - -377 003985 FURMANITE REINJECT FACKING REINJECTED VALUE PACKING WITH FlRMA NITE NUCLEAR GRAIE COMPOUND N-FIBER CART LOT # 1011 TO STOP LEAK.WD l SUBMITTED TO REPAIR 6098630 R03 08/27/84 02-MS - -381 003971 NIGH PRESSURE STEAM LEAK ON DRILLED TAPED AND INJECTED VALVE B0 NNET WITH FURMANITE NUCLEAR GRADE C OMFOUND F 83 NEW LOT till TO STOP LEAK. WO SUBMITTED TO REPAIR WO WO $098631 R03 08/27/84 02-MS -HSS -34A 004204 FLUID LEVEL LOW FLEASE REFILL FOUND RESERVOIR 4/5 FULL AND ADDED 160UNCES OF SNUBBER FLUID TO RESERVOIR R03 08/29/84 02-CS - -069 004129 3/4" LINE COMING OFF 0F 2-CS-0 REh0VED PIFECAP REMGJED OLD TEEAD DOPE.USED FILE TO REMOVE BtRS FROM TmEADS.USED NEW TR EAD DOPE AND REINSTALLED PIPE CAP p R03 08/30/84 02-CH -P -1A 004356 REPLACE AUX OIL FUMP REMOVED OLD AND INSTALLED EW I AUXILIARY DIL FUF AND ADD AFTROX l 1 GALLEN OF OIL (IND 68) TO RESERVOIR O h e 9
t Page.29 of 38 O MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS l UNIT NO.1 ELECTRICAL MAINTENANCE 1 4 + o
Page 30 of.38. -
VEPCO SAFETY RELATED DLRING REILCED PulER SORTED BY LMIT AVO DEPARTPENT PROGRAM F T09860 09/10/94 15I06 FROM 08/01/84 Tistu 08/31/84 LMIT 01 SLRRY RETtstpED TO WD DEPT SERVICE MARK NLMBER NLMBER WO TITLE HISTRY SL39WtY R04 08/10/84 01-EPH- -IC 003504 REPLACE 1C RSS LEAD FROM TRANS PERFUDED "HI-POT" TEST ON CABLES F CR C RSS XFP5t DECKED ALL CABLES AN D FDLMD 1F1PH9 (M C 0 TO IE BAD 8/10/B4 R04 08/13/94 01-NI -REL -IRBYB 003431 RELAY IS ET PICKED LP SELLD REPLACED COIL AND RELAY AS!EMBLY AS PER EPP-C-RT-24 9-9-64 R04 08/16/94 01-EE -90/ -104 003679 Sp/ WILL ET (PEN REPLACED COIL AfE AUX CIMTACT R.DCK IN 1-EE-P-1C M.C.C. R04 08/16/94 01-EPL-BKR -1912 003559 CIRCUIT BREAKER TRIPS AND BRIDGED AND EDGERED AC 9.2 AB 8.67 BC 9.2 PEG (ED 1000M 'A' CAUSES BREA KER TO TRIP TEST BKR SAT SUSPECT 'A ' PHASE AS PROBLEM 8-12-94 EATER SE EMS TO BE SAT EST TAG BKR 1481-2 ~ ~ R04 08/16/84 01-IA -C -4B 003036 AIR COPP BKR TRIPS n4EN CDPRE PERFIRED PMS ON 1-IA-C-4B AND TEST RAN SAT,ND PROR. EMS FOUE WITH TE 4 BREAKER TRIPPIE R04 08/1484 01-IA -D -4B 001993 HI(M TDP ALARM IN lMILE PERF(RMING PMS ON 1-IM-4B TE AIR DRYER DEIXED OUT SAT AND D i ID DOT TRIP TE BREAKER 9-14-64 R04 08/16/84 01-MS -SOV -102A 003336 ELEC. DISC 0f0ECT/ RECD 9ECT DISC 30ECT SOV B-14-64 INSTALL AND AD.1ET LIMIT (M SOV 102A B-15-64 R04 08/16/94 01-MS -SOV -102B 003335 ELECT. DISCOP0ECT/RECOP6ECT DISCDGECTED SOV'S DEED 20" (F #1 LIRIID TIINT FOLMD LIQUID TISHT BROCKEN.INSTALLAND AILRJST LIMIT ON SOY 102B 9-15-64 R04 08/16/B4 01-SW -MOV -105C 003733 DO NOT DET CLOSED INDICATION C REAILXJS1ED' LIMIT SWITDES AND TESTE D SAT 9-16-44 R04 08/21/B4 01-NI -DET -32 003521 REPLACE PRE-#P REPLACED PRE APP AND PERFIRPED PT-1 4 ON ERAlER TO RETLRN TO SERVICE R04 08/22/B4 01-RC -PT '-456 003432 ALARM IS SPtRIOUS AND IS BEI E REPLA 2 D PC-456A PC-456B PC-456C PC -456D AND PM-456 AND PM-456A DECKE D F(R LOOSE C0f0ECTICMS BUT FEMD N GE.PERFIRPED PT-2.4A SAT IO(ITIR L O(P WITH RECGtIER 90 SPINES R04 08/23/94 01-01 -P -2D 003669 REMOVE INSLLATION/DISCD9ECT llEEVED EAT TAPE AND DISCWSECTED 9-20-84.IIEINSTALLED EAT TRACE REPAIRED FLEX 31 STRIP EATERS 9-23-94 R04 08/23/84 01-RC - -4GSC 003998 ALARM IN 90LLD ET E IN "DE KF RELAY 15B3 AS FGMD READIES lERE ACCEPTABLI BUT DLE TO LDEXPLAN (PERATIONS TE RELAY 1%S BEEN REPLA - CED WITH STOCK PARE KF R04 08/29/94 01-EE -BKR -1H12 004228 BREAKER 15 ICT 1ABELED AND IS SWlE i
- 1I04 '88/30/94 41-EPH-tKR -15J10 004121 REPLACE PIN AND 9'RIE IDFLETED INSTALLATION IF CL(ME '
1AltH ANTI SED 1PRIIG AND 4EW ~ COTTER KEY LEIM PRG2R5lE TDP-C-E ^ PH-129 BLEAKER TESTED F29-94 SATIS 'TACTGtY e 4104 -08/30/94 01-4E -PCV -102A 404316 SISCDGECT/IEIDGECT ILECT. LIMIT SIITDES afb SOV 185LTED FR0 fl YALUE 8-29-64. LIMIT SIITDES AfS NIV 4ERE AUEADY IM UALVE DEDO p p. 70 MAKE E5lE EVERTHIIE ABEINED E F1104 L ~ M /94 01-95 -PCV -102B 004315 SISC30EL7/IEIDGECT ELECT LIMIT SIITDES AND SOV LIGELTED l 4 fit 0M UALUE 4-29-94 LIMIT SWITDES AND 1mV nERE ALflEADY ML1ED LP DECRED TO SEE IF ABENED 1 .1 _ g ~ er e y ww --.----e,.,, ,ee w-+-+ --w-c-s-~ew e e--'w wso-'-ve--w----+--%,e -ewvv--eav--we*-we--wwwe-=-e~= = - = w
3 Page 31 of 38 4 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING ~ OUTAGE OR REDUCED POWER PERIODS UNIT NO. 2 ELECTRICAL MAINTENANCE . ~.. _.. _. _ _ _. _ -. _,..
O P ge 32 of 38 WPC0 SAFETY RELATED ILRING REDLCED POWER SDRTED BY UNIT AND DEPARTMENT PROGRAM F T09860 09/10/84 FROM 08/01/84 Tmu 08/31/84 UNIT 02 SURRY RETLRNED TO WD ICPT SERVICE MARK NUMBER NUMBER WO TITLE HISTORY
SUMMARY
ADJUSTED LIM 5T SWITCH ARM ON IFFER R04 08/10/84 02-CH -FCV -2113A 003417 INTEREDIATE INDICATION SWITCH TO GIVE OPEN LIGHT FAILURE MDIE: INCORRECT LIGHT INDICATIONS: FAILURE MECHANISM: LIMIT SWITCHES OUT OF ANUSTMENT R04 08/1l 94 02-DA -LS -121B 003707 HI LEVEL ALARM WILL NOT CLEAR AFitIED HEAT AT 1930 CHECKED WITH OFS AND ALARM 13 NOW CLEARED R04 08/17/84 02-RC -BKR -4/4 003698 14:EAKER TRIPS AND WILL STAY BRIDGE AND MEGGER SAT BKR STILL TRI PS 8-15-84 70 AMP (W) CAT 3 EHL3070 A R04 08/17/04 02-RP -IKR -A/B 002784 INSTALL TIMING CIRCUITRY IN TIMING CIRCUIT ADDED TO A+B BREAKER S AND INST TECH PT 81 CONFtETE RETURNED TO NORMAL OFS 8-16-84 R04 08/20/34 02-RI -ANN -AA7 001833 ALARM WILL NOT INDICATE BULBS JUHFER CONTACT TO GIVE ALARM IN CONTROL ANN BOARD. REPLACED CAER NO CECK ALARM SAT 4 R04 08/22/84 02-FP -PNL -2 004016 POWER FAILURE LIGHT IS ON FUES FOUND TO BE BAD ORDERED NEW FU SE MIN 5 STOCK 40325214 INSTALLED F USE AND RESTORED FT)WER TO DETECTOR IELUGE PNL.CECKED WITH CONTROL R00 M OPERATOR TO CLEAR ALARM i R04 08/23/84 02-HS -PNL -2A1 003905 t#CERTEMP INDICATION LIGHT IS CKT 55 NOT IN SERVICE THIS MODULE IS A SPARE CKT 53 IS TE LAST CNT L ISTED IN BOOK 2A1 f R04 08/30/84 02-MS -LC -497BX 004029 RELAY IS CHATTERING EXISTING RELAY REMOVED EW RELAY INSTALLED R04 08/31/84 ObCH -P -1A 004494 AUX OIL PUPF DRAWS HIGH FOUND THE EATERS WERE TO SMALL MOT (R PtLLS.86 MS HAETERS 111 i GOOD FCR.598 1115 HEATERS WERE FUT IN. b t e o f t ,a
Page 33cof'38 MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNIT NO.1 INSTRUMENT MAINTENANCE I e e-y- g m, w- ,-g w-w-2- y w-9 ++gaw, g w-+ wr-y-,- y- ,-w-----,m-------w---g,r --tw, w-g-g.,,e----v-,+w-y-, m,e g g r-g-N-,
VEPCD $ SAFETY JtELATD ILRINO REDU::D PDER SDRTD BY UNIT AE DEPARTENT PkDGRM IFT09860 09/10/84 15tC6 FROM 08/01/94 T)stU 06/31/94 UNIT 01 SURRY Page 34 of 38 RETIKeED TD 61 0 . DEPT SERVIE MARK E SER NLMBER WO TITLE HISTORT SUPMARY T22 08/03/84 01-RP -MISC-FB 003153 IRFI F-B STLI:K REMOVED AND AD.1JSTD POINTER AND RE INSTALLED IEICATIONS CECK 0000 T22 08/13/94 01-RM -SV -111 002976 MONIT(R SPIKING CAUSING HI ALE MONITDRED PROBLEM Ftm 7 DAYS COLLD DCT DET PROBLEM TO IAP ICATE RETLRNItG PENIT!R TO SERVICE l T22 08/16/94 01-RP -MISC-D4 002133 VERY INRATIC DEDICATION PLACD.AAPER IN ROD BUTTOM BISTABL E MONITGIED ROD VELTE FOR SEVERAL DAYS. REEVED. ASPER ON BISTABLE DE CKED AND RETLAtED TD SERVICE TOOLS 1 V(LTETER VO-24 T22 08/16/B4 01-51 -PT -929 002697 RECALIBRATE/LARGE DEVIATION BE DECKD CALIBRATION OF INDICATER SAT T22 08/16/94 01-SI -PT -931 002698 RE:ALIBRATE/LAR(E DEVIATICH BE DEKED CALIlutATION (F INDICATOR SAT PROCEDL5tE SENT TO ENDIEIRIE TO(LS DMW VO-15 T22 06/20/84 01-RP -MISC-N/A 003421 CPUT SETPOINT LENT LD INVESTI-VOID SNE AS 3902003422 l T22 06/21/84 01-CS -LI -100D 002B40 CHIV RWST LEVEL READS LulER TH AILEJSTED INDI:ATOR AS PER PT.219A DECKED SAT PT SEh7 TD EE T22 06/21/B4 01-RC -TI -467 003870 TDPERATINtE IEICATOR FIR P DECKED TE CALIBRATION OF TE LIN-LEVEL NFLIFIER AND INDICATER ALSD DECED TE RTD RESISTMCE ALL IGij LES NE WITHIN SPEEIFICATION DECKE D SAT T22 06/22/94 01-CV -P1 -101A 003805 ).1 DP DIFFERENCE BEThED 1-C 2ERO SHIFTED ON TRANSMITTERS.PERFOR ED TRANSMITTER CALIBRATION DEKD SAT (BOTH CHAl#ELS P-CV-101A & 101 B) PT"S SENT TO DEIMIRIE T22 06/22/94 01-ftM -RI -160 003603 IENITER FAILD TIOHTDED FLEE DEUER DEKED SAT T22 06/22/94 01-VG -4tM -130/2 OC2230 REPLA 2 PLPP REPLACED PUPP ELETRICIANS TA0(E . D BREAER AND REMOVED LEADS TD PL7F i T22 06/24/94 01-BR -LI -103A 002103 CALIBRATE EVEL IEICATIR PERFORED CALIBRATION COPPLITELY MA DE MDER AD.AJSTENTS AS EESSARY (PS SAT T22 08/24/94 01-BR -LI -103C 002104 CAJBRATE PETER (FUPP CAVITATED PERFORPED CALIBRATION PR6CEILFC l CDPITELY MADE MINOR AILAETENTS AS REDUIRD i (PS SAT l , T22 08/24/94 01-CH -+CV -1104 003863 C BAST RE::IRC VALE WILL E T REPUGD RESTRICTER PLIE ABSY T22 08/24/94 01-HI -YI -100C 003963 LITT BAR (N LIMI9t4PH ET REPLACED IIISPLAfDMt AND DEKED LLMI9tAPH T2_2 0.8../24/B4 01-RC -TR.4099 003182 RED PEN IS DIRATIC REPLA2D REI:0RDER SERVO ETOR,CALIB T22 08/24/94 01-51 -PI -1943 00372B GALDE PCT POLNTD TD BRACKET ICLNTED Id7D E150lET ~ T22 08/24/94 01-SI -PI -1944 003727 94 LIE ET POLNTED ON BRACKET 1CLNTED GLMOE TD 3 RACKET IPS SAT T22 418/30/94 01-RM -4tR -150 004258 RE-IE REIUtDER IE PAD REPLACED LTtNT PRINTDE TE PADS PADS PN 430735591-501 30735591-506 30735591-503 122 48/30/94 01-YS -IET -100B 004095 4AAIINIIG ALARM WILL POT CLEAR PERFUtPED CAL 41HTIND CALIIRATION CARD REIEf! RED AILAJSTIENT. AD.AETED SAPE-{P SAT 722 08/31/94 01-CC -PI -1139A 002593 lIISCHARIE PREES SALIE fEDIED H CALIBRATD IISICATER m 08/31/94 11-Di -P --2B -003866 84 LIE TEDS 701E ItECALIBRATED REPLACED RAE 1PS SAT 'T22 38/31/94 D1-Di-PI -1151 903359 #EALIBATE SMLIFY AND ASSIGIE PERFUDED PT 40 SALIE JPS SAT 722 9B/31/94 01-eW -H34 -102 004196 IMPECT & ltEPAIR A6 IEIESSARY INSTALLD EW ADtCMG OUTPUT 4GILLE AND CALIBRATD IT. VELTIETER SIE212
Page 35 of 38 i MAINTENANCE OF SAFETY RELATED SYSTEMS DURING OUTAGE OR REDUCED POWER PERIODS UNTT NO. 2 INFTRUMENT MAINTENANCE I s
Page 36 of 38 VEFC0 - SAFETY RELATED IllRING REDUCED FSER SORTED BY UNIT AND IEPARTMENT PROGRAM IFT09860 09/10/84 15:06 FROM 08/01/84 T}RU 08/31/89 UNIT 02 SURRY RETURNED TO WO IEPT SERVICE MARK NUMBER NLFBER WO TITLE HISTORY
SUMMARY
T22 08/16/84 02-CH -FCV -2114A 003158 REMOVE REINSTALL INSTRUMENTATI REFLACED INSTRUMENTATION ON VALVE AND STROKED FROM CONTROL ROOM T22 08/16/84 02-CH -FCV -2114B 003159 REMOVE REINSTALL INSTR'JMENTATI REMOVED INSTRUMENTATION FOR VLAVE MAINTENANCE 8-10-84 REFLACED INSTRUMENTATION T22 08/16/84 02-FW -FT -2486 003664 TRANSMITTER INDICATING LOW REPLACED FM-486 AND PERFORMED IMP-C -RP-009 AND PT-2-10A ON NEW MODULE T22 08/21/84 02-RI -MISC-422B 003422 HM-2-422B FUNCTION GENERATOR REF1. ACED FUNCTION GENERATOR AND CHE CKED CALIBRATION PT SENT TO ENGINEERING T22 08/21/84 02-RM -RMS -260 003525 ALARM SETFOINT 11% HIGHER THAN CHECKED SETFOINST IN ACCORDANCE WITH CALIBRATOR PROCEDURE T22 08/23/84 02-NI -MISC-NA 003925 PERM. STATUS LIGHT NOT LIT. REPLACE RELAY i PRB-XB 8-21-84 T22 08/24/84 02-IC -IC -B 003673 REFtACE INCORE DETECTOR 'B' REPLACED B" INCORE IETECTOR T22 08/31/84 02-RC -MISC-408 002802 TONE READS 21/2 F HIGER FERFORMED REPLACEMENT OF TAVE AM-PLIFER VEPCO STOCK 1430252. OP CK AND CALIBRATION SAT. PART ?4739932 END OF REPORT
m. Page 37 of 30 HEALTH PHYSICS Aucust, 1984 'Ihere was no single release of radioactivity or radiation exposure - specifically associated with an cutace that accounted for more than ten percent of the allowable annual values in 10CER20. F 9 l
Page 38 of 38 e PROCEDURE DEVIATIONS REVIEWED BY STATION NUCLEAR SAFETY AND OPERATING COMMITTEE AFTER TIME LIktn SPECIFIED IN TECHNICAL SPECIFICATIONS August,1984 Number Unit Title Date Date Rev. Deviated g SNSOC EMP-C-EPL-70 1 Replacing Terminal Block 3-2-83 8-23-84 Termination with Raychem WCSF-N Type In Line Field Splices MMP-C-HSS-023 1,2 Corrective Maintenance Procedure 4-2-84 8-21-8 4 for 8" and 10" Grinnell Hydraulic Suppressors Dual Bleed Orifice MMP-C-CN-132 1 Replacement of Condenser 9-27-83 8-28-84 Expansion Icint Rubber Belt 1-SC-CN-1A M MP-C-CN-132 1 Replacement of Condenser 9-27-83 8-28-84 Expansion Joint Rubber Belt 1-SC-CN-1B
o + .g t t 1 I ) l This is a corrected page for July '84 Monthly Operating Report for Surry Power Station 1 9/14/84 l MD 1 1
Pagul0 of 36 o' e e
SUMMARY
OF OPERATING EXPERIENCE - Corrected ' Copy l MONTH / YEAR July,1984 Listed below in chronological sequence by unit is a summary of operating ' experiences for this month which required load reductions or resulted in significant non-load related incidents. UNIT TWO 07-01-84 0000 This reporting period begins with the unit at 100% power (775 MW's). 07-08-84 0356 Commenced power reduction for load following at 150 } MW's/HR. 0453 Holding power at 84% (660 MW's). 0710 Commenced power increase at 150 MW's/HR. 0800 Unit at 100% power (775 MW's). 07-09-84 0041 Commenced power reduction for load following at 150 MW's/HR. 0143 Holding power at 84% (660 HW's/HR). 0440 Commenced power increase at 150 MW's/HR. 0550 Unit at 100% (775 MW's). 07-16-84 0847 Turbine bearing indicating a vibration problem with #2 L.P. Turbine. 07-17-84 1930 Commenced plant shutdown at 150 MR's/HR to allow balancing #2 L.P. Turbine. 07-18-84 014 9 Unit off the line. 0221 Reactor shutdown. 1525 Reactor critical. 2005 Unit on the line. 2054 Unit at 35% power (230 MW's), holding for chemistry. 2234 Commenced power increase. 2340 Holding at 60% power (420 MW's) for return of "E" main feedpump. 07-19-84 0500 Commenced power increase. 0759 Unit at 100% power (770 MW's). 07-31-84 - 2410 This reporting period ends with the unit at 100% power (770 MW's). i l l
0 e x~n..n. VIRGINIA 1$LECTRIC AND' Powsu COMPANY Ricnwown,VamoxxrA 20261 - ' W.L.Stawaar . f,2*,",$"""","L September 14,:1984 Mr. Maurice R. Beebe Serial No. 551 Office of Resource Management N0/JDH:acm U. S. Nuclear Regulatory Commission Docket Nos. 50-280 Washington, D. C. 20555 281 License Nos. DPR-32
Dear Mr. Beebe:
DPR-37 VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT NOS. 1 AND 2 MONTHLY OPERATING REPORT Enclosed is the Monthly Operating Report for Surry Power Station Unit Nos. I and 2 for the month of August, 1984. ry.... t ru urs. \\ s W. L. Stewart Enclosure (3 copies) cc: Mr. R. C. DeYoung. Director (12 copies) Office of Inspection and Enforcement Mr. James P. O'Reilly (1 copy) Regional Administrator Region II Mr. D. J.-Burke NRC Resident Inspector Surry Power Station l - _ - _ _ _ _ _ - _ - -}}