ML20093B095

From kanterella
Jump to navigation Jump to search
Informs of Close Out of GL 89-10, SR MOV Testing & Surveillances Activities
ML20093B095
Person / Time
Site: LaSalle 
Issue date: 09/29/1995
From: Querio R
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
GL-89-10, NUDOCS 9510110227
Download: ML20093B095 (2)


Text

__

O>mmonwealtli 111iven Company laSalle Generating Station j

f 2601 Nortin 21st Road Marwilles, 11. 6134 l-9757 Tcl til5 3574>76I September 29,1995

)

United States Nuclear Regulatory Commission Washington, D.C. 20555 Attention:

Document Control Desk

Subject:

Closcout of Generic Letter 89-10 Activities

Reference:

1. D.L. Taylor (Comed) letter to US NRC, dated September 28,1990.
2. L.O. DelGeorge (Comed) letter to US NRC, dated November 1,1993.

The Reference I and 2 letters transmitted LaSalle Station commitments to complete required actions associated with Generic Letter 89-10, " Safety-Related Motor-Operated Valve Testing and Surveillances". This letter notifies the NRC, per item m. of Generic Letter 89-10, that actions a. through h. are completed with exceptions noted below. This letter transmits LaSalle County Station's request for closure of Generic Letter 89-10.

There are 8 Motor Operated Valves (MOVs) on LaSalle Unit I that still require dynamic testing. The 8 MOVs,4 globe valves and 4 flex wedge gate valves, are ranked in the Low and Low Low safety significant categories of LaSalle's deterministic /PRA prioritization for the Generic Letter 89-10 MOV population. A margin evaluation of the diagnostic data from completed static tests has shown more than adequate margin is available. The methodology used considered the significant uncertainties commonly used to predict MOV reliability. The remaining tests are scheduled during the next refuel outage which begins 01/26/96.

If there are any questions, please contact Baron Westphal at (815) 357-6761, ext. 2770.

Respectfully, 4

/

/.

R. E. Querio Site Vice President LaSalle County Station 100G33 Gf 0

9510110227 950929

'1 0

PDR ADOCK 05000373 P.

PDR A linicum Company

a

,. H. i. Miller, Regional Administrator, Region III cc:

W. D. Reckley, Project Manager, NRR P. G. Brochman, Senior Resident Inspector, LaSalle D. L Farrar, Nuclear Regulatory Services Manager, NORS Central file 2