Nonradiological NPDES Permit Violation Repts,Nov 1983 - Apr 1984
ML20092M058
Person / Time
Site: Palisades 
Issue date: 04/30/1984
From: Johnson B
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8407020117
Download: ML20092M058 (13)


Text

{{#Wiki_filter:-- i;. ?,'. i i d ATTACHMENT Consumers-Power Company Palisades Plant - Docket 50-255 COPIES.OF NON-RADIOLOGICAL NPDES PERMIT VIOLATION REPORTS ' November-1983 through April 1984 s' t n-t - 8407020117 840430' .PDR ADOCK 05000255 R PM a:: 10 Pages '.0C0584-0021 A-NLO2 - MO [ ib I e

rv u-- -g g s-g.y. I ~ f -t ~. f i ~ t I i F I I ATTACHMENT Conaumers Power Company Palisades Plant - Docket 50-255 i COPIES OF NON-RADIOLOGICAL NPDES PERMIT VIOLATION REPORTS. November 1983 through April'1984 r l C ) t L i t 10 Pages OC0584-0021A-NLO2 e _ ~..., _.... _ _. -.... _. _.. _ _..

File No P10.2.1 i Incident No: PAL-84-03-AD92 i A . NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitatien April 5, 1984 ' Plant: Palisades Permit No: MI 0001457 i - Outfall

Description:

Radwaste (00E) Outfall Code No: 800217 Boronj otal Chromium Parameter Code No: 01022, 01034 T Parameter: 1. Dste of Incident: March 11 to March 14, 1984 2. Identification of specific effluent limitation or monitoring requirement affected: The NPDES Permit requires radwaste releases be analyzed for boron and total i chromium content. 3. Description of Incident: From March 11 to March.14, 1984, 87,500 gallons of water from the condensate storage tank was released without being monitored for boron and total chromium. This oversight was discovered on March 15, 1984 at 1500 hours. 4. Apparent Cause: Plant Procedure HP3.6 did not identify boron and chromium as required analyses of the condensate storage tank if the tank was released as a radwaste batch. 5. If not immediately corrected, the anticipated time the condition is ~ expected to continue: NA. 6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: Plant Procedure HP3.6 will be revised to include the required monitoring. ' 7. Additional ~ Comments: NA. '8. Signed: RLFobesgg;rg; 7 d Revised 10/26/83 RP0384-0612A-TP02 L._

~ l STATE OF MICHIGAN DEPARTMENT OF NATURAL RESOURCES REPORT OF OIL, SALT OR POLLUTING MATERIAL LOSSES i i Pursuant to the provisions of Act 245 of the Public Acts of Michigan 1929 as amended, regulations have been issued which require that all owners, managers or operators of ve sels, oil storage or on land facilities shall notify the Water Resources Commission or his authorized representative of oil, salt and polluting material losses. This notification shall be made promptly by telephone or telegraph, giving briefly the particulars, and by mail, giving a detailed account of events and conditions. Date Compe.7y Name March 8, 198h Consumers Power Company Lacetion of Loos (se specific) CP Co - Palisades Nuclear Plant. Route 2. Box 15h. Covert. Michigan h90h'4 T-10 (Diesel Fuel 011 Ste' rage Tnnk) area - scuth of nl ant Motones Lost Amount Name of Surface Water levolved i -Fuel oil h0 gallons None l Date Loss was Discovered Time of Discovery l February 2h, 198h 1h30 Name tf Department of Natures Resources Representative Contacted Operator 2h, PEAS System - MNDR [ Teeephoned or Toiseraphed by Whom Time j A. Clark Kahn 2/2h/8h G 1600 hours Cagse of Loss Uncsude Type of Equipment and Otner Detsiis) Fuel oil tank (T-10) was overfilled. forcing oil through the finna arran+4ne vant. ) l i l l Nature tf Loss Unclude Complete Descnotion of Demogel l As the oil erited the fl ama arrestar pine it epillaa nntn +ha enn+h e4aa ne P_7n ninng a trailer and onto the ground. Thirty to forty gallons were lost. r t Additior.et Comments Unclude Method of Control, Piens for Provention of Recurrence, etc ) A crev van 4e nd4ntely mnh4147pd tn nlaan up tha ep411aa nil-Tha n1 ann up mn+av4 ale and the oil-contaminated soil was removed and the vaste placed into barrels. The vaste will then be disposed of in the appropriate manner. In the future, the filling operation of Tank T-10 vill be closely supervised in order to prevent any recurrence. l Company Nome By (Signature) Consumers Power Company A C Kahn j 24-Hr Emergency Notifiestion Number (800) 292-4706 RmMhm Environmental Department Pernall Road Jackson, Michigen R461S t 10/73 r* 4--w .'-tt-w-'w-w- yw--- mer ..y.yy.y. ,e w,,,. _, ,q-,.,, ,,y.

j SPCC/PIPP e fl't.'SIlI.*

  • ,3;,.....t y

~. App 2nd1x C i i j', /,, 'l 4_ ! ~~ k Rsvisica 3 y'.] .s. _. > / / c 7 ' - v-,'- - ; w.

  • s. /,,

Pags 2 of 4 s.tLi.p;r-8 16 %g... m., .t..m. 4 .m .s

1..

..g W > ' * /s. M,7 ? k :. ~ ~. l. Cg '.n), 3~ 4~w j I..9.-L_ q'1 ~ - - s

y i

I' l . g( ~ i, g I ', - I . k [//i':h g 3,. i 3 gj 'i i w ,l, g' t a m . 1, .. (('I l i -l-??Q t l__; t v ~ v.' /_. ', 4 ,/ %< q--} ._.{p i I -, e c _( r

3...

s! 4 F., o p-j\\ ci.: i r, _ y --. .r p i. ,i j r s.. -i .I. a- - .. wm . ti, l ind a

it9,

! Iy t ),, s r- .i}. ',. I g 'I q. j_I i. 4 y I 4 u $4 . i: ,a I m 1 i ,i af ./- i L tt ,i 4 >/ 8 e fr[ ( LJ- _' s.W ', ~ d]- g am t- - > ( s '.,,, - e, .,r ,....f. ._ g : W ___._. 2. s., r ....... W o c.-- C ~'p.... n 1... 1 .l N L y l yJ g.-.g . ;.,, m Q s 0 - 4j t d

v. -

O .s s, r ',. / ' V_; W. N w 1 l i g g.,,,3 ) s/- _-

)

u.I a

aJ./ ~-

l! )c l '9 j/ S' l // . t, 3 N. p-i-, l > / /p'e / r 7 s[ i ;i H .g l.l -N., N -f-3 ,'l-t.=f .N g

  • L.c

. \\'] ~., [' 6.f i j i / /- g"" l N %'

  • [. 7 [

[,gj e' ea.' ,..y,;, 3/. Q 4' J g .,3 .e/// u c m-g (Ne8 i,, a. 2,, / /,'/,' h .6

    • +

/ '... 5 s

  • y o,-

gy /c + r.N pg s w e 1 et o .t.' s

Fils Na P10.2.1 Incid:nt No: PAL-84-02-AD91 _s NPDES NOTIFICATION ' Apparent Difference From Daily Average / Maximum Limitation March 8, 1984 Plant: = Palisades Permit No: MI 0001457 10utfall

Description:

Discharge to Lake Michigan (001) Outfall Code No: 800095

Parameter: 1 Total Residual Chlorine (TRC)

Parameter Code No: 50060 - 1. Date of Incident: 2/17/84 2.- Identification of specific effluent limitation or monitoring requirement affected: The NPDES permit requires three grab samples of the plant discharge to be collected and analyzed for TRC during the chlorination of the plant circulating and cooling water systems. 3. Description of Incident: On 2/17/84 during chlorination.of the service water system,' only two grab samples for TRC were collected instead of the required three samples.

4. Apparent Cause:

Technician error. The technician had not been involved with chlorination procedures for the past six months. The plant's chemistry procedures 'specifically require that three grab samples for TRC be collected during chlorination. 5. If not immediately. corrected, the anticipated time the condition is expected to continue: NA

6. ' Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence:

All technicians were reminded of the TRC sampling requirements as well as other responsibilities and requirements of the NPDES permit. The plant's chlorination data sheet is also being revised to include the NPDES sampling requirements during a chlorination. 7. ~ Additional Comments: The second sample of the plant discharge was taken at the end of chlorination and measured less than detectable (<.02 ppe) TRC. 8. Signed: R L Fobes s miO384-0144a-46

r Fils No P10.2.1 Incid:nt No: PAL-84-01-AD90 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation i February 15, 1984 Plant: Palisades Permit No: MI 0001457 Outfall

Description:

Intake (000) and Discharge Outfall Code No: 800149 to Lake Michigan (001) 800095 Parameter: Temperature and pH Parameter Code No: 00011 00400 1. Date of Incident: 1/7/84 and 2/4/84 2. Identification of specific effluent limitation or monitoring requirement affected: Continuous monitoring of intake and discharge temperature and pH is required. 3. Description of Incident: On 1/7/84 the pH recorder, pHR 1312, was found to be malfunctioning. The pH readings were erratic, fluctuating off scale from low to high. The pH recorder remained out of service until 2/3/84. On 2/4/84 the temperature recorder, TR 5370, failed to operate properly. The recorder was out of service until 2/8/84. 4. Apparent Cause: ~ The ribbon cable on the pH recorder shorted out to the instrument case. The temperature recorder had a faulty switch and ribbon cable.

5. -If not immediately corrected, the anticipated time the condition is expected to continue:

NA 6. Corrective Action - The'fo11owing corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: The pH recorder was removed from service. A maintenance order was filed. The ribbon cable was replaced and a loose wire to the probe was also repaired. The pH recorder was calibrated and returned to service after repairs were completed. The recorder ribbon cable will be made a stock item. A maintenance order for the temperature recorder was initiated. The recorder's switch was repaired and the ribbon was replaced. The temperature reco.ier was then returned to service. 7. Additional Comments: While the pH recorder was out of service, the discharge to Lake Michigan was grab' sampled and analyzed three times per day for pH. While the temperature recorder was out of service, temperature repdings of the intake and discharge miO284-0307a-63-48 i

~ 2 were taken~ once per shift. The plant is investigating placement of a redundant temperature recorder for each parameter to be placed at a local sample point to minimize recurrence of this event. t 8. Signed: R L Fobes i I f t F i t l I t L t I I i t 1 I i i i e 1 i i miO284-0307a-63-48 t _,._,.-_,__,,._._....m_ ,,r,,

STATE OF MICHIGAN DEPAltTHENT OF NATU8 tit. Esc 50uRCES REPORT OF CIL, SALT GR POLLUTING MATERIAL LCSSES Pursuant to the provisions of Act 245 of the Public Acts of Michigan 1929 as amended. regulations have been issued which require that all owners. managers or operators of vessels, oil storage or on land facilstres shall notify the Water Resources Commission or his authorized representative of oil, salt and polluting matenal losses. This notification shall be made promptly by telephone or telegraph. giving bnefly the particulars, and by mail, giving a detailed account of eve'ts and conditions. u.a. G.m a, seam. January 19, 1983 Consumers Power Company 6.s a 6 .G. S cssa At the T-10 storage tank site located at the CP Co Palisades Nuclear Plant near Covert, MI as

n. 6.m a

Ebel Oil 150 None o6 o t.m. e o ,y January 11, 1984 1850 hrs si e o a maiw a a m com ceae Operator 15 (Beth Mersch) Michigan Department of Natural Resources r a - r y ea .,wa.- 1 T Kanicki, Duty Shift Supervisor 2053 hrs c 6 r, . s o a.,o A tank truck appeared to have been using excessive pressure to fill the T-10 storage tank, near the completion of the fill operation (see attached map). l c o n-. o. .The fuel oil overflowed.from the T-10 vent pipe while the tank truck was pumping in the inst 500 gallons of fuel oil. The lost oil was trapped in the snow around the vent pipe and the south side of the tank. i c ...a. c Clean-up was immediate. The effected snov was removed and placed in 8 barrels. Oil dry vill be added to the be.rrels and they will be disposed of according to regulations in a 1 licensed disposal facility. I c, e, is.,..... j Consumers Power Company A C Kahn l Return this form to: Environmental Department 24 hr. Emergency Notification Number Farnall Retd Jackson, Michian (900) tR2.-19 0'. [ A.4i$ terf3 _. _ _ _ ~

.x" / SPCC/PIPP q,y qg: gM o App ndix C e ~1-* ip 7 d q-fjNhIMf[ '.\\---, g /p, ',, 'y_- R",vi::1:n 3 2 _., i-a ',. C..-, - r----, a --, .'N i N j' ' ' '.? s,,. Page 2 of 4

  • H -{g '1-4 'lii 8

p.U.I ]Lp,..j s. f..,f/*/..I _ '- .it r, - '.'.,fs. ' 3, -. $n i s1l3lg. .~ j \\ //./ . c1. s > y--s / '\\ ,T a s s ie;ql $,q9.;4 o iI-(_,.,

/

. i. - .- \\ f j!. .[, . ! [ y, =... 8 ..___i "'7_ 3 <~ E' l -jf, e { 7 !*l i.. '. - !'i I I !]: fi. -- -t j {Ne /- '\\ 4 e' J$ j I ~ ._j_3a II i.i!. (- i --[. V v(/ f i i hw / W. -- r 1 c.f~ - i . _ J. ,.i -*~ T -4..F J -N ' r S. a ~.a 'n.. M ,i. p t \\ U 4 = l I, L.i I --2 t.. _. " )l l 1 u sJ l \\ 8 e .8I 6 e Q e,%g s- - s.4 ,.A 3 e 1 I (--) 1 7 N== l -N;ff I, a! l I i o s i t__ n a.. o l ..4 y 1 o .s 3t = y' p f f I, lf, ,a ! [_,. E. [ /,,ye p ( N 3.-.,'- a..'k' 3 \\\\ .o+ l u ig7::.. , e r'. u....s~-- , c J l ~~ w,-p. u. I C Q *s f.).... . e m,..._.t . (.: W.

y. / ~'s,

.. t \\ y f

  • f"" q f"'~~~ -Q $1

~ %. 5 b -- ' ' ~~~. 1 = '~.~~;,'~~~) j g3 T l, l i Iw 1 ' i. s'; i - )... s I.I W* \\ { / [ Q "j .b &g ip .' y/- - y j zy ul 8 )il' j _ ~ ) I

  • l L #-

/ // "l h l'/ / j/ /, ' N '- g.O 2 i., /// l // , f 's N l ~.. s, g !~ j T-i i f .s,- ] lj /' o ..f N 'N 's.

i., /

L.. m% -g O ~ \\ ~,, e. F .,. / / fiif,f '> - ]~ Q ~. 0 :.c,,,* <,*., a-i s f, 'r' W .i / s 1.g( ; ,, / i s . f; /.y./, N N' S $-g 8 't, N . r.,n. ,s g i 3

2.,,.

s // 't-s ,7, N Q, s g(0 i / ?./g/ '24'y?;,r':~'~:,::.',. / ( I s x it

/
.. ~ ~

.,,q..e.-;,,'

7. 'e' Fila No P10.2.1 Incidrnt No: PAL-83-12-AD89 NPDES NOTIFICATION i Apparent Difference From Daily Average / Maximum Limitation January 6, 1984- ' Plant: ~ Palisades Permit No: MI 0001457 Outfall

Description:

Intake (000) and Discharge to Outfall Code Nos: 800149 t Lake Michigan (001) 800095 Parameter: Temperature Parameter Code No: 00011 1. Date of Incident: 12/16/83 through 12/20/83 2. Identification of specific effluent limitation or monitoring requirement affected: Continuous monitoring of the intake and discharge temperature is required. 3. Description of Incident: a From 12/16/83 at 2100 hours to 12/20/83 at 1700 hours the temperature recorder for'the intake and discharge samples from/to Lake Michigan was malfunctioning. 4. Apparent Caussi Printer malfunction. ~ 5. If not immediately corrected, the anticipated time the condition is expected to continue: .NA 6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: A maintenance order was initiated and the recorder was repaired. 7. Additional Comments: As an interim measure, daily grab measurements of Antake and discharge temperatures were performed. 8. Signed: R L Fobes a miO184-0105a-153 + um

j ' )I Fils No P10.2.1 IncidInt No: PAL-83-11-AD88 NPDES NOTIFICATION Apparent Difference From Daily Average / Maximum Limitation December 22, 1983 riant: Paix..Jos Permit No: MI 0001457 Outfall

Description:

-Turbine Sump 011 Separator Outfall Code No:

800218 Wastewater (00G) Parameter: 011 and Grease _(Freon) Parameter Code No: 0055C 1. Date of Incident: Week of 11-20-83 through 11-26-83 l 2. Identification of specific effluent limitation or monitoring requirement affected: The Turbine Sump 011 Separator Wastewater is required to be sampled and analyzed for oil and grease once per week. 3. Description of Incident: During the week of November 20 through November 26, 1983, the Turbine Sump Wastewater was not sampled. 4.. -Apparent Cause: Failure to take routine sample on 11-21-83. 5. If not immediately corrected, the anticipated time the condition is expected -to continue: NA 6. Corrective Action - The following corrective action was taken or will be taken to reduce, eliminate and prevent recurrence: A sample was collected on 12-1-83 when the oversight in sampling was discovered. This matter was also discussed at the weekly Technician meeting. A weekly checklist of required sampling and analyses was prepared. Additionally, a Plant Procedure CH 9.1, Site Surveys, is under development. 7. Additional Ccmments: Daily visual observations of the final discharge to the lake showed no oil or grease during this period. Visual analysis of the Turbine Sump 011 Separator Wastewater on 11-21-83 and 11-25-83 also showed no oil or grease. 8. Signed: R L FobesdF e rp1283-0502a-153 -__.___.-_...____.s.

bina r. Consumets . Power Company t . o.n.r.: ome : is4s 5.,e P rn.ii no.d. J.ck,on, ui 4920s. (st717ss-osso Y May 31,-1984 ij; t f(- W f

1. -

' James G Keppler,' Administrator ~ Region III US Nuclear Regulatory Commission 799 Roosevelt Road' Glen Ellyn, IL 60137 b DOCKET 50-255 - LICENSE DPR PALISADES PLANT - COPIES OF NON-RADIOLOGICAL NPDES PERMIT VIOLATION REPORTS i. ' Section 3.2 entitled " Reporting Related to the NPDES Permits and State

Certification" of Appendix B to Provisional Operating License No DPR-20 Palisades Plant Consumers Power Company Docket 50-255 Environmental Protection Plan (Non-Radiological) dated January 22, 1981~ states that copies of reports to the state of Michigan indicating violation of NPDES parmits are to be sent to the NRC. Attached.to'this letter are copies of.five (5) NPDES Notifica-tions covering the-six (6) month period from November 1983 through April 1984.

Also attached are copies of two (2) Reports of 011, Salt or Polluting Material

Losses that occurred during the same period.

' Brian D Johnson Staff Licensing Engineer CC Director, Office of Nuclear Reactor Regulation Director, Office of Inspection and Enforcement NRC Resident Inspector - Palisades Attachments E OC0584-0021A-NLO2 5f0l l \\ -}}