ML20092M036

From kanterella
Jump to navigation Jump to search
Special Rept:On 840504,loose Parts Monitor Channel 9 Inoperable for Greater than 30 Days.Caused by Open Connection in micro-dot Cable.Union Will Be Installed at Next Opportunity After Part Is Available
ML20092M036
Person / Time
Site: LaSalle 
Issue date: 06/25/1984
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
0382R, 382R, NUDOCS 8407020109
Download: ML20092M036 (1)


Text

.

@ RuralRoute #1, Box 220 Commonwrith Edison LcSalle County Nucim Station Marseilles, Illinois 61341 Telephone 815/357-6761 June 25, 1984 J. G.-Keppler Regional Administrator Region III U.S. Nuclear Regulatory Corunision 799 Roosevelt Road Glen Ellyn, Ill.

60137

Dear Sir:

This special report is submitted in accordance with LaSalle Unit #2 Operating license NPF-18, Appendix A Technical Specification 3.3.7.12 and 6.6.c.

On May 4, 1984, the loose parts monitor channel #9 was inoperable for greater than 30 days per Technical Specification 3.3.7.12.a/b.

The degraded status results from an open connection in the micro-dot cable which runs from the pre-amplifier to an accelerometer. This is caused from construction activities at the 820 level within the drywell. Maintenance, during a short outage pulled a new micro-dot cable to the accelerometer.

During the connection of the newly pulled cable and the accelerometer, a small female to female union was accidently dropped and lost. 'the station storeroom and instrument maintenance shop could not locate a spare, so the union (with spares) was ordered 1sunediately. Channel #10 is 180 degrees apart and provides redundant coverage of the area of the vessel that was being monitored by Channel #9.

' At the next opportunity after the part is available and the Unit is in cold shutdown the union will be installed. AIR-01-84-67082 was written to track this work.

This report is submitted late due to an oversight by the personnel responsible for reporting the inoper.sble equipment. These personnel will be reminded of the importance of prompt reporting of inoperable equipment required by the Technical Specifications, n

. J. Diederich Superintendent LaSalle County Station GJD/TAH/ceh

'cc:

U. S. NRC Document Management Branch Inpo-Records Center File /NRC 8407020109 840625 PDR ADOCK 05000 d

DOCUMENT 0382r O

UUN 2 7 maa

  1. , O