ML20092K371

From kanterella
Jump to navigation Jump to search
Amend 80 to License NPF-57,changing TS 4.1.3.1.2.b, Control Rods SR to Require That Action to Be Taken When Control Rod Becomes Immovable Due to Excessive Friction from at Least Once Per 24 H to within 24 H
ML20092K371
Person / Time
Site: Hope Creek 
Issue date: 09/20/1995
From: Stolz J
Office of Nuclear Reactor Regulation
To:
Public Service Electric & Gas Co, Atlantic City Electric Co
Shared Package
ML20092K378 List:
References
NPF-57-A-080 NUDOCS 9509250365
Download: ML20092K371 (4)


Text

_ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ -.

l qo 4

UNITED STATES NUCLEAR REGULATORY COMMISSION e

o l

f WASHINGTON, D.C. 20666-0001

/

PUBLIC SERVICE ELECTRIC & GAS COMPANY ATLANTIC CITY ELECTRIC COMPANY DOCKET NO. 50-354 HOPE CREEK GENERATING STATION AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 80 License No. NPF-57 1.

The Nuclear Regulatory Comission (the Comission or the NRC) has found that.

A.

The application for amendment filed by the Public Service Electric

& Gas Company (PSE&G) dated January 20, 1995, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Comission; C.

There is reasonable assurance:

(i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations set forth in 10 CFR Chapter I; D.

The issuance of this amendment will not be inimical to the comon defense and security or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 2.C.(2) of Facility Operating License No. NPF-57 is hereby amended to read as follows:

(2) Technical Soecifications and Environmental Protection Plan The Technical Specifications contained in Appendix A, as revised through Amendment No. 80, and the Environmental Protection Plan contained in Appendix B, are hereby incorporated into the license.

PSE&G shall operate the facility in accordance with the Technical Specifications and the Envirrnmental Protection Plan.

9509250365 950920 PDR ADOCK 05000354 P

PDR j

l

N j

i f.

.I^

n )

f 3.

The license amendment is effective as of its date'of issuance, to be implemented within 60 days.

FOR THE NUCLEAR REGULATORY COMISSION oh b. S o z, irector Pr ject Directorate I-i vision of Reactor Projects - I/II Office of Nuclear Reactor Regulation j

)

Attachment:

Changes to the Technical Specifications

'Date of Issuance: September 20, 1995 i

1 l

r

)

I l

l o-l s

ATTACHMENT TO LICENSE AMENDMENT NO. 80 FACILITY OPERATING LICENSE NO. NPF-57 DOCKET NO. 50-354 Replace the following page of the Appendix "A" Technical Specifications with the attached page. The revised page is identified by Amendment number and contains vertical lines indicating the area of change.

Remove Insert 3/4 1-5 3/4 1-5

[

e f

I v

REACTIVITY CONTROL SYSTEMS

'SURVIILIANCE REQUIREMEh7S (Continued) electrically or hydraulically shall be demonstrated OPERABLE by moving each control rod at least one notch:

e a.

At least once per 7 days, and b.

Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when any control rod is immovable as a result of l

excessive friction or mechanical interference.

i 4.1.3.1.3 All control rods shall be demonstrated OPERABLE by performance of Surveillance Requirements 4.1.3.2, 4.1.3.4, 4.1.3.5, 4.1.3.6 and 4.1.3.7.

4.1.3.1.4 The scram discharge volume shall be determined OPERABLE by demonstrating:

a.

The scram discharge volume drain and vent valves OPERABLE at least once per 18 months, by verifying that the drain and vent valves:

1.

Close within 30 seconds after receipt of a signal for control rods to scram, and i

2.

Open when the scram signal is reset.

I l

i v

l l

i

' HOPE CREEK 3/4 1-5 Amendment No.80 l