Text

M I%SC00 Sin Electnc eowca couraur 231 W. MICHIGAN, P.O. BOX 2046. MILWAUKEE, WI 53201 June 18, 1984 Mr.

J.

G. Keppler, Regional Administrator Office of Inspection and Enforcement, Region III U. S. NUCLEAR REGULATORY COMMISSION 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Mr. Keppler:

DOCKET NOS. 50-266 AND 50-301 RESPONSE TO IE BULLETIN 84-02 FAILURES OF GENERAL ELECTRIC TYPE HFA RELAYS i

IN USE IN CLASS IE SAFETY SYSTEMS POINT BEACH NUCLEAR PLANT In response to IE Bulletin 84-02, " Failures of General Electric Type HFA Relays in Use in Class IE Safety Systems" there are no GE type HFA relays used in safety-related applications at the Point Beach Nuclear Plant.

Westinghouse type NBFD relays are the equivalent relays installed in safety related systems.

These NBFD relays were initially supplied with nylon coil bobbins.

Because of concerns similar to those expressed in the IE Bulletin, the safety related NBFD relays with nylon bobbins in the Reactor Protection and Engineered Safety Features systems have been replaced with NBFD relays containing coil bobbins made on an improved material.

Please contact us if you have any questions concerning this submittal.

Very truly yours, bY 8406260275 840618

~

PDR ADOCK 05000266 Vice President-Nuclear Power G

PDR C. W. Fay Copies to NRC Resident Inspector l

NRC Document Control Desk, Washington (w/ original)

Subscribed and sworn to before me this ILtAday of June, 1984 l

blev 94 - e b71 reou JUtJ21 g Notary Publ/ic, State of Wisconsin l

hy Commission expires 7<,a o /9 PP f6II

-