ML20092A999

From kanterella
Jump to navigation Jump to search
Forwards Changes to 911230 Plant Attribute Library,Critical Safety Function Parameter List & Data Point Library,As Required for Implementation of Emergency Response Data Sys
ML20092A999
Person / Time
Site: Callaway Ameren icon.png
Issue date: 02/06/1992
From: Stiller M
UNION ELECTRIC CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
ULNRC-2554, NUDOCS 9202100392
Download: ML20092A999 (10)


Text

_ _ - _ _ _ _ _ _ - - _ - _ _ _ - _ _

m,'

r.

February 6, 1992 j

ONION ELI.I.'( 'TRIC

'!3 U.

S. Nucicar Regulatory Commission Attn Document Control Desk Mail Station F1-137 Washington, D.C.

20555 Gentlemen ULNRC-2554 DOCKET NUMBER 50-483 CALLAWAY PLANT EMERGENCY RESPONSE DATA SYSTEM DATA POINT LIBRARY CHANGES On December 30, 1991, Union Electric submitted a Plant Attribute Library (PAL), a Critical Safety Function Parameter List, and a Data Point Library (DPL) as required for implementation of the Emergency Response Data System (ERDS) at Callaway. The following changes should be in these documents and appropriately incorporated into your files.

1)

Page 1 of 3 of the Critical Safety Function Parameter List should be replaced to indicate changes in the Data Point Library (DPL) listed in Item 2, below (revised page is attached).

2)

The following changes to the DPL should be made (revised pages are attached):

PAGE PARAMEIEB QLD POINT ID NEW POINT ID 6 OF 61 REAC VES LEV SPDS0042 REU0523 10 OF 61 SG LEVEL 1/A SPDS0043 RELO404A 11 OF 61 SG LEVEL 2/B SPDS0044 RELO424A 12 OF 61 SG LEVEL 3/C SPDS0045 RELO444A 13 OF 61 SG LEVEL 4/D SPDS0046 RELO464A The old point ids toggled betwoon narrow range and wide range depending on plant condition. The new point ids monitor only wide range.

t I

I I

9ao2 0039a 92o206 PDR ADOCK 05000403 F

PDR

February 6, 1992 ULNRC-2554 Page 2 Also, the ERDS modem will be located in the TSC instead of the Plant Computer Room as indicated in our October 22, 1991 transmittal of the ERDS Implomontation Plan.

If you have any questions, please contact Mr. Al Whito, Supervisor, Emergency Preparedness, (314) 676-4961, or Mr. Eric Schulto, Engineer, Computer Support, (314) 676-8486.

Very truly yours,

/

Milton A.

Stiller Manager, Nuclear Safety and Emergency Preparedness MAS /AEW/dch Attachments cci A.

B. Davis, Regional Administrator, USNRC Region III R.

L.

Hague, Chief, Reactor Projects Section 3C, USNRC Region III M.

D. Lynch, USNRC Licensing Projects Manager (2 copics)

Manager, Elcetric Department, Missouri Public Service Commissioner, w/o D.

L.

Bartlett, Senior Resident Inspector Shaw, Pittman, Potts, & Trowbridge, w/o

i i

e i

1 e

l i

i i

CRITICAL SAFETY FUNCTION PAllAMl?TEll LIST

+

t i

I F

i I

t i

t I

i h

t.

[

s l

p 4

5 i

2/3/92

/

f STICAL SAFETY FUNCTION PARAMETERS PAGE 1 OF 3 E'

COMPUTER afsRAMETER DESCRIPTION UNITS POINT s

cr.NTROL ruclear.nstruments, Power Range

?

SPDS0059 3

w n1

'.s (NG Nuclear Instruments, Intermediate Range AMPS SPDS0060 Nuclear Instruments, Source Range CPS SPDS0041 NI '

s

.. L Pcst Accident 910e Range PCM SEN0701 NL Post Accident Source Range CPS SEN0702 COR1 COOLINC REAC VES LEV Rom s7r Vessel Water Level REU0523 TEMP. CORE EX Highest Tamperature at the Core Exit DEGF REU0090 SUS MARGIN Saturation Temperature-Highest CET DEGF SPDS0006 CORE FLOW Total Reactor Coelant Flow REUO487 STEAM GENERM )RS SG LEVEL 1/A Steam Generator 1 (or A) Water Level RELO404A SG LEVEL 2/3 Steam Generator 2 (or B) Water L?vul RELO424A SG LEVEL a/C Steam Generator 3 (or C) Water Level RELO444A SG LEVEL 4/b Steam Generator 4 (or D) W ' 9r Level RELO464A

.9G PRESS 1/A Steam Generator 1 (or A)

P., asure PSIG SPDS0022 SG PRESS 2/B Steam Generator 2 (or B) Pressure PSIG SPDS0023 SG PRESS 3/C

-? team Generr. tor 3 (or C) Pressure PF7G SPDS0024 SG PRESS 4/D Steam Generator 4 (or D) Pressure SPDS0025 1

MN FD FL 1/A Stm Gen 1 (or A) Main Feedwater Flow

<uB/HR SPF,S0026 NN FD FL 2/D Stm Gen 2 (or B) Main Feedwater Flow KLB/HR SPDS0027 MN FD FL 3/C Stm Gen 3 (or C) Main Feedwater Flow KLB/HR SPDS0028 MN FD FL 4/D Stm Gen 4 (or D) Main Feedwater Flow KLB/HR SPDS0029 AX FD FL 1/A Stm Gen 1 (or A) Auxiliary FW Flow KLB/HR SPDS0054 AX FD FL 2/B Stm Gen 2 (or B) Auxiliary FW Flow KLB/HR SPDS0055 AX FD FL 3/C Stm Gen 3 (or C) Auxiliary FW Flow KLB/HR SPDS0056 AX FD FL 4/O Stm Gen 4 (or D) Auxiliary FW Flow KLB/HR SPD30057 HL TEMP 1/A Stm Gen 1 (or A) Inlet Temperature DEGF SPDS0030 HL TEMP 2/B Stm Gen 2 (or B; Inlet Temperature DEGF SPDS0031 HL TEMP 3/C Stm Gen 3 (or Ci Inlet Temperature DEGF SPDS0032 HL TEMP 4/D Stm Gen 4 (or D) Inlet Temperature DEGF SPDS0033 CL TEMP 1/A Stm Gen 1 (or A) Outlet Temperature DEGF SPDS0034 CL TEMP 2/B Stu Gen 2 (or B) Outlet Temperature DEGF SPDS0035 CL TEMP 3/C Stm Gen 3 (or C) Outlet Temperature DEGF SPDS0036 CL TEMP 4/D Stm Gen 4 (or D) Outlet Temperature DEGF SPDS0037 I

v.

.e

. t.

.4 x_

DATA POINT LIBRARY 4

_o

.l 1

l iI

')

i

p. '.

l :-

p l --

i 8

{t l -

t l-:

i.

2/3/92.

,e

~-^A-

~

- Nl t.

-.'r,

DATA POINT LIBRARY REFERENCE FILE Page 6 of 61 Dcte:

01/13/92 R actor Unit:

CW1 Data Feeder:

N/A NRC ERDS Parameter:

REAC VES LEV Point ID:

REUO523 Plant Spec Point Desc:

RV WR A/B LEVEL AVG G:neric/Cond Desc:

REACTOR VESSEL WATER LEVEL Analog / Digital:

A Engr Units / Dig States:

Engr Units Conversion:

N/A Minimum Instr Range:

-2.500E+00 Maximum Instr Range:

1.250E+02 Zero Point

Reference:

N/A R3ference Point Notes:

N/A PROC or SENS:-

P Number of Sensors:

2 How Processed:

AVERECE S0nsor Locations:

REACTOR VESSEL Alarm / Trip Set Points:

N/A NI Detector Power Supply Cut-off Power Level N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failure Mode:

LOW t

l Temperature Compensation l

For.IM? Transmitters:

Y Level Reference Leg:

WET Unique = System Desc:.

USES DIFFERENTIAL PRESSURE ACROSS THE

~

VESSEL TO DETERMINE VESSEL LEVEL OR RELATIVE VOID CONTENT OF THE CIRCULATING l

PRIMARY COOLANT SYSTEM FLUID.

l.

VESSEL IS 43.8 FEET HIGH AND HAS AN INSIDE DIAMETER OF 173 INCHES.

MAY FAIL HIGH.

I

DATA POINT LIBRARY REFERENOE FILE Page 10 of 61 D2te:

01/13/92 R:acter Unit:

CW1 Data Feeder:

N/A NRC ERDS Parameter SG LEVEL 1/A Point ID:

RELO404A Plant Spec Point Desc:

SG A WR LEVEL G:neric/Cond_Desc STEAM GEN A WATER LEVEL Analog / Digital:

A Engr Units / Dig States:

4 Engr Units Conversion:

STEAM GENERATOR VESSEL IS 812 INCHES HIGH Minimum Instr Range:

0.000E+00 Maximum Instr Range:

1.000E+02 l

Z ro Point

Reference:

UTUBES R ference Point Notes:

N/A PROC or SENS:

S i

Number of Sensors:

1 How Processed:

N/A S nsor Locations:

STEAM GENERATOR A Alarm / Trip Set Points:

N/A-NI_ Detector Power Supply Cut-off Power Level:

N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failure Mode:

LOW

'T mperature Cc.fonsation u

For DP Transmitters:

Y l

L vel Reference Leg:-

WET

-Unique Systr'a Desc:

MAY FAIL HIGH.

l l

l l

DATA POINT LIBRARY REFERENCE FILE Page 11 of 61 Date:

01/13/92 Reactor Unit:

CW1 Data Feeder:

N/A NRC ERDS Parameter:

SG LEVEL 2'B Point ID:

RELO424A Plant Spec Point Desc:

SG B WR LEVEL Generic /Cond Desc:

STEAM GEN B WATER LEVEL Analog / Digital:

A Engr Units / Dig States:

Engr Units Conversion:

STEAM GENERATOR IS 812 INCHES HIGH Minimum Instr Range:

0.000E+00 Maximum Instr Range:

1.000E+02 Zero Point

Reference:

UTUBES Reference Point Notes:

N/A PROC or SENS:

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

STEAM GENERATOR B Alarm / Trip Set Points:

N/A HI Detector Power Supply Cut-off Power Level:

N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failure Mode:

LOW Temperature Compensation For DP Tranruitters:

Y Level Reference Leg:

WET Unique System Desc:

MAY FAIL HIGH.

-i, DATA POINT' LIBRARY REFERENCE FILE Page 12 of 61 Dite r -

01/13/92 R0 actor Unit:

CW1

~ D3ta Feeders-N/A NRC-ERDS-Parameter:

SG LEVEL 3/C-Point IDI-RELO444A Plant Spec Point Desc SG C WR LEVEL Generic /Cond Desc:-

STEAM GEN C WATER LEVEL Analog / Digital:

A Engr-Units / Dig States:

Engr Units l Conversion:

STEAM GENERATOR IS 812 INCHES HIGH Minimum ~ Instr-Range 0.000E+00 iM2ximum Instr-Range:

1.000E+02

~Zsro Point Returence:

UTUBES

!Raference Point Notes:

N/A PROC or SENS:

S Number of Sensors:-

1 How Processed:

N/A-

'S$nsor' Locations:

STEAM GENERATOR C

. Alarm / Trip Set Points:-_

N/A NI Detector Power Supply-JCut-off Power Level:

N/A

'NI Detector Power _' Supply LTurn-on: Power Level:

N/A' Instrument: Failure Mode:~

LOW T&mperature Compensation-For DP Transmitters:

-Y Lsvel Reference Leg:-

WET.

Unique System Desc:-

.MAYl FAIL HIGH.

m h

i v

-.J.

DATA POINT LIBRARY REFERENCE FILE Page 13 of G1 Date:

01/13/92 Raactor Unit:

CW1 Data Feeder:

N/A NRC ERDS Parameter:

SG LEVEL 4/D Point ID:

RELO464A Plant Spec Point Desc:

SG D WR LEVEL Gsneric/Cond Desc:

STEAM GEN D WATER LEVEL Analog / Digital:

A Engr Units / Dig States:

Engr Units Conversion:

STEAM GENERATOR IS 812 INCHES HIGH Minimum Instr Range:

0.000E+00 Maximum Instr Range:

1.000E+02 Zero Point

Reference:

UTUBES Reference Point Notes:

N/A PROC or SENS:.

S Number of Sensors:

1 How Processed:

N/A Sensor Locations:

STEAM GENERATOR D Alarm / Trip Set Points:

N/A NI Detector Power Supply Cut-off Power Level:

N/A NI Detector Power Supply Turn-on Power Level:

N/A Instrument Failuro Mode:

LOW Temperature Compensation For DP Transmitters:

N/A Level Reference Leg:

N/A Unique System Desc:

%AY FAIL HIGH.

l

_