Final Deficiency Rept CP-91-003 Re Corrosion of Installed Hilti-Kwik Bolts.Initially Reported on 910611.Caused by Water Submergence of Base Plate Assemblies.All Bolts Replaced & Housekeeping Procedures Enhanced
ML20091P622
Person / Time
Site: Comanche Peak 
Issue date: 01/31/1992
From: William Cahill
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
CP-91-003, CP-91-3, TXX-92059, NUDOCS 9202030226
Download: ML20091P622 (2)


Text

--__

I "Jl7" J""

7 ~--

Log il TXX-92059 File (! 10110 3

3

  1. 903.7 Ref # 10CFR50.55(e) a uan M, M wmum J. c. hut, Jr.

ow v m r,.u,u U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C.

20555 5cject:

COMANCHE P[ AK STE AM ELECTRIC ST AT ION - UNIT 2 DOCKET NO. 50-446 CORRODED HILTl BOLTS SDAR CP-91-003 (FINAL REPORT)

Gentlemen:

On June 11, 1991 TU E lectric ora 11y notified the NRC of a deficiency involving the corrosion of installed Hilti Kwik Bolts (HKB). We have completed our review of this issuc and nave concluded, based on toniervative calculations, that a safety significant issue at CPSES did not result from this deficiency and that the existence of Conditions determined to cause the corrosion did not represent, or originate from, a significant breakdown in the Quality Assurance Program.

As a result this deficiency is not reportable.

A discussion of this issue is provided below.

DISCUSSlQ!!

r tential for galvanic and crevice corrosion in

~

This deficiency invokes the o

HKBS that are utilized to anchor component support base plates in areas that may subject the base plates to water submergence. The deficiency was identified when a HKB on a floor mounted pipe support base plate broke during a retorquing activity. Examination of the broken bolt identified a s'.gnificant reduction in cross sectional area due to corrosion.

Further investigation of Unit 2 rooms / areas where baseplates could have been submerged, revealed additional instances of corroded HKBS on floor mounted base plates in seven plant areas.

TU Electric arranged for a metallurgical examination of these HKBs by an independent laboratory.

Based on this examination it was concluded that the corrosion mechanisms were galvanic corrosion and crevice corrosion resulting from exposure of the instdlled HKBS and base plate assembly to water submergence.

Pipe and equipment support base plate assemblies involve the use of several dif ferent metal components in various configurations.

Submersion of these assemblies in water could establish conditions f avorable for galvanic corrosion.

In the total population of HKBs f ound to be af fected at CPSES, there was no indication that certain base plate configurations were more susceptible than

others, 030013

)-

9202030226 920131 gDR ADUCK 0500 6

P. O. Box 1002 Glen Rose. Texas 7Nul002

w TXX-92059 -

Page 2 of ?

Our review has concluded.that the corroded HKBs resulted from water submergence of the base plate assemblies.

The water submergence was determined to have occurred between the time Unit 2 construction was suspended in December 1987 and resumed in June 1990.

CORRECTIVE ACTION All of the corroded HKBs identified during the investigation are being replaced.

Concerns related to this deficiency can be eliminated by promptly correcting conditions (either permanent or temporary) that can result in water submergehce in plant areas with bas' plate assemblies.

Therefore, the Unit 2 construction housekeeping procedure has been enhanced to emphasize that water submergence of base plates in construction areas is not permitted and that sump pumps located in construction areas to prevent this should remain operational, in addition, base plate assemblies in areas subject to rain-water submergence (e.g. roof areas) will be provided, where required, with temporary protection after installation to prevent corrnsion until permanent protection is installed.

This is our final,;, ort on this issue. Corroded HKBs identified during review will be replaced prior to Unit 2 fuel load.

Sincerely, g/

William J. Ca 11, Jr.