ML20091F052

From kanterella
Jump to navigation Jump to search
Safety Evaluation Supporting Amends 48 & 49 & 27 & 28 to Licenses NPF-68 & NPF-81,respectively
ML20091F052
Person / Time
Site: Vogtle  
Issue date: 11/01/1991
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20091F038 List:
References
NUDOCS 9111220241
Download: ML20091F052 (2)


Text

_ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _.

[pa ae og%

UNITED STATE S l' 3 % 'k NUCLE AR REGULATORY COMMISSION j

wAsmNGTON D. C. M55 k...+/'SAFETYEVALUATIONBYTHEOFFICEOFNUCLEARREACTORR

+

RELATED TO AMENDMENT NOS.

48 AND 44 TO FACILITY OPERATING LICENSE NPF-6R AND AMENDHENT NOS. 27 AND 28 TO FACILITY OPERATING LICENSE f4PF-81 GEORGIA POWER COMPANY, ET AL.

DOCKET NOS. 50-424 AND 50-4?5 V0GTLE ELECTRIC GENERATING PLANT, UNITS 1 AND ?

1.0 INTRODUCTION

By "ELV-01761, Application for Amends to Licenses NPF-68 & NPF-81,revising Tech Spec Tables 2.2-1,3.3-1 & 4.3-1 Re Reactor Trip Sys Instrumentation Requirements to Delete [[Topic" contains a listed "[" character as part of the property label and has therefore been classified as invalid. Function for Both Facilities|letter dated August 14, 1990]], Georgia Power Company, et al. (GPC or the licensee), proposed licensing amendments to change the Technical Specifications (TS) for Vogtle Electric Generating Plant (Vogtle or the facility), Units 1 and 2.

The proposed changes would delete the Negative flux Rate Trip (NFRT) function from the Reactor Trip System instrumentation requirements specified in TS Tables 2.2.1, 2.2.la, 3.3.1, and 4.3.1, and TS Bases 2.2.1.

2.0 EVALUATION The current design of the Reactor Protection System for Vogtle Units 1 and 2 includes an NFRT function. The purpose of the NFRT function, when first incor-porated into the trip system design, was to prevent unconservative local departure f rom nucleate boiling (DNB) due to local flux peaking in the event of a single or multiple Rod Cluster Control Assembly (RCCA) drop. The licensee now proposes to delete the NFRT function on the basis of analyses performed with the Westinghouse Owners Group Topical Report, " Methodology for the Analysis of the Dropped Rod Event," WCAP-11394-P-A (proprietary) and WCAP-11395-P-A (non-proprietary). These reports provided generic justification for NFRT removal by demonstrating that the DNB design basis is met during the dropped RCCA transient without taking credit for a power reduction due to dropped rods or actuation of any automatic trip features. These WCAP documents have been previously reviewed and found to be acceptable by the MRC for plant-specific applications. The licensee indicated that the deletion of the NFRT function would provide a benefit to plant safety by eliminating unnecessary automatic reactor trips and resulting challenges to safety systems.

To justify deletion of the NFRT function for Vogtle Units 1 and 2, the licensee applied the WCAP-11394-P-A methodology and performed plant-specific evaluations to demonstrate that the DNR design basis is met during the dropped RCCA tran-sient. The licensee evaludted Vogtle FSAR (Final Safety Analysis Report)

Loss-of-Coolant Accidents (LOCA) and non-LOCA transients / accidents, including steam generator tube rupture, and LOCA-related conditions; fluid systems; con-tainment integrity; and systems interaction. The licensee's analyses did not assume any actuation of power reduction features due to dropped RCCAs. The licensee determined that only one non-LOCA transient would be affected by the NFRT function and therefore, would require evaluation. This was the "RCCA Misalignment (System Malfunction or Operator Error)," which involved two scenarios: (1) one or more dropped RCCAs within the same group, and (2) a dropped PCCA bank.

All other LOCA and non-LOCA events are not associated with the NFRT protective function.

and therefore, would not be affected by deletion of the NFRT function.

91112 POP 41 t/11101 PDR ADOCK 05000424 P

PDH

~

. The licensee applied the WCAP-11394-P-A methodology to analyze the "RCCA Misalignment" transient for the case of one or more dropped RCCAs within the same group.

The analyses demonstrated that the DNR design limits are met without the NFRT function. The licensee's analyses also showed that the power overshoot which may occur in the automatic rod control mode of operation and the asymmetric power change assumptions made for the one or more dropped PCCAs within the same group would bound the case of a dropped RCCA bank.

The NRC staff has reviewed the proposed changes and concludes that the 1 kensee's analyses are based on input and assumptions appropriate for Vogtle, and upon approved methodologies. The results demonstrate that DNB design basis continues to be met in the absence of the NFRT function.

Further, the licensee has committed to perform similar analyses in advance of each fuel reload to verify that DNB design limits are not exr.eeded during the respective cycles of operation. Therefore, the proposed TS changes, which reflect the NFRT function removal, are acceptable.

3.0 S' ATE CONSULTATION in accordance with the Commission's regulations, the Georgia State official was notified of the proposed issuance of the amendments.

The State official had no coments.

A.0 ENVIRONMENTAt CONSIDEpATION The amendments chance requirements with respect to installation or use of a facility component located within the restricted area as defined in 10 CFR Part 20 and change surveillance requirements. The NRC staff has determined that the amendments involve no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendments involve no significant hazards consideration, and there has been no public coment on such finding (56 FR 20035).

Accordingly, forth in 10 CFR 51.22(c)(9)gibility criteria for categorical exclusion set the amendments meet the eli Pursuant to 10 CFR 51.22(b) no environmental impact statement or environmental assessment need be prepared in connection with the :ssuance of the amendments.

5.0 CONCLUSION

The Comission has concluded, based on the considerations discussed above, that:

(1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendments will not be inimical to the comon l

defense and security or to the health and safety of the public.

Principal Contributors:

H.-Abelson, SRXB/ DST L. Raghavan, PDll-3/DRP Date: November 1. 1991 l

_