Forwards Independent Assessment of Underpinning Weekly Rept 83 for 840415-21,including Minutes of Daily Meetings Between Assessment Team & Site Engineering,Const & QA Personnel
ML20091A553
Person / Time
Site: Midland
Issue date: 04/24/1984
From: Lucks A
STONE & WEBSTER, INC.
To: Cook
NRC
References
MPF-83, NUDOCS 8405300008
Download: ML20091A553 (15)


Text

'

mM6

(:

l'.

.FRIN)lPALSTAFF g

jgg0PRP lMA 0/RA E

STONE & WEBSTER MICHIGAN, INC.

(/RA otNSF (C

3RMA 5CS P.O. Box 2325, BOSTON. M ASSACriUSETTS O2107

- pao Ml-sGA M-gi-File AI E

United States Nuclear Regulatory Corraission April 24, 1984 Midland Site Resident Office Route 7, J.O. No. 14358 Midland, Michigan Ref. MPF 83 Attcntion: Mr. Cook DOCKET No. 50-3@/330 MIDLAND PLANT UNITS 1 & 2 INDEPENDENT ASSESSMENT OF UNDERPINNING REPORT No. 83 A copy of the Independent Assessment of Underpinning Weekly Report No. 83 for the period of April 15, 1984 through April 21, 1984 is enclosed with thia letter. Included as attachments are the minutes of the daily meetings held during the week between members of the Assessment Team and Site Engineering, Construction, and Quality Assurance personnel.

If you have any questions with respect to this report please contact me at (617) 589-2067 a)LA%h A.S.%he A.

Stanley Lucks Project Manager Enclosures ASL/pd 8405300008 840424

/h0k \\ \\

PDR ADOCK 05000329 h

R PDR g 23N

Notes of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power. Company Held at Midland Site Midland, Michigan April 19, 1984 Present For:

Consumers Power Bechtel MPQAD Stone & Webster G.

W rray J.

Fisher J.

McN ster D.

Benvie R.

Wheeler J.

Kelleher J.

Meisenheimer D.

Zito E.

W Parsons Brinckerhoff B.

Metros PURPOSE This meeting is held each day to discuss items regarding the Independent Soils Assessment at the Midland Plant, Units 1 & 2.

DISCUSSION Status Items Item 83 Au'iliary Builu.1g Undepinning Activities.

Installation of the reshore members is in progress for the drift to pier W5.

Routine rejacking has been completed for pier CT 1.

Excavation of the W17 pier shaft is complete.

Pier Kc9 was rejacked for load verification.

(INFORMATION ITEM)

New Items Item 83 Receipt Inspection of the CT 3/10 Transfer Frames and E/W5 Grillages.

J.

McN ster reported that MPQAD will begin receipt inspection of the CT 3/10 transfer frames today.

D.

Benvie asked if receipt inspection of the E/W 5 grillages has been completed.

J.

Fisher will respond. (OPEN ITM)

Item 83 Weekly Report # 82.

The text of Weekly Report # 82 was reviewed. It was determined that all open items hAd been previously identified.

(INFORMATION ITEM)

Response Items Item 83 NIR 24 Design Drawing Review at UAT Workprint Station.

D.

Benvie stated that the Assessment Team has reviewed the QAR response to NIR 24 addressing document deficiencies at the UAT workprint station.

Document deficiencies noted in the NIR have been corrected. Additionally, j

a sample audit of the UAT workprint stqtion by MPQAD did not reveal any l

deficiencies. Based on the sample audit results and an independent review by the Assessment Team that the noted document deficiencies were corrected, NIR 24 is closed.

(INFORMATION ITM)

J.O. No. 14358 Midland Plant i

Units 1 & 2 Independent Assessment of Underpinning jyklyReportNo.83 April 15, 1984 through April 21, 1984 Personnel on Site Stone & Webster Michigan, Inc.

P.

Majeski 4/15 - 4/17 D.

Benvie 4/16 - 4/21 D.

Zito 4/16 - 4/20 L.

Rouen 4/16 - 4/20 J.

Springer 4/17 - 4/19 Parsons Brinckerhoff Michigan, L7c.

J.

Oliveira 4/15 - 4/18 B.

Metros 4/18 - 4/21 Meetings Attended Ihte Represented Purpose 4/16 - 4/20 Stone & Webster Daily Assessment Bechtel Team Meeting Consumers Power Parsons Underpinning and Remedial Soils - Construction Pier E17: Excavation of the drift was completed.

Pier ES: Excavation of the pier shaft began. Drifting to the reactor containment for installation of the E5 grillage continued.

Kc4-Kc5 and Kc9-Kc8 Drifts: Excavation, lagging installation and backpacking continued.

Piers CT 3/10: Soils stabilization grouting and excavation of the drop pits for piers CT 2/11 continued in preparation for drifting to piers CT 3/10.

Piers CT 1/12: Routing rejacking has been completed for these piers.

Pier W5: Drifting to the reactor containrtent for installation of the W5 grillage was cortpleted.,

Pier W17: Excavation of the pier is in progress.

Access Shaft Level "C" Wales: Alignment and fitup of the level C wales continued for the east and west access shafts.

SWPS:

Installation of the upper level wales continued. Grouting of the strut plates for support of the-soldier pile wall has been cortpleted along the east wall.

BWST: Construction of the ring foundation addition for both tanks has resumed.

Cathodic Protection:

Installation of cathodic protection in the yard area has resurted.

-.. ~ _

,,_.-_y-_-...

2 J.O. No. 14358 Midland Plant Units 1 & 2 4

Independent Assessment of Underpinning Assessment Team Observations - Construction

- Completion of load transfer for the CT 1 and 12 piers has allowed underpinning activities to progress into other areas of the Auxiliary Building. Excavation, backpacking, lagging placement and support steel erection for the drifts to piers Kc5/9 and E/W5 was observed by the Assessment Team. Lagging was installed one' board at a time and backpacked prior to installation of the next board. The sand backpacking was tamped firmly and evenly into place. Drift support steel was aligned in accordance with design requirements. Drilling, installation and torquing of expansion anchors for the drift support sets conformed with project procedures. The level of workmanship exhibited in perfortting the activities associated with drift construction continues to result in a quality installation.

Other underpinning activities in the Auxiliary Building overviewed by the Assessment Team include soil stabilization grouting for the CT 3/10 drifts and excavation of the E5 and W17 pier shafts. The method of grout placement

- and grouting pressures used were in accordance with the procedures. Stability r

of the excavated CT 3/10 drift walls subsequent to grouting indicated that the

-grouting was effective. Excavation of the E5 and W17 pier shafts was perfortted with the aid of a template. Use of the template was effective in minimizing over excavation and maintaining the pier shaft alignments. The Assessment Team concludes that the implementation of the grouting program and use of the template was prudent and effective in stabilizing the soil and minimizing over-excavation.

Assessment Team Observations -~QA/QC i

The Assessment Team overviewed the MPQAD receipt inspection of the CT 3/10 transfer frames. The MPQAD inspector used proper inspection techniques to thoroughly

- verify all dimensional requirements with the applicable design and shop drawings.

All material mark numbers were checked for traceabilit,y. The MPQAD findings included a fabrication error associated with a cross member of one of the transfer frames and a determination that some of the material mark numbers were missing. The Assessment Team concludes that the MPQAD receipt inspection of the CT 3/10 transfer frame was complete and thorough.

Crack mapping in the Control Tower by the crackmapping subcontractor (WJE) was witnessed by the Assessment Team. The activity was being performed by two technicians under the direction of a WJE Quality Assurance Engineer. The Assessment Team' believes this approach is an effective method to ensure that both the procedural and technical intent of the project requirements for crack

- mapping are met.

Work Activity Packages The followin6 ork Activity Package (WAP) overviews are in the open responsd W

stage or have been completed during the past week.

WAP No.

Title Status (Opened) (Closed) 83 Excavate, Install 4/10/84 4/16/84 and Backfill Electric Ductbank and Equipment Pad For HVAC Fans f

I r

- + = -

-w-vwr+.

w

-r w

y

,,,,,,-.,,,-,.,,-.-e.-.-,

r,,

---.v

,-,-e-,.-,.-,,--,-.,

,.,,,e,,,,,,

c, 4

c.

w--e+-

---m-.,,

,,-rw----+-,-wt

r --

J.O. No. 14358 Midland Plant Units 1 & 2 Independent Assessment of Underpinning Nonconfomance Identification Reports The following Nonconfomance Reports (NIRs) remain open or have been closed during the week.

NIR No.

Description Status (Opened)(Closed)

.22 Resident Engineering 2/21/84 Document Control Stations 24 Design Drawing 3/30/84 4/19/84 Review at UAT

~Workprint Station 25 Compressive Strength 3/30/84 Testing of Concrete Cylinders Open Items Items discussed during meetings are categorized as follows:

OPEN ITEM - An item for which anactionis required. The item will remain open until the required action has been taken. Tracking is required.

CLOSED ITEM - An item, usually brought. forward by the Assessment Team that is discussed and adequately responded to. No tracking is required.

INFORMATION ITEM - An item brought forward to provide general background information regarding work, such as work status or an upcoming design change.

No tracking is required.

OPINION ITEM - An opinion or suggestion given by the Assessment Team expressing an alternate construction or quality assurance technique. The opinion or suggestion is given as a possible alternate that n:ay facilitate an operation.

CIDSES ITEM - XX-XX - This notation identifies an action that closes a previously identified open item. Tracking of the open item stops.

The following listing of all Open items from the Daily Meeting Notes with Bechtel and the text of the Weekly Reports. Carry-Over items from past weeks which have been Closed this week are also listed.

Item No.

Description Closure 64-7 QAP Review Program 83-24 64-10 Trend Analysis Open 71-17 Computerized Civil Open Drawing Register

4 J.O. No. 14358 Midland Plant Units 1 & 2 Independent Assessment of Underpinning Item No.;

Description Closure 74-21 US Testing Corrective Open Action 79-26 Upper Leveling Plates Open 79-28 SWPS Backpacking Open Material 79-34 SWPS Backpacking Open Placement 81-8 MPQAD Welding Audit 83-25 81-21 P'e Construction Verification of Soils Open Work 81-25 Trend Analysis Work 82-9 82-3 Surface Voids in Grout Open 82-9 Trend Analysis Update Open 83-17 Crackn:apping open Subcontractor Audit u.)1. F L UM40ukAs%k Project Engineer Project Manager 6

Notea of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Constners Power Company Held at Midland Site Midland, Michigan April 16, 1984 Present For:

Consumers Power Bechtel MPQAD Stone & Webster G.

M2rray J.

Fisher J.

McMaster P.

Majeski J.

Kelleher R.

Sevo D.

Benvie E.

Cvikl D.

Zito B.

Brandes L.

Rouen Parsons Brinckerhoff J.

Oliveira PURPOSE This meeting is held each day to discuss items regarding the Independent Soils Assessment at the Midland Plant, Units 1 & 2.

DISCUSSION Status Items Item 83 Auxiliary Building Underpinning Activities.

Routing rejacking is in progress for piers CT 1/12.

Excavation of the drop pits to piers CT 2/11 has begun in preparation for drift excavation to piers CT 3/10.

Installation of lagging and backpacking has been completed for the pier W17 drift.

Excavation of the Kc4 to Kc5 and Kc9 to Kc8 drifts and installation of drift sets and associated lagging and backpacking is 1:4 progress.

Drifting to piers E/W5 has begun.

(INFORMATION ITEM)

Item 83 SWPS Underpinning Activities.

J.

Fisher reported that rain during the weekend had washed in a small portion of backpacking material along the north side of the SWPS. The affected area is presently being repacked.

(INFORMATION ITEM)

Item 83 US Testing Corrective Action.

J.

Kelleher reported that all of the US Testing quality control procedures with attached work instructions have been submitted to project engineering for review. Final issuance of the quality control pmcedures is expected in the near filture.

(Item 74-21 remains OPEN)

Item 83 Upper Leveling Plate.

J.

Kelleher reported that smaller welds will be used to alleviate warping of the upper leveling plate that has resulted during welding of the leveling and bearing plate assembly. Project engineering will issue DCNs designating the

c g

Notra of Daily Meeting Ind: pendent Assessment of Und;rpinning Midland Plant, Units 1 & 2 Consumers Power Company Held at Midland Site Midland, Michigan April 16, 1984 new welding requirements for each type of leveling and bearing plate assembly.

(Item 79-26 remains OPEN)

(INFORMATION ITEM)

Item 83 NIR 22 - Resident Engineering Document Control.

J.

McMaster stated that the MPQAD audit of the Resident Engineers controlled documents required as part of the closure for NIR-22 has been completed. The audit verified that deficiencies with.the Resident Engineers controlled documents noted in NIR22 have been corrected. Additionally, results of the audit indicate that the Resident Engineers controlled documents are being maintained properly.

(NIR 22 remains OPEN) (INFORMATION ITEM)

Item 83 NIR 25 - Compressive Strength Testing of Concrete Cylinders.

E.

Cviki stated that the QAR response written to address NIR 25 has been transmitted to MPQAD for review. NIR 25 was written as a result of deficiencies associated with the use of the maxinum load indicator needle on the US Testing concrete compression machine. (NIR 25 remains OPEN)

(INFORMATION ITEM)

New Items Item 83 Superplasticized Concrete.

P.

Majeski asked if superplasticized concrete will be used for any fbture underpinning work.

J.

Fisher will respond.

(OPEN ITEM)

Item 83 NCR Processing.

P.

Majeski asked if a review of the NCR process response tirte will be perfortred. MPQAD will respond.

(OPEN ITEM)

Item 83 Direct Hire Work.

J.

Fisher reported that the following direct hire work activities will get underway in the near fbture:

A.

Baron Water Storage Tanks (BWSTs) ring foundations.

B.

Cathodic protection.

C.

Unit 2*HVAC foundation pad.

D.

Diesel Generator fbel oil lines.

(INFORMATION ITEM)

Response Items No response items were addressed.

r Notes of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power Company Held at Midland Site Midland, Michigan April 17, 1984 Present For:

Consumers Power Bechtel MPQAD Stone & Webster G.

Marray J.

Fisher R.

Sevo D.

Benvie J.

Kelleher D.

Zito E.

Cviki L.

Rouen J.

Springer Parsons Brinckerhoff J.

Oliveira PURPOSE

'Ihis meeting is held each day to discuss items regarding the Independent Soils Assessment at the Midland Plant, Units 1 & 2.

DISCUSSION Status Items Item 83 Auxiliary Building Underpinning Activities.

Soils stabilization grouting has begun for the drift to pier CT 10.

Excavation has begun for the W17 pier shaft.

Pier W9 was rejacked for load verification.

(INFORMATION ITEM)

Item 83 QAP Review Program.

R.

Sevo stated that the QAP task force recomendations for improving selected PQCIs, construction procedures and specifications will be submitted to CP Co today.

(Item 64-10 remains OPEN) (INFORMATION ITEM)

New Items Item 83 Pier E17 Drift.

D. _Benvie discussed the drift to pier E17. It was noted that the drift, which is in full face concrete has progressed far enough to allow excavation of the E17 pier shaft. He questioned the need for completing the drift to the reactor wall, as the remainder of the drift is in fill concrete.

J.

Fisher will respond.

(OPEN ITEM)

Response Item Item 83 Superplasticized Concrete.

In response to the Assessment Team question regarding fbture use of superplasticized concrete, J.

Kelleher stated that it is not planned to

s Notes of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power Company Held at Midland Site Midland, Michigan April 17, 1984 use this type of concrete for future work. The original intent for. the use of superplasticizer was to facilitate pier concrete placement and develop high early concrete strength in order to allow loading of piers within 2 to 3 days of concrete placement. For piers cortpleted to.date,

-~

no placement problems have been experienced with concrete that does not contain superplasticizer. Additionally, load transfer has norr. ally not been performed until at least 7 days after completion of concrete placement, alleviating the need for hign early strength of the concrete.

(CLOSES ITEM 83-7)

E 4

4 4

r Notc3 of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2

' Consumers Power Canpany Held at Midland Site Midland, Michigan April 18, 1984 Present For:

Consumers Power Bechtel MPQAD Stone & Webster G.

Murray J.

Fisher J.

McMaster D.

Benvie R.

Wheeler J.

Kelleher D.

Zito J.

Schaub E.

Cviki L.

Rouen W.

Brandes J.

Springer Parsons Brinckerhoff None PURPOSE h is meeting is held each day to discuss items regaro*ng the Independent Soils Assessment at the Midland Plant, Units 1 & 2.

DISCUSSION Status Items Item 83 Auxiliary Building Underpinning Activities.

Soils stabilization grouting is in progress for the drift to pier CT 3.

Installation of lagging and backpacking is in progress for the drifts to piers E/W5.

- Drift excavation to the containment for the E/W5 grillage is ongoing.

(INMRMATION ITEM)

Item 83 NIR 24 Design Drawing Review at UAT.Workprint Station.

J.

McMaster provided the Assessment Team with a copy of the QAR response to NIR 24 addressing document deficiencies at the UAT workprint station for review.

(NIR 24 remains OPEN) (INmRMATION ITEM)

Item 83_1_6_.

_ Upper Leveling Plates.

- J.

Kelleher stated that a welding demonstration using smaller welds for the upper leveling and bearing plate assettblies will be given today. he purpose of the demonstration is to determine whether the smaller weld will decrease leveling plate warping.

(Item 79-16 remains OPEN)

(INFORMATION ITEM)

New Items b

Note] of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power Company Held at Midland Site Midland, Michigan April 18, 1984 Item 83 Crackmapping Subcontractor Audit.

E.

Cvikl stated that the MPQAD audit of the crackmapping subcontractor (WJE) was completed yesterday.

D.

Benvie requested a copy of the audit report when it is issued.

(OPEN ITEM)

Response Item Item 83 Pier E17 Drift.

J.

Fisher responded to the Assessment Team question concerning completion of the pier E17 drift. Presently the drift which is in full face concrete, does not have to be advanced any further to allow construction of the E17 pier. However, procedural changes required to terminate the drift at this point would delay work on the E17 pier. The drift will,therefore, be completed to design limits.

(CLOSES ITEM 83-12) t I

l t

m 1

)

Notes of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 &.2 Constners Power Company Held'at Midlalid Sit.e t' Midland, Michigan 2 2 April.,19i.1984;,a Item 83 NCR Processing.

J.

Meisenheimer responded to the Assessment Teams question concerning NCR process response time. It was stated that with minor exceptions, the process time associated with recent NCRs has not adversely impacted construction progress. MPQAD believes that timely processing of future NCRs can be maintained as the construction activity and complexity increases. h e Assessment Team concurs with this response. However, D.

Benvie stated that as part of the Assessment Team's normal overview of the work, the NCR resolution process will continue to be evaluated.

(CwSES ITEM 83-8)

Item 83 QAP Review Program.

h e Assessment Team reviewed the QAP task force recommendations for o

improving selected PQCIs, construction procedures and specifications that were subtitted to CP Co. The recoratendations include revisions to these docurcents to facilitate construction and inspection of structure steel fabrication and erection, expansion anchor installation and welding.

Be recornnendations also include guidelines for use in developing PQCIs, construction procedures and specifications associated with new construction areas or revisions to existing construction areas. De Assessitent Team believes that the efforts of the QAP Task Force were thorough. he reconstendations developed by the Task Force will be useful in streamlining and facilitating inspection and construction for the processes reviewed.

Be Assessrtent Team also believes that the guidelines recoratended for developing PQCIs and procedure for new construction areas will enhance the respective inspection and construction processes. This item is closed.

(CWSES ITEM 64-7)

Item 83 MPQAD Welding Audit.

J.

McMaster provided the Assessrtent Team with a copy of the MPQAD Welding audit report.

(CLOSES ITEM 81-8) a Y

4 9

)

[

Notes of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power Company Held at Midland Site Midland, Michi6an April 20, 1984 Present For:

Consumers Power Bechtel MPQAD Stone & Webster R.

Wieland J.

Fisher J.

Moran D.

Benvie J.

Kelleher D.

Zito E.

Cviki Parsons Brinckerhoff B.

Metros PURPOSE

'Ihis meeting is held each day to discuss items regarding the Independent Soils Assessment at the Midland Plant, Units 1 & 2.

DISCUSSION Statu;s Items Item 83 Auxiliary Building Underpinning Activities.

Excavation of the E5 pier shaft has begun.

All major structural sections have been set into place for the Level C wales in the east access shaft.

Piers E9/10 were rejacked for load verification.

(INFORMATION ITEM)

Item 83 SWPS Underpinning Activities.

J.

Fisher stated that welding of wale gusset plates and shims for the soldier pile wall along the east side of the SWPS was in progress. Full penetration welds are required for the gussetplates and shims. 'Ihis requirement has delayed fbrther excavation below the first level wales on the east side of the SWPS until later next week.

(INFORMATION ITEM)

Item 83 Direct Hire Work.

J.

Fisher reported that direct hire work on the BWST ring foundations and cathodic protection has begun. Work in the Unit 2 HVAC foundation pad will consence once the work package has been approved by CP Co.

(INFORMATION ITEN)

New Items No new items were discussed.

Response Item

Note:a of Daily Meeting Independent Assessment of Underpinning Midland Plant, Units 1 & 2 Consumers Power Company HeldatMidlandSiNi Midland, Michigani April 20, 1984 Item 83 Receipt Inspection of E/W5 Grillages.

In response to the Assessment Teams question regarding receipt inspection of the E/W5 grillages, J.

Fisher stated that receipt inspection has not been performed. However, the established schedule for inspection of the grillages does provide for timely inspection of the grillages prior to the scheduled installation.

(CLOSES ITEM 83-20) 4.