Discusses pre-exam Review of Multisite Lsro License Written Exam & Requests Concerns for Inclusion of Written Exam Grading Process by NRC
ML20090J298
Person / Time
Site: Peach Bottom, Limerick  
Issue date: 01/17/1992
From: Leitch G
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Martin T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
Shared Package
ML20090J228 List:
References
NUDOCS 9203170161
Download: ML20090J298 (8)


Text

..

t =

PIIILADELPIIIA ELECTRIC COMPANY LIMERICK GENFRATINO STATION P. O. BOX 2300 POITSTOWN PA 19464 0920 January 17, 1992 (m) n71200. EXT. x(o Docket Hos. 50-277 50 278 av m 18:!!!

uutna atstum swtw License Nos. OPR-44 DPR-56 NPF-39 NPF-B5 Mr. Thomas T. Martin, Regional Administrator U. S. Nuclear Regulatory Commission Region 1 475 Allendale Road King of Prussia, PA 19406

Subject:

Peach Cottom Atomic Power Station, Units 2 and 3 Limerick Generating Station, Units 1 and 2 Limited Senior Reactor Operator License Written Examination Post-Exam Review Comments

Dear Mr. Martin:

On January 2,1992, a pre-exam review of the multisite limited Senior Reactor Operator (LSRO)(i.e.,forfuelhandling)licensewrittenexaminationwascondactedby members of the Philadelphia Electric Company (PECo) Nuclear Training Section at the USNRC Region 1 offices.

As a result of this review, concerns were identified with several of the examination questions, and a concensus was reached between PEco and the NRC on recommended revisions to the examination.

The multisite LSR0 written examination was administered by the NRC on January 13, 1992, at Limerick Generating Station.

As a result of a post-exam review by PECo Nuclear Training Section personnel, and comments received by the multisite LSR0 license candidates, concerns were identified with the written examination which were not completely addressed or resolved by the pre-exam review.

These concerns (identified by the examination question number) are provided in Attachment 1 to this letter. We request that these concerns be considered for inclusion in the written examination grading process by the NRC.

)

If you have any questions, please contact Mr. E. S. Bright - Nuclear Training Section at (215) 640-6663.

Sincerely, 9203170161 920306

,J._)

/

/ [Q,(,

{DR ADOCK 0500 7

j;

/

je c 1

~_.

Attachment f

r T. J. Kenny, USNRC Senior Resident inspector, LGS (w/o attachment) cc:

J. J. Lyash, USHRC Senior Resident inspector, PBAPS (w/o attachment)

J. H. Williams, USNRC Chief Examiner, Region 1 (w/ attachment)

Document Control Desk, USNRC, Washington, D. C.

(w/oattachment)

___m

3 -

I ;

o Page 1 of 3 ATTAClIMEFT 1 LIM RIC1LD Eh !;RATIEQ_ S TAT IO N_ _ UNI T a1&_l L

ERA 91LILOIIDM_A10mp POWER _f!IATION UNITS 2 &3 liRTI-SITT._LEBp__NRC WRITTEN EXhli_pojiggBF,3 QUESTIO!1 On6 (1.00) l CO!! SIDERATION PEQUESTFDs Deletion BASIS FOR REQUEST: Por 143S !!P-102 the t.nnual dose is limited to 4,000 mr/yr. No response of 0.0 !!rs is provided, therefore deletion is requested. If the question is retained, then per Lesson Plan LSRO-1705 pace 19 of 33, a limit of 4,500 nr/yr is referenced.

Uring this "alue response c is the most correct answer.

QUESTION: 008 (1.00)

CollSIDERATIO!1 REQUESTED: Correct Answer c

DASIS FOR REQUEST: The primary method for limiting exposure on the refuoi platform during core off-load is flooding the cavity to wor};

underwatcr.

QUESTION: 015 (3.00) l-CONSIDERATION REQUESTED: Deletion CASIS FOR REQUEST: All responses provided are within a range of answers obtainable by the candidates. Calculations are based upon--

a candidate's reasonable interpretation of graphed values. The graph referenced in the question was duplicated from Lesson Plan GF-0260 where it was intended for use as a classroom visual aid, not as a tool for problem solving exercises. It was also noted that less than 50% of the candidates selected the same. response. All responses woru selected at least once.

l l

l r

.--g

, +.,. _

-e n-+,.

t e

o Page 2 of 3 QUESTION: 017 (1.00)

CONSIDERATION REQUESTED: Deletion BASIS FOR REQUEST: This question testo knowledge of generic time l

limitations for the restart of large motors. This is not the intent of the referenced objective GF-0780 LO-6 291005K106 (2.9/3.1) which states " Give the reason for limiting the number of motor starts in a given time period." Three of the responses provided gave the correct reason but at different time intervals.

QUESTION: 018 (1.00)

CONSIDERATION REQUESTED: Correct Answers b, c, d BASIS FOR REQUEST: Response b-lu correct, the bridge trolley can move at fast speed out of the jog zone. Response o is correct if the bypass button lo depressed (bypass button-condition.nct given). Reference LSRO-0760 page 15 and 16.

QUESTION: 028 (1.00)

CONSIDERATION REQUESTED: Deletion BASIS FOR REQUEST: No correct answer is given per Technical Specification 3.5.2 in that one RHR pump e -"able does not meet the operability requirements of a LpCI subafotem.

QUESTION: 048 (1.00)

CONSIDERATION REQUESTED: Correct Answers b, d DASIS FCR REQUEST: The answer-key identifies d as the correct response as it includes both an electrical limit and a mechanical stop. It is contended that b is also a correct answer in -that tlu)

I question is in regard to interlocks. Mechanical stops are a cackup and final means of persennel and equipment protection in the event of an interlock failure.

l 1

i

, _._ _.., =. _ _,..,,..,.. -

,_c,

,,s

O Page 3 of 3 QUESTIO!1:

058 (1.00)

CO!1SIDERATIO!1 REW ESTED:

Deletion BASIS FOR REQUESTt This question does not test the knowledge intended by the referenced objectivo LSRO-0760 LO-6 which states "Doccribe the refueling interlocks associated with....".

The question is testing knowledge of the physical composition of the interlock, not a description of the result of interlock operation.

Additionally, the responses are referenced from a "noto" in a procedural stop of which the candidates are not accountable for by learning objectivo.

PJQUEST SUMMAEh QUESTIOlit REOUESTt 006 DELETIO!1 008 CORRECTIOli 015 DELETIOli 017 DELETIOli 018 MULTIPLE A!!SWER 028 DELETIO!1 048 MULTIPLE A11SWER 058 DELETIOli y

..--e

.,:y

_..w_.

y m

.-m.,-

,:w..r

-,-y..vy.

7

-7.-

'o NRC RESPONSE TO FACILITY COMMENTS Following the pro-examination review of the multi-sito Limited Senior Reactor Operator (LSRO) licenso written examination, all facility comments were addressed and incorporated into tho examination material, including replacement of soveral questions.

Facf.11ty representativos agrood that the examination was both fair and reasonable following this review.

The NRC response to the facility's post-oxamination review comments is below.

QUESTION: 006 (1.00)

CONSIDERATION REQUESTED: Deletion BASIS FOR REQUEST:

Per LGS HP-102 the annual doso is limitod to 4,000 mr/yr.

No responso of 0.0 lirs is provided, thoroforo dolotion is requested.

If the question is retained, then por Lesson Plan LSRO-1705 pdge 19 of 33, a limit of 4,500 mr/yr is referenced.

Using th:,s value responso o is the most correct answer.

NRC RESPONSE:

Comment not acceptod.

The question and answer were derived using the referenced Lesson Plan (LSRO-1705) from which the applicant's were trained.

HP-102 (LGS) would appear to limit exposure to 4000 mr/yr, while A-106 (PBAPS) allows an individual to exceed 4000 mr/yr with Vice President approval.

The training material does not match either of the facility's proceduros, nor does it identify the differences in procedures at the two sites.

This question was revisod following the pre-examination review to incorporato facility comments.

The answer key provided to the facility with the exam was in error, and the correct answer is c.

QUESTION: 000 (1.00)

COMIDERATION REQUESTED: Correct Answer o BASIS FOR REQUEST:

The primary method for limiting expouuro on the refuol platform during core off-load is flooding the cavity to work undarwater.

NRC RESPONSE:

Comment accepted.

The answor key provided to the facility with the exam was in error, and the correct answer is c.

This question was revised following the pre-oxamination review to incorporato facility comments.

e o

QUESTION: 015 (1.00)

CONSIDERATION REQUESTED: Deletion BAS"S V:P REQUEST:

All respAses provided are within a range of answers cbtainable by the candidates.

Calculations are based upon a candidate's reasonable interpretation of graphed values.

The graph referenced in the question was duplicated from Lesson Plan GF-0260 where it was intended for use as a classroom visual aid, not as a tool for problem solving exercises.

It was also noted that less than 50% of the candidates selected the same response.

All responses were selected at least once.

NRC RESPONSE:

Comment accepted.

The graph supplied with the examination may not have provided sufficient detai~.

'o allow the examinees to obtain the expected response.

There were no comments that required question revision made on this question during the pre-examination review.

QUESTION: 017 (1.00)

CONSIDERATION REQUESTED: Deletion BASIS FOR REQUEST:

This question tests knowledge of Teneric time limitations for the restart of large motors.

This is not the intent of the referenced objective GF-0780 LO-6 291005K106 (2.9/3.1) which states "Give the reason for limiting the number of motor starts in a given time period."-

Three of the responses provided gave the carrect reason but at different time intervals.

NRC RESPONSE:

Comment not accepted.

This question was derived almost verbatim from the referenced lesson plan and - the correct answer should have been selected by the knowledgeable examinee.

System Generic K/A's require that examinees demonstrate the ability not only to explain but also to apply system -limits and precautions.

Knowledge such as that tested in this question is necessary to apply the precaution regarding start attempts for large motors.

There were no comments that required question revision made on this question during the pre-examination review.

i l

1

  • b QUESTION: 018 (1.00)

CONSIDERATION REQUESTED: Correct answers b, c, d BASIS FOR REQUEST:

Response b is correct, the bridge trolley can move at fast speed out of the jog zone.

Response o is correct if the bypass button in depressed (bypass button condition not given).

)

Reference LSRO-0760 page 15 and 16.

NRC RESPONSE:

Comment not accepted.

The Boundary Zone Bypass light indicates that the Refuel Platform is in the Exclusion Zone, therefore answers a and b cannot be correct.

The stem of the question and the answers did not specify that the Boundary Zone Computer was bypassed.

Examinees did not inquire about the status of the bypass button when responding to this question during the examination (no clarifications were requested on this question).

Therefore, answer c is not correct.

There were no comments that required question revi:cion made on this question during the pre-examination review.

QUESTION: 028 (1.00)

CONSIDERATION REQUESTED: Deletion i

BASIS FOR REQUEST:

No correct answer is given per Technical Specification 3.5.2 in that one FOIR pump operable does not meet the

(

operability requirements of a LPCI subsystem.

NRC RESPONSE:

Comment accepted.

There were no comments that required question revision made on this question during the pre-examination review.

QUESTION: 048 (1.00)

CONSIDERATION REQUESTED: Correct answers b,

d BASIS FOR REQUEST:

The answer key identifies d as the correct.

response as it includes both an electrical limit and a mechanical stop.

It is considered that b is also a correct answer in that the question is in regard to interlocks.

Mechanical stops are a backup and final means of personnel and equipment protection in the event of an interlock failure.

NRC RESPONSE:

Comment accepted.

There were no comments that required question revision made on this question during the pre-examination review.

........9 6

'k QUESTION: 058 (1.00)

CONSIDERATION REQUESTED: Deletion BASIS FOR REQUEST:

This question does not test the knowledge intended by the referenced objective LSRO-0760 LO-6 which states

" Describe the refueling interlocks associated with The question is testing knowledge of the physical composition of the interlock, not a description of the result of interlock operation.

Additionally, the responses are referenced from a ' note' in a procedural step of which the candidates are not accountable for by learning objective.

NRC RESPONSE:

Comment not accepted.

This question addresses the exeminee's depth of knowledge and understanding of an important ref,eling interlock.

The switches that operate this interlock are highly susceptible to damage during refueling operations.

Understanding of the makeup of the interlock is important to the examinee's ability to apply his/her knowledge of fuel handling equipment interlocks in order to identify and interpret operational problems encountered during refueling.

There were no comments that required question revision made on this question during the pre-examination review.