[pn M%,b UNITED STATES NUCLE AR REGULATORY COMMISSION 8\\

g,

.e WASHINGTON, D. C. 20555 k.....

l SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION PELATED TO AMENDMENT NO. 25 TO FACILITY OPERATING LICENSE NPF-12 SOUTH CAROLINA ELECTRIC & GAS COMPANY SOUTH CAROLINA PUBLIC SERVICE AUTHORITY VIRGIL C. SUMMER NUCLEAR STATION, UNIT 1 1.

INTRODUCTION On November 1, 1983, the NRC issued Generic Letter (GL) 83-37, "NUREG-0737 Technical Specific.ations."

It requested that licensees review Technical Specifications, identify deviations or absence of a Technical Specifica-tion and submit an application for a license amendment in the event any deviations were identified.

South Carolina Electric and Gas Company (SCE&G) reviewed their Technical Specifications to GL 83-37 and by letters dated January 18 and March 22, 1984, SCE&G requested a change to Technical Specifications pertaining to hydrogen monitors. The requested amendment would add a surveillance requirement for a channel check to be performed at least once per twelve hours, add an action statement for both hydrogen monitors being inoperable, and delete a one time only exception for per-formance of initial criticality that was granted in Amendment No. 4 to the operating license.

II.

EVALUATION The requested additions ^o Technical Specifications of a 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> channel check surveillance requirement and an action statement for both hydrogen monitors being inoperable are in accordance with the proposed Technical Specifications contained in GL 83-37 and are acceptable. Deleting the one time only exception for performance of initial criticality that was granted in Amendment No. 4 to the operating license is acceptable since that portion of the Technical Specifications is no longer applicable.

Therefore, the staff concludes that the requested amendment is acceptable.

III. ENVIRONMENTAL CONSIDERATION This cmendment involves a change in the use of a facility component located within the restricted-area. The staff has determined that the amendment involves no significant increase in the amounts of any effluents that may be released offsite and that there is no significant increase in individual or cumulative occupation radiation exposure. The Commission tas previously issued a proposed finding that this amendment

-involves no significant hazards consideration and there has been no public comment on such finding. Accordingly, this amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR Sec 8407110497 840702 PDR ADOCK 05000395 P

PDR

.. 51.22(c)(9).

Pursuant to 10 CFR 51.22(b) no environmental impact state-ment or environmental assessment need be prepared in connection with the issuance of this amendment.

IV.

CONCLUSION The Commission made a proposed. determination that the amendment involves no significant hazards consideration which was published in the Federal Register (49 FR 17873) on April 25, 1984, and consulted with the state of South Carolina.

No public comments were received, and the state of South Carolina did not have any comments.

We have concluded, based on the considerations discussed above, that:

(1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the propused manner, and (2) such activities will be conducted in compliance with the Commission's regulations and the issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public.

Principal Contributor:

Jon B. Hopkins, Licensing Branch No. 4, DL Dated: July 2,1984 m.

vp>

f f

July 2,1984 AMENDMENT N0 25 TO FACILITY OPERATING LICENSE N0. NPF Virgil C. Sumer Unit 1 DISTRIBUTION w/ enclosures:

bcc w/ enclosures:

06cket'No. 50-395

NRC PDR LB #4'r/f~

Local PDR J. Hopkins NSIC M. Duncan PRC System 0 ELD ACRS (16)

E. Adensam R. Diggs, ADM T. Barnhart (4)