I COR5058f8 power mm Voce President - Projects, Engineering and Construction e
Generel *)ffices: 1945 West ParnaH Road, Jackson, MI 49201 + (517) 788-0453 March 12, 1984 J G Keppler, Administratcr U S Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen E11yr=, IL 60137 MIDLAND ENERGY CENTER MIDLAND DOCKET NOS 50-329, 50-330 IE BULLETIN 83-06: NONCONFORMING MATERIALS SUPPLIED BY TUBE-LINE CORPORATION FILE: 0505.12 SERIAL:
28433
REFERENCE:
(1) B&W 10 CFR PART 21 REPORT DATED JANUARY 10, 1983 (2) I!&W LETTER TO R C DEYOUNG DATED JUNE 17, 1983 (3) CPC0 50.55(e) REPORT (82-06) TO J G KEPPLER DATED FEBRUARY 28, 1983 (4) CPC0 50.55(e) REPORT (82-06) TO J G KEPPLER DATED MAY 31, 1983 (5) CP C0 INTETIM IE BULLETIN 83-06 RESPONSE TO J G KEPPLER DATED NOVEMBER 17, 1983 In accordance with the directive given in IE Bulletin 83-06, this report.
identifies the activities that have been completed and/or are in progress, to resolve the issue of nonconforming material supplied by the Tube-Line Corporation (T-L).
An investigation has been performed by Bechtei San Francisco Central ' upplier S
Quality (SFHO) Department to determine if any sub-suppliers have supplied Tube-Line material to the Midland Plant. The following is a. summary of this investigation and of the corrective actions taken:
1.
To date, of the 413 letters nailed from SFHO, 65 letters went to vendors that supplied material to the Midland project. Bechtel Ann Arbor has received 84 (99%) of the Midland responses.
2.
Of the 84 responses, 81 vendort have responded that no Tube-Line material was furnished to Midland. The three vendors that have furnished Midland Tube-Line material are Guyen Alloys, Liberty Equipment, and W J Woolley.
3.
All Tube-Line ma+ trial identified as being furnished to Midland has been entered on nonconformance reports.
oc0384-0781a100 8403220016 840312 NM19 N/*
PDR ADOCK 05000329 fQ G
~-
g s.
2 I
a) Nonconformance Report C-00355; identifies 50 fittings received from l
Guyon Alloy and Liberty Equipment, 17 fittings are located in Warehouse No 1 in the separated hold area with hold tags attached.
b) Nonconformance Report C-00961; identifies nine fittings from Guyon Alloy and Liberty Equipment that have been incorporated into Q systems. All nine fittings have been located and a hold tag placed on l
each fitting.
c) Nonconformance Report C-00915; identifies two 10" caps from W J Woolley that have been incorporated into ASME Class-2 Air Tank OT-921. Hold tags have been attached.
t These three Nonconformance Reports are scheduled to be dispositioned by June 1, 1984.
A final report on IE Bulletin 83-06 is planned for June 15, 1984.
/
JWC/WFK/bjw CC RJCook, Midland Resident Inspector i
DSHood, US NRC i
1 l
oc0384-0781 algo