January 10,1992 U.S. Nuclear Regulatory Commicslon Attn: Decument Control Desk WashintJto., DC 20555
Subject:
LaSalle County Nuclear Station Units 1 and 2 Response to Notice of Violation :
Inspection Repori Nos. 50-373/91020; 50-374/91020 NRC Docket Nos. 50-373 and 50-374
Reference:
Brent Clayton letter to Cordell Reod dated -
December 13,1991 transmitting NRC Inspection Report 50-373/91020; 50 374/91020 Enclosed is Commonwealth Edison Company's (CECO) response to the subject -
.e Notice of Violation (NOV) which was transmitted with the referenced letter and Inspection Report. Tne NOV cited one Severity Level IV violation. The violation -
ca.icerned the failure to notify the NRC within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after determining that the testing-for certain undervoltage relays was inadequate. CECO's response is provided in the '
following attachment.
if your staff has any questions or comments concernin them to Annette Der.anberg, Compliance Engineer at (708) g this letter, please refer 515 7352, 1
Very truly youra.
/)
/.
T.J.
vach Nuclear Lic sing Manager <
Attachment cc:
A. Bert Davis, NRC Regional Administrator - Rlli--
B. Siegel, Project Manager - NRR T. Tongue, Senior Resident inspector 1.G0011
- o2o116o143 92o11o g
i R.
ADOCK10500 3
g-
- ZN'.D1430/1_-
g 4q
RESPONSE TO LEVEL IV VIOLATION INSPECTION REPORT 50 373/91020;50-374/91020 L
ATTACHMENT A L
VK)LATICN: IR 50-373/91020-01 practical and in(b)(2)(lii)(D) requires the licensee to notify the NRC as so 10 CFR 50.72 l
l all cases within four hours of the occurrence of anv event or condition that alone could have prevented the fulfillment of the safety function-of structures or systems that are needed to mitigate the consequences of an-l accident.
Contrary to the above, on November 7,1991, notification of the NRC was not made within fout hours when it was dotermined that inadequate testing of the undervoltaga relays for the cafety divisions 1,2, and 3 electrical bt ses on both units 1 and 2 could have prevented any or all Emergency diesel Generators from performing their safety functions during an accidsnt condition.
REASON FOR THE VIOLATION:
Station management believed that NRC guidance similar to that in Generic Letter 87-09 existed and was app!! cable to the specific situation. It was -
believed that this guidance '.llowed a 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> provision' period during which L
the surveillances could be,erformed without declaring the equipment inoperable. On November'e 1991 at approximately 7:30 a.m., Regulatory Assurance revicwed tne event, cluestioned the potential of having missed an ENS notification, and initiated ac ditional review. Furtt.er investigation by senior station management led to a decision that the 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> provision period was inappropriately applied to Technical Specification 4.0.3. This action led to not declaring the Diesel Generators inoperable and not entering Technical l
Specification 3.0.3. As a result, the need for a 10CFR50.72 notification was l
not recognized.
CORRECTIVE STEPS THAT HAVE BEEN TAKEN AND RESULTS ACHIEVED:
ENS notification was initiated on November 8,1991.
CORRECTIVE STEPS THAT WILL BE TAKEN TO AVOID FURTHER VIOLATIONS:
This svent has bean discussed.:.mong LaSalle County Station, Senior Management and Regulatory Assurance personnel to ensure m:ssed surveillances are dispositioned properly.
DATE WHEN FULL COMPLIANCE WILL BE ACHIEVED:
Full compliance was achieved November 8,1991.