ML20087B458

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept Re Pullman Const Industries Undersized Shop Filet Welds on Corner Details of Stiffener Angles for HVAC Ducts.Condition Not Reportable Per 10CFR50.55(e) or 10CFR21
ML20087B458
Person / Time
Site: Vogtle  Southern Nuclear icon.png
Issue date: 02/24/1984
From: Foster D
GEORGIA POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
GN-322, NUDOCS 8403090097
Download: ML20087B458 (1)


Text

George Power Company Routi 2. Box 299A Waynesboro, Georoia 30830 Telephone 404 554-9961 404 724-8114 F bruary 24, 1984 Vogtle Project t

United States Nuclear Regulatory Commission File: X7BG03-M43 Office of Inspection and Enforcement Log:

GN-322 Region II-Suite 3100 101 Marietta Street Atlanta, Georgia 30303

Reference:

Vogtle Electric Generating Plant-Units 1 and 2, 50-424, 50-425 Pullman Construction Industries Duct Shep Detail; also GN-264, dated 10/3/83 Attention: Mr. James P. O'Reilly Gentlemen:

In our previous correspondence to the NRC, Georgia Power Company indicated that the NRC would be notified by February 24, 1984, of the results of our evaluation of undersized shop filet welds on corner de-tails of the stiffener angles for HVAC ducts. Georgia Power Company has completed its review and evaluation of this event and has concluded that it is not reportable pursuant to the requirements of 10 CFR 50.55 (e) and 10 CFR 21.

A random sample of duct pieces was made and transmitted to Bechtel Power Corporation. Bechtel performed an engineering analysis assuming a configuration worse than any encountered by the sampling. The results of this evaluation indicated that all ductwork installations were ade-quate for the desigr load conditions.

It was concluded that if the weld discrepancies in the HVAC duct systems had remained undetected, safe operation of the plant would not be compromised.

Since the NRC has defined a "significant deficiency" as one having an adverse effect upon, or likely to adversely affect, the safe opera-tion of the plant, Georgia Power Company has concluded that, this event does not constitute a significant deficiency in design or construction.

This response contains no proprietory information and may be placed in the NRC Public Document Room upon request.

Yours truly, h u 'W D. O. Foster" #

REF/D0F/tdm U.S. Regulatory Commission, Document Control Desk, Washington, D.C.

xc:

xc:

R. J. Kelly D. E. Dutton J. A. Bailey L. T. Gucwa R. E. Conway W. F. Sanders

0. Batum M. Malcom G. F. Head R. H. Pinson G. Bockhold H. H. Gregory, III C. W. Hayes P. D. Rice S. M. Guthrie J. T. Beckham, Jr.

D. N. MacLemore R. A. Thomas E. D. Groover J. L. Vota 8403090o97 e402?4 OWICIAL CW' PDR ADOCK 03 COO 424 S

pyg g77