Part 21 Rept Re C Feedwater Isolation Valve Actuator Failure During Testing.Caused by Poppet Seal in Control Valve Assembly.New Design Poppet Seal Extensively Tested & Placed Into Svc,Resolving Problem
ML20087B321
Person / Time
Site: Summer 
Issue date: 01/06/1992
From: Skolds J
SOUTH CAROLINA ELECTRIC & GAS CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-PT21-92 NUDOCS 9201130084
Download: ML20087B321 (2)


Text

,

e j

So th C rolin2 Drctrte & G:e CompIny John ko o Jenhnsvius, Sc N065 Nuclear Operations 803) 345-4040 SCE&G Jte 0 0 W2 Document-Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555 Gentlemen:

Subject:

VIRGIL C. SUMMER NUCLEAR STATION DOCKET NO. 50/395 OPERATING LICENSE N0. NPF-12 INTERIM PART 21 REPORT (SSH 920001)

South Carolina Electric & Gas Company (SCE&G) submits this letter in accordance with 10CFR21.21(a)(2) as an interim report of an identified defect potentially associated with a substantial safety hazard.

On November 7, 1991, the "C" Feedwater isolation Valve (FWIV) actuator (XVG-1611C-0-FW) failed during post modification testing.

The failure has been tracked to a " poppet" seal in the control valve assembly which controls the opening and closing of the FWlV. Subsequently, several additional failures occurred during extended testing. As a result, a new design " poppet" seal was extensively tested and placed into service, resolving the problem.

At this time. SCE&G is proceeding to evaluate the failures as follows:

1.

Performance of testing by an independent lab to determine physical properties of the original " poppet" seals.

2.

Compare "as found" physical properties of the " poppet" seals to "as specified" properties.

3.

Perform " finite element" analysis on the original and new " poppet" seal designs.

4.

Develop conclusions as to 10CFR21 reportability.

.SCE&G expects to complete tnis evaluation by July 15, 1992, due to the tieed for vendor input.

}

if you require any further infvmation, please contact Ms. Jacquelyn Graham

.at (803) 345-4056.

Very truly yours, John L. Skolds J0G:JLS: led

{