Amend 86 to License NPF-29,modifying Surveillance Requirement for Performance of Channel Functional Test of RPS Electrical Assemblies
ML20086U161
Person / Time
Site: Grand Gulf 
(NPF-29-A-086, NPF-29-A-86)
Issue date: 12/18/1991
From: Larkins J
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20086U164 List:
References
NUDOCS 9201070233
Download: ML20086U161 (5)


Text

.

ps ue

/

'o UNITED ST ATE J

'g l' > v (

~

i NvCLE AR REGULA10RY COMMISSION w u niNovo N.o.c.to n s s.....-

ENTERGY OPERATIONS. INC SYSTEM ENERGY RESOUr.CES. INC.

SOUTH HISSISSIPP? ELECTRIC POWER ASS 001Att0N HISSISS1PPI POWER AND LIGH1 COMPANY DDCLETN0.50-413 GRAND CULF NUCLEAR STATION. UNIT 1 AMENDMENT TO FAC11.1TY OPERATING LICENSE Amendment No. 86 License No. NPF-29 1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amindment by Entergy Operations, Inc. (the licensee)datedSeptember 11, 1991, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),

and the Comission's rules and regulations set forth in 10 CFR Chapter 1; B.

The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commit.sion; C.

Thereisreasonableassurance(i)thattheactivitiesauthorizedby this amendment can be conducted without endangering the health and l

safety of the public, and (ii) that such activities will be conducted in compliance with the Comission's regulations; l

D.

The issuance of this amendment will not be inimical to the conmon defense and fecurity or to the health and safety of the public; and E.

The issuance of this amendment is in f.ccordance with 10 CFR Part 51 of the Comission's regulations and all applicable recnirements have been satisfied.

l 9201070233 911210 PDR ADOCK ObOO9416 P

9D9

l 2

2.

Accordingly, the license is amended by changes to th Technical

$pecifications, as indicated in the attachment to tb., license amenchent; and paragraph 2.C.(2) of racility Operating License No. NPf.2915 hereby amended to read as follows:

(2) Technical Specifications I

c The Technical Specifications contained in Appendix A and the i

Environmental Protection Plan centained in Appendix B, as revised through Amendment No. 86, are here'y incorporated into this license. Entergy Operations, Inc. Shall operate the facility in accordance with the Technical $pecifications and the Environmental Protection Plan.

1 3.

This license amendment is effective as of its date of issuance.

FOR THE NUCLEAR REGUL ATORY COMMISSION

)4f.. /

a John T. Larkins, Director Project Directorate 1V-1 Division of Reactor Projects 111, lY, and V Office of Nuclear Reactor Regulation

Attachment:

Changes to the Technical i

$pecifications Date of Issuance: December 18, 1991 i

l l

l l

lr i

4 r

,.,,_e,._n, y

.,,.q

..,.wa.

...,.g.w,,.y y--

i 1

ATTACHMENT TO LICENSE AMENDMENT NO. 86 FAC11ITY OPLRATING. LICENSE NO. NPr.?9 gEtrT NO 60 416 P

L Replace the following page of the Appendix A Technical Specifications with the attached page.

The revised page is identified by amend.ncnt number and contains a vertical line indicating the area of change. The corresponding overleaf page is also provided to maintain document completeness.

BEMOVE PAGE INSERT PAGE 3/4 8-54 3/4 8-54 T

P l

I

\\

l.

e P

t y

s'M*

"d r

'*R

+TF "h2**-

'W T

TABLE 3.8.4.2 3 (Continued)

NOTOROPERATE0VALVESTHERSALOVERLOADPROTECTION BYPASS DEY!CE (CON-TINUOUS) (ACCIDENT SYSTEM (5)

VALVE HUMBFR CONRTIONS)(HO)

AFFECTED Q1P72F123 Continuous.

Drywell CV System Q1P72F122 Continuous Drp ell CV $ystem Q1P72F125 Continuous Drywell CW System Q1P72F123 Continuous Dryvell CW System Q1P72F124 Continu;a Drywell CW System Q1P72F126 Continuous Drywell CW System Q1P44F042 Continuous Plant SW System Q1P44F054 Continuous Plant SV System Q1P44F067 Continuous Plant SW System Q1P45F096 Continuous Floor & Ecmt. Drain System Q1P45F097 Continuous Floor & Eqmt. Drain System Q1PS2fl95 Continuous Service Air System Q1P$3F003 continuous Instrument Air System Q1P53F007 Continuous Instrument Air System Q1T4SF005 Continuous SGTS Q174BF006 Continuous SGTS Q1T4BF024 Continuous SGTS Q1T4Er026 Continuous SGTS Q1745F023 Continuous.

SGTS Q1T4SF025 Continuous SGTS Q1945F273 Continuous Floor & Eomt. Drain System Q1P457274 Continuous Floor & Egmt. Orain System GRAND' gut.F-UNIT 1 3/4 6-53 Amendment No. 21 l

E'fective Date:

October 20, 1986

l I

REACTOR PROTECTION SYSTEM ELECTRIC POWER MONITORING LlHITIN3 CONDITION FOR OPERATION 3.8.4.3 Two RPS electric power monitoring assemblies for each inservice RPS

('

MG set or alternate power supply shall be OPERABLE.

]

APPLICABILITY:

At all times.

ACTION:

a.

With one RPS electric power monitoring assembly for an inservice RPS MG set or alternate power supaly inoperable, restore the inoperable power monitoring system to OPERA 3LE status within 72 haurs or remove the associated RPS MG set er alternate power supply from service.

b.

With both RPS electric power monitoring assemblies for an inservice RPS MG set or alternate power supply inoperable, restore at least one electric power monitoring assembly to OPERABLE status within 30 minutes or remove the associated RPS MG set or alternate power supply from service.

SURVEILLANCE RE0VIREMENTS 4.8.4.3 The above specified RPS electric power monitoring assemblies shall be determined OPERABLE:

a.

By performance of a CHANNEL FUNCTIONAL TEST each time the plant is in COLD SW.'T00WN for a period nf more than 24 nturs, unless performed in the previous 6 months.

L>.

At least once per 18 months by demonstrating the OPERABILITY of over-voltage, under-voltaae and under-frequency protective instrumentation by performance of a CHANNEL CAllBRATION including simulated automatic actuationoftheprotectiverelays,trippinglogleandoutputcircuit breakers and verifying the following setpoints-1.

Over-voltage Bus A

< 132.9 VAC Bus B 3133.0VAC 2.

Under-voltage Bus A

> 115.0 VAC Bus B 1115.9VAC 3.

Under-frequency Bus A

> 57 Hz Bus B

[57Hz GRAND GULF-UNIT 1 3/4 8-54 Amendment No. 86