P A-53 suur'Emem.

00CKETED

///ms$

37 9

66

% J114 A10:27 GPC EXHIBIT 53 BOCICIOLD EX. G OFFICE OF SECRETARY DOCKETING & SERVICE Interoffice Correspondence GeorgiaPoner A DATE: April 9, 1990 RE:

Dewpoint Readings FROM:

H. D. Duncan T0:

C. L. Coursey The following dewpoint readings are for Unit 1 and Unit 2 Diesel Generator Air Compressor. Samples were taken from air receiver tanks on 4/8/90.

(

Unit IA Diesel Generator 12403G400lK01 34.2'F 12403G400lK02 33.2'F Unit 18 Diesel Generator 12403G4002K01 44.5'F 12403G4002K02 36.6*F Unit 2A Ofesel Generator 22403G400lK01 43.9'F 22403G4001K02 60.9'F Unit 2B Diesel Generator 22403G4002K01 33.7'F 22403G4002K02 44.4*F Unit 2A Diesel Generator Air Receiver K02 is currently out of specification and is being continuously blown down.

p NUCLEtB REGULATORY COMM ss!ON

~

  • @J.

Dacket f[Y' % -)3 Obctal bh. No' I-M in the meerotgggg e

HDD/jbc M-tDF.f3IND

/'

s Ine e r rE ED vr 0R ConrgO!rt h

b Contracnr

/./py i

\\

pyg 0*

newer _,Ar,c)

_ weess h c r /, j j 9508030187 950601 PDR ADOCK 05000424 0