ML20086L413

From kanterella
Jump to navigation Jump to search
Forwards Response to Questions in Detailed Design Description & Intermediate Sys Design Description Per TMI Item II.F.2 & RCS Coolant Inventory Trending W/Reactor Coolant Pumps Operating. Encl Withheld (Ref 10CFR2.790)
ML20086L413
Person / Time
Site: Crane 
Issue date: 01/31/1984
From: Hukill H
GENERAL PUBLIC UTILITIES CORP.
To: Stolz J
Office of Nuclear Reactor Regulation
Shared Package
ML19289B825 List:
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.F.2, TASK-TM 5211-83-379, NUDOCS 8402080215
Download: ML20086L413 (2)


Text

g P

GPU Nuclear Corporation Nuclear

ersgr8o o

Middletown, Pennsylvania 17057-0191 717 944 7621 TELEX 84-2336 Writer's Direct Dial Number:

January 31, 1984 5211-83-379 Office of Nuclear Reactor Regulation Attn:

J. F. Stolz, Chief Operating Reactors Branch No. 4 Division of Licensing U. S. Nuclear Regulatory Commission Washington, D.C.

20555

Dear Sir:

Three Mile Island Nuclear Station, Unit 1 (TMI-1) f Operating License No. DPR-50 Docket No. 50-289 Inadequate Core Cooling (NUREG 0737 II.F.2)

By letter dated June 14, 1983 the NRC provided conceptual design approval of our proposed RCS Inventory Trending System. The NRC further identified several concerns and requested a schedule for providing the requested information. By letter dated August 25, 1983 GPUN provided responser to the short term items and agreed to provide the responses to the remaining questions in the detailed design description. The attached response to some of the questions and the intermediate system design description provide partial fulfillment of this requirement and the first milestone (namely the detail design description) discussed in our response of March 10, 1983.

The enclosure entitled "RCS Coolant Inventory Trending (CIT) with RC Pumps Operating" provides the method for developing void fraction for various RCS pump configurations based on motor current. GPUN intends to use pump power which is directly related to current as the input parameter.

GPUN has now contracted with a vendor for the more detailed design phase and will submit a final design package in June, 1984. GPUN has installed a tap in the DHR dropline, engineered a tie-in to the RV head vent and developed the software for the RCS void fraction calculation.

, Dyth 8402080215 840131 PDR ADOCK 05000289 C

PDR P

p k

f 60 A

Mr. J. F. Stolz 5211-83-379 Pursuant to the provisions of 10 CFR 2.790(b) we request that portions of the enclosed document (B&W DOC. I.D. 47-1149188-00) be classified as proprietary and withheld from public disclosure pursuant to 10 CFR 2.790(A)(4).

Sincerely,

. D.

lukill Director, TMI-l HDil:LWil:vj f Enclosure cc:

R. Conte J. Van Vliet