ML20086H959
| ML20086H959 | |
| Person / Time | |
|---|---|
| Site: | Peach Bottom |
| Issue date: | 02/23/1975 |
| From: | Cooney M PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC |
| To: | Anthony Giambusso Office of Nuclear Reactor Regulation |
| References | |
| RO-75-4, NUDOCS 8401200368 | |
| Download: ML20086H959 (2) | |
Text
- n.
O O
t
~ '. ' ~.,
PHILADELPHIA ELECTRIC COMPANY 9
y d'
2301 MARKET STREET
.\\
j 4
PHILADELPHI A. PA.19101
(-
,]f t
h
'?, /
2 t si s41-4ooo NfN w~
qy February 23,1975 Mr. Gismbusso Director Division of Reactor Licensing Office of Nuclear Reactor Regulations United States Nuclear Regulatory Ccrmission Washington, D.C.
20555
Dear Mr. Giambusso:
Subject:
Fnvironmental Deviation Tue Iv11vdag duviaLiva wut., rupurL4 Lv Mr. '.?alL D wa A, Office of Inspection and Enforcenent, Region 1, United States Nuclear Regulatory Comminsion on February 1h,1975
Reference:
License Number DPR-hh/56 Environmental Technical Specifications 2.2.h and 3 2.h Report No.:
50-277/278-75-h Report Date:
February Th,1975 Deviation Date:
February 13, 1975 Facility:
Peach Bottom Atcanic Power Station Units 2 and 3 R.D.1, Delta, Pennsylvania 1731h Identification of Deviation:
Eccessive chenical usage.
Conditions Prior to Deviation:
Units 2 and 3 in initial startup phase of operation duz-ing the second half of 197h.
a79 ?$
go E#*f88#8d!gg Wh
<9 2140 a
1 1
COPY SENT REGION
Mr. A. Giambusco Febru ry 23,1975 O
C)
>c= > 2 Description of Deviation:
The following chmical usage exceeded 2 times the estimated yearly usage which is an Ehvironmental Deivation.
Chemical Annual Usage Tech Spec Limit (2 x est. usage) s Alum 61,000 lbs.
h0,000 lbs.
Sodium Hydmxide 381,h10 lbs.
3h0,000 lbs.
Sodium Sulfite 1,200 lbs.
1,000 lbs.
' Designation of Apparent Cause of Deviations The high usage of alum and sodium hydroxidt resulted from.
the large dein water requirments of the preoperational flush program.
The high sodium sulfite usage is a result of the poor auxilia:y boiler deaerator perfomance and design probles in the condensate return syste (which requires large makeup with air saturated water). Both of these pmb1ms require additional sodium sulfite injection to cont ml dissolved 02 in the. auxiliary boilers.
Analysis of Deviation:
No safety implications. ' No adverse offcets,to the.Conowingo Pond have-been observed rhia t.n +M. ovaarriv arrge.
Corrective Action:
The alum. nd sodium hydroxide usage will decrease since the flushing pmgran is over and danand for dmin water has decreased.
Modifications to the condensate retum syste planned for the spring is expected to reduce sodium sulphite usage.
Failure Data:
None.
.c.
Very truly yours, M.
. Cooney Ass't Gen 81 Superintendent Generation Division cc Mr. J. P. O'Reilly Directoi-Office of Inspection and Ehforument Region 1 United States Nuclear Regulatory Canmission 631 Park Avenue King of Prussia, PA 19h06