1115P EST APR 7. 72 PB003 KA604
.I K CVA353 PD VERNON VERMONT 7 NFT US ATOMIC ENERGY COMM DIRECTOR _ DIVN OF COMPLI ANCE REGION ONE 970 BROAD ST NEWARK NJER THIS WILL CONFIRM CONVERSATION AT 1510 HOURS THIS DATE WITH R A FIEL OF REGION ONE COMPLIA' ICE REGARDING A FAILURE OF SGTS FAN A TO START. AT 1615 HOURS.WITH THE RE ACTOR SHUT DOWN AND UNDER THE CONDITION THAT NEITHER SECONDARY CONTAINMENT NOR JE STAND BY GAS TREATMENT SYSTEMS REQUIRED IN ACCORDANCE WITH TECH SPECS ON 4-6-72 A LOW WATER LEVEL SIGN AL-WAS INITI ATED BY INSTRUMENTATION PERSONNEL WHILE PERFORMING MAINTENANCE WORK
^
[
ON INSTRUMENTATION RACK 25-5 SGTS FAN A DID NOT START. FAN 58 B STARTED AND REACTOR BUILDING VENTILATION ISOLATED AS REQUIRED.
}$
1620 HOURS REACTOR BUILDING VENTILATION SYSTEM WAS RETURNEJ S$
TO NORMAL ATTEMPTS TO MANUALLY START FAN A WERE UNSUCCESSFUL.
I IN COURSE OF INVESTIGATION IMPOSED A DOWN SCALE TRIP ON REACTOR mm
~
O r\\
t
)s mesfern union kelegram '
~ EAR M
%%9 Y
l x
l
~' L
{,
BUILDING VENTILATION MONITOR SYSTEM. NEITHER SGTS FAN STARTED.
2147 THERMAL OVERLOADS IN SGTS FAN MOTORS A AND B CHANGED f
FROM 41 TO 44 REPEATED ST ARTS ON EACH F AN WERE PERFCRMED WITH NO F AILURES 0200 4-7-72 SECURED FOUR HOUR. CONTINUOUS RUN FOR
~
BOTH SGTS FANS AGAIN NO FAILURES WERE NOTED L L L AWYER VERMONT YANKEE NUCLE AR POWER CORP PO BOX 157 VERNON x
)