Environ RO 75-13:on 750716,two Cooling Towers Simultaneously Inoperative.Caused by Setpoint Drift in Flow Switch of Lift Pump Lube Water Supply Line.Faulty Vibration Switch Replaced & Fan Restarted
ML20086G416
Person / Time
Site: Peach Bottom  Constellation icon.png
Issue date: 07/25/1975
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Anthony Giambusso
US ATOMIC ENERGY COMMISSION (AEC)
References
RO-75-13, NUDOCS 8401110366
Download: ML20086G416 (2)


Text

I 1

O O

PHILADELPHIA ELECTRIC COMPANY 2301 MARKET STREET PHILADELPHIA, PA.19101

~

  • 9 s s (2151 e414000 3V pthp@s Q, l l (y 0, f,) 'i' b July 25, 1975

, m,%!

c. J,,,

e-. ~

(-k C'

L'~"'

j.7 Mr. A. Giambusso Y ',;;,,

(Q."

~"

Director

.//~f7;}il/

Division of Reactor Licensing n

Of fice of Nuclear Reactor Regulations

{

I United States Nuclear Regulatory Commission Washington, DC 2055$

Dear Mr. Giambusso:

Subject:

Environmental Deviation The following Deviation was reported to Mr. Walt Bounack, Region 1, Of fice of Inspection and Enforcement, United States Nuclear Regulatory Cormiission on July 16, 1975

Reference:

License Number DPR-44/56 Environmental Technical Specifications -

Appendix B.2.1 Report No.:

50-277/ 278-75-13 Report Date:

July 25,1975 Deviation Date:

July 16,1975 Facility:

Peach Bottom Atomic Power Station Units 2 and 3 R.D. 1, Delta, Pennsylvania 17314 Identification of Deviation:

Two cooling towers simultaneously inoperative.

Conditions Prior to Deviation:

Unit 2 and 3 at approximately 50% power.

Description of Deviation:

The "C" cooling tower was out of service due to an apparent malfunction of a flow switch in the lift pump lube water supply line.

On the "B" tower the "F" f an was out of service with a fan drive motor failure.

The deviation occurred when the "B" tower "E" fan tripped due tc an faulty vibration switch, rendering the "B" tower " inoperative" since it only had 9 operable fans.

$d dh 7

_ 8401110366 750725 Ol.b, d PDR ADOCK 05000277 f

[1y **t'.

S PDR aY aarragigw -

,S

.Mr. A. Giambusso ()

5 7/278-75-13 July 25,1975 P

2 Designation of Apparent Cause of Deviation:

Cause of deviation was setpoint drift in the "B" tower "E" f an vib' ration switch causing an erroneous high vibration trip of the fan.

Analysis of Deviation:

Due to the reduced plant power level and the remaining capacity of the "B" cooling tower wi th nine f ans still operable no change beyond the limits of background variations in measured river temperature was observed.

Corrective Action:

The f aulty vibration switch was replaced and the f an restarted.

The length of time the fan was out of service was one hour.

Failure Data:

None.

Very truly yours, fa W M.

Cooney f'/

A*

't Gen't Superintendent Generation Division cc: Mr. J. P. O'Rei ll y Director, Region 1 Office of Inspection and Enforcement United States Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 x