Environ RO 76-11:on 760218,settling Basin Effluent Suspended Solids Concentration Exceeded Environ Tech Spec Limit.Caused by High Suspended Solids Level in River Water.Settling Basin Contents Settled & Solids Pumped Out
ML20086G308
Person / Time
Site: Peach Bottom  
Issue date: 02/28/1976
From: Cooney M
PECO ENERGY CO., (FORMERLY PHILADELPHIA ELECTRIC
To: Stello V
Office of Nuclear Reactor Regulation
References
RO-76-11, NUDOCS 8401110185
Download: ML20086G308 (2)


Text

__

O O

PHILADELPHIA ELECTRIC COMPANY o

e D

2301 MARKET STREET g

f,

[ h.

_6 1

PHILADELPHIA. PA.19101

/ &g lj (215) 8414oOO O

i>l r

5 Februa ry 28, 1

,'\\q; d

v Hr. Victor Stello, Jr., Director Division of Operating Reactors Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C.

20555

Dear Mr. Stello:

Subject:

Envi ronmental Deviation The following deviation was reported to Mr. Harvey Cantor, Office of Inspection and Enforcement, Region 1, United States Nuclear i

Regulatory Commission on February 18, 1976.

Reference:

LicenseNumberDPR-44/56 Envi ronmental Technical Specifications:

2.2.2 r

Report No.:

50-277/278-76-11 Report Date:

Februa ry 28, 1976 Deviation Date:

Februa ry 18, 1976 Faci li ty:

Peach Bottom Atomic Power Station Units 2 and 3 R.D. #1, Delta, Pennsylvania 17314 Identification of Deviation:

Settling basin effluent suspended solids in excess of the Envi ronmental Technical Speci fication limi t.

Description of Deviation:

Routine analysis showed that the suspended solids concen-tration of the settling basin effluent was 45 ppm greater than that of the river water.

Designation of Apparent Cause of Deviations.

High suspended solidst levels in the river water resulted in a build-up of solids in the settling basin and also necessitated high blowdown flows from the raw water clarifier. This combination resulted in carry-over in the effluent from the settling basin.

0401110185 760228 DR ADOCK 05000 2136

m J

O e

Mr. Victor Stallo, Jr.

50-7/7/278-76-11 February 28, 1976 Page 2 l

l Analysis of Deviation:

l Due to the short period of time that the settling basin effluent was out of speci fication, dilution wi th ci rculating water i

flow, and high river flow (greater than 100,000 cfs), the envi ron-mental impact of this deviation is minimal.

Corrective Action:

The clarifier blovdown was terminated.

The settling basin contents were allowed to settle, and the solids pumped out.

Normal operations were then resumed.

Failure Data:

Envi ronmental Deviation Reports 50-277/278-74-10,and 50-277/278-74-9 Very truly yours,

(,.; ; "

M J. Cooney Superin tenden t Gen. Div. - Nuclear cc:

Mr. James P. O'Reilly Director, Region 1 Office of Inspection and Enforcement U.S. Nuclear Regulatory Conunission 631 Park Avenue

~

King of Prussia, PA 19406 m-w

- +