Text
.
k 2,
W$LF CREEK NUCLEAR OPERATING CORPORATION Richard N. Johannes June 21,1995 CO 95-0087 U.- S. Nuclear Regulatory Commission ATTN: Document Control Desk Mail Station F1-137 Washington, D.
C.
20555
Subject:
Docket No. 50-482: Changes to Wolf Creek Generating Station Radiological Emergency Response Data System Data Point Library Gentlemen:
This letter transmits changes to Wolf Creek Generating Station's (WCGS)
Data Point Library (DPL).
The level indications for the containment recirculation sumps were revised as a result of a plant configuration change.
The level was previously transmitted in inches.
The revised range is based on building elevation. The new points reflect a thirteen foot range from 1993.10 to 2006.10 feet.
The Emergency Response Data System points affected are EJLOOO7 and EJL0008.
The changes are being transmitted as replacement pages to update the WCGS DPL. These changes were implemented May 24, 1995.
If you should have any questions regarding this submittal, please contact me at (316) 364-8831, extension 4001, or Mr. Richard D.
Flannigan at extension 4500.
Very truly yours, H$)$$$
Richard N. Jo annes RNJ/jra Attachment ec:
L. J. Callan (NRC), w/a D. F. Kirsch (NRC), w/a J. F. Ringwald (NRC), w/a J.
C.
Stone (NRC), w/a 9506280432 950621 PDR ADOCK 05000482 F
PDR PO. Box 411/ Bunington, KS 66839 / Phone. (316) 364-8831 An Eaual Oppodunny Employer WF/HCNET
' i i
k
- Attachment to CO 95-0087
-/
Page 4 of 2'
- DATE:(8) :
05/24/95 l
Reactor Unit: (3).
' WC1 '
s Data Feeder:(10)
-N/A NRC ERDS Parameter: (12)
EJLOOO7 Plant Spec Point Desc.: (40)
CTMT RECIRC SUMP A LEVEL Generic /Cond Desc.:(32)
CTMT EMERGENCY RECIRC SUMP Analog / Digital: (1)
A Engr Units / Dig States:(12)
ELEV l
- Engr Units Conversion:(40)
N/A-Minimum Instr Range: (10) 1993.10-
' Maximum Instr Range: (10) 2006.10 Zero Point
Reference:
(6)
ELEV Reference Point Notes: (40)
N/A PROC or SENS: (1)
S Number of Sensors: (3) 1 How Processed: (40)
N/A Sensor Locations: (40)
INSIDE CTMT AT RECIRC SUMP A Alarm / Trip Set Points: (40)
N/A NI Detector Power Supply Cut-off Power Level:(15)
N/A NI Detector Power Supply Turn-on Power Level: (15)
N/A Instrument Failure Mode:(30) LOW = LOP
. Temperature Compensation for DP Transmitters: (1)
N/A a
Level Reference Leg: (3)
N/A Unique System Desc.: (100)
RECIRC SUMP LEVEL XMTR TRAIN A EJLIT0007 LOW LIMIT 1FT 1 IN ABV SUMP FLOOR l
COMPUTER ALARMS
'I MODE fil FP 2002.20 i
I LP
.2002.20 HS 2002.20 HC 2002.20 CS 2002.20 RF 2002.20 e
l l
i l
g.
Q. -
.A -
AttOchment to CO 95-0087 Page 2.of 2 DATE:(8) 05/24/95 l
Reactor Unit- (3)
WC1 -
Data Feeder: (10)'
N/A.
NRC ERDS Parameter: (12)
CTMNT SMP NR
_' Point ID: (12)
. 'EJLOOO8 Plant Spec Point Desc.: (40)-
CTMT RECIRC SUMP B LEVEL Generic /Cond Desc.:(32)
CTMT EMERGENCY RECIRC SUMP Analog / Digital: (1)
A Engr Units / Dig States:(12)
ELEV l
Engr Units Conversion: (40)
N/A Minimum Instr Range: (10) 1993.10 Maximum Instr Range: (10) 2006.10 Zero Point
Reference:
(6)
ELEV Reference Point Notes: (40)
N/A PROC or SENS: (1)
S Number of Sensors: (3) 1 How Processed:(40)
N/A Sensor Locations: (40)
INSIDE CTMT AT RECIRC SUMP B Alarm / Trip Set Points: (40)
N/A NI Detector Power Supply Cut-off Power Level:(15)
N/A NI Detector Power Supply Turn-on Power Level: (15)
N/A~
Instrument Failure Mode: (30) LOW = LOP Temperature Compensation
' for DP Transmitters:(1)
N/A Level Reference Leg: (3)
N/A Unique System Desc.: (100)
- RECIRC SUMP LEVEL XMTR XMTR TRAIN B EJLIT0008 LOW LIMIT 1FT 1 IN1FT 1 IN ABV SUMP FLOOR l.
COMPUTER ALARMS -
MODE Hi FF 2002.20 LP 2002.20 HS 2002.20 HC 2002.20 CS 2002.20 RF 2002.20
_ _ _.