Fifth Interim Significant Const Deficiency Rept 70 Re GE 480-volt Trip Coils Not Dropping Out After Tripping.Two of 86 Breakers Remain to Have Design Change Installed & Verified.Final Rept Will Be Submitted by 831221
ML20085L168
Person / Time
Site: Waterford 
Issue date: 10/07/1983
From: Gerrets T
LOUISIANA POWER & LIGHT CO.
To: Jay Collins
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
References
10CFR-050.55E, 10CFR-50.55E, 70, W3K83-1512, NUDOCS 8310210293
Download: ML20085L168 (2)


Text

_ _ _ _ _ _ _ _ _

i LOUISIANA POWER & LIGHT /Waterford 3 SES/P. O.

Box E/Killona, LA 70066 NSNhYSE October 7, 1983 W3K83-1512 Q-3-A35.07.70 Mr. John T. Collins Regional Administrator, Region IV I

U. S. Nuclear Regulatory Commission i

OCT I 4 M3 1

611 Ryan Plaza Drive, Suite 1000 g

. y Arlington, Texas 76012 g

-l

REFERENCE:

LP&L letter W3183-0305 dated September 9, 1983

Dear Mr. Collins:

SUBJECT:

Waterford SES Unit No. 3 Docket No. 50-382 Significant Construction Deficiency No. 70 "GE 480-V Trip Coils Do Not Drop Out After Tripping" Fifth Interim Report l

The above referenced letter indicated that a Final Report would be submitted l

to the USNRC by October 11, 1983.

At the present time, only 2 of 86 breakers remain to have the design change installed, and verification of supporting documentation is in progress. The corrective action is expected to be completed in November 1983.

l A Final Report will therefore be submitted to the USNRC on December 21, 1983.

Very truly yours, D

T. F. oerrets Quality Assurance Manager TFG:CNH:VBR cc: Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D.C.

20555 8310210293 831007 PDR ADOCK 05000382 1 b-1 S

PDR eO

t-

.o 3.,

Mr. John T. Collins October 7, 1983 W3K83-1512 Page 2 cc: Director Office of Management Information and Program Control U. S. Nuclear Regulatory Commission Washington, D.C.

20555 Mr. E. L. Blake Shaw, Pittman, Potts, & Trowbridge 1800 M Street, N.W.

Washington, D.C.

20036 Mr. W. M. Stevenson Monroe & Lemann 1424 Whitney Building New Orleans, Louisiana 70130 1

1 4

l