Telecopy Ro:On 730729,during Unit Startup,Msiv 1B Found to Have Closure Time Above Tech Spec Limit.Cause Not Stated. MSIVs Will Remain Closed Pending Evaluation
ML20085K259
Person / Time
Site: Dresden 
Issue date: 07/31/1973
From: Worden W
COMMONWEALTH EDISON CO.
To: Grier B
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20085K261 List:
References
NUDOCS 8310200367
Download: ML20085K259 (2)


Text

- _ _ _ _. - -. -._

l l

maa Em.

Telegram mestem union lw

-- BND106(1H04)(1-007727C212)PD 07/31/73 1002 I

l ICS IPMVEIC MVN 03038 (03228) TDVE MORRIS ILL 93 07-30 330P CDT FON 3128582660

]

BOYCE BRIER DIFECTOR DI\\ OF COMPLIANCE REGION E US ATodIC ENEFCY COMMISSION 799 ROOSEVELT RD GLEN ELLYN IL 6 037 l

SUBJECT DPR-25 DRESDEN NUCLEAR POWER STATION UNIT 3.

THIS WILL CONFIRM A CONVERSATION WITH MR F MAURA 0F YOUR OFFICE I

AT 1930 HOURS THIS DATE CONCERNING FAST CLOSURE TIME ON IB MAIN STEAM ISOLATION VALUE. ON 7/29/73 DURING A UNIT STAT UP IB MSIV WAS TIMED AND FOUND TO HAVE A CLOSURE TIME OF 2.6 SECONDS.

CABLE 3.7.1 0F TECHNICAL SPECIFICATIONS REQUIRES A C10SURE TI ME OF BE.

T-SF.1201 (RS49)

BETWEEN 3 AND 5 SECONDS UNTIL PROBLEMS CAN BE CORRECTED, MSIVS 1 B AND 2 B WILL REMAIN CLOSED W P WARDEN SUPERINTENDENT DRESDEN NUCLEAR POWER 3TATION 8310200367 730731 PDR ADOCK 05000 S

SF 12C1 (RS491

9 o

-#26

[

'g UNITED STATES I

ATOMIC ENERGY COMMISSION

) ',

L. Q. L DIVISION OF COMPLE ANCE REGION lll 799 ROOSEVELT ROAD GLEN ELLYN. lLLINols 60137 (3:23 ass-2sso A.

RO Inspection Report No.

Transmittal Date Distribution:

Distribution:

RO Chief, FS&EB RO Chief, FS&EB 7 0Tli G 5)~

RO:HQ (4)

DR Central Files L:D/D for Fuel & FMterials Regulatory Standards (3)

DR Central Files Licensing (13)

B.

RO Inquiry Report No.

Transmit.tal Date I

I Distribution:

Distribution:

RO Chie f, FS&EB RO Chief, FS&EB RO:HQ (5)

RO: liq DR Central Files DR Central Files Regulatory Standards (3)

Licensing (13)

C.

Incident Notification From: Cor:=onwealth Edison Co.

DPR-25 (Licensee & Docket No. (or License No.)

Transmittal Date

August 6,1973 Distribution:

Distribution:

R0 Chieh FS&EB RO Chie f, FS&EB RO:HQ (4)

RO:HQ (4)

Licensing (4)