h 4,q,'. -
E Log # TXX-91393 File # 10110
- = - - - -
h
. ~. _
903.8 r
-=
Ref. # 10CFR5055(e)
NELECTRIC October 23 1991
,,q c,,,
, na e uo rra.u a v
U. 5. huclear Regulatory Commission-Attention:. Document Control Desk
- ?.
Washington, D. C.
205552
$?f
SUBJECT:
COMANCHE PEAK' STEAM ELECTRIC STATION (CPSES), UNIT 2 4
7#
- DOCKET H0.t50-446
~
REJECTABLE INDICATIOWS IN CONTAINMENT ELECTRICAL' PENETRATION STRUCTURAL WELOS SDAR CP.-91-04 (FINAL REPORT) 60ntlemen:
10n;' June 24,:1991,-TU Electric notified N W Region IViof a potentially 1*
freportabloideficiency involving rejectableLind' cations in-containment j
electrical-penetration structural welds. The last report ~ was TXX-91373 dated October 16, 1991., As discussed in TXX-91268, dated July 24, 1991, this issue involved seventy-five.(75) Unit.2 electrical penetrations that lacked-g volumetric ~ examinations required by the ASME Code.
Ultrasonic examination of these>penetrationsidentifiedthree(3).withrejectableindications.
N' ALcalculation has been performed which demonstrates that the presence of
!these indications would not have: impaired the functional capability of-these.
- ponetrations._'As-a result,'this deficiency would not havel adversely affected the" safety of plant; operations and-is not-reportable under the provisions of 10CFR50.55(e).JHowever,-these-indicationshavebeencorrec*dto-complywith
+
ithe ASME-Codel.-Records: supporting this determination are available-for=your
~ inspector's' review..
i
.J Sincerely,
.- y
-^
-William J. Cahill, Jr.
J.- l CBC/JAA/
ci-~ Mr. R. D..-Martin, RegionLIV o
^
~ ',
Resident Inspectors CPSES (2)-
p
'\\ Q s
L91'10300011 - 911023 -
L yR.ADOCK0500g6-400 N.OHvo 5tml 1.B. 81 Daum,Tum ?not i.
[
~