Special Rept:On 950515,121 Motor Driven Fire Pump Was Taken Out of Svc Due to Failed Transformer in Pump Control Circuitry
ML20085G059
Person / Time
Site: Prairie Island  
Issue date: 06/12/1995
From: Richard Anderson
NORTHERN STATES POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9506200051
Download: ML20085G059 (2)


Text

_. _ _

i-

.l Northern States Power Company Prairie Island Nuclear Generating Plant 1717 Wakonade Drive East Welch. Minnesota 55089 -

June 12, 1995 Technical Specification Section 3.14 U S Nuclear Regulatory Commission Attn: ' Document Control Desk Washington, DC 20555 PRAIRIE ISIAND NUCLEAR GENERATING PIANT Docket Nos. 50-282 License Nos. DPR-42 50-306 DPR-60 Report of Fire Protection Pump Removed from Service for Greater Than Seven Days This special report is being submitted in accordance with Prairie Island Technical Specification 3.14.B.2.

Technical Specification'3.14.B.2 requires that, "With one or two of the pumps required by Specification 3.14.B.1.a inoperable, restore the inoperable equipment to OPERABLE status within seven days or provide a special report to the Commission within 30 days outlining the plans and procedures to be used to provide for the loss of redundancy in the FIRE SUPPRESSION WATER SYSTEM."

On May 15, 1995 the 121 Motor Driven Fire Pump was taken out of service due to a failed transformer in the pump control circuitry. The control circuit components are being removed, inspected, and replaced as necessary to correct the problem. Repair of the pump control circuitry is continuing and has required more than seven days to complete.

Due to the nature of the failure, the Motor Driven Fire Pump is available for service, but will not be declared operable until control functions are restored and the pump is adequately tested. During the time the Motor Driven Fire Pump is and has been out of service, either the 122 Diesel Driven Fire Pump or the 121 Screenwash Pump have been operable.

In addition, the plant has the ability to crosstie the cooling water system to the fire header for a back-up suppression supply.

No new NRC comrnitments are bein5 made in this letter.

h 9506200051 950612 PDR ADOCK 05000282 S

PDR

l*p.,.[

l l

USNRC NORTHERN STATES POWER COMPANY June 12, 1995 Page:2 l.

Please contact Jack Leve111e (612-388-1121, Ext. 4662) if you have _ any questions related to this letter, kbY Roger O Anderso Director Licensing and Management Issues c: Regional Administrator - Region III, NRC Senior Resident Inspector, NRC NRR Project Manager, NRC J E Silberg l