N Comm:nwealth Edisen f
.)
1400 Opus Place 7 _ Dowr.ers Grove, Imnois 60515
'i v
'%./
August 27,1991 Dr. Thomas E. Murley, Director Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Attn: Document Control Desk
Subject:
Quad Cities Nuclear Power Station Units 1 and 2 Noncompliance with NPDES Permit IL-0005037 NBR.DocketNom50:254/265 Gentlemen:
In accordance with Facility Operating License DPR 29 and DPR-30, Appendix B Environmental Protection Plan, enclosed is the Notice of Noncompliance which was i
submitted to the Illinois Environmental Protection Agency and U.S. Environmental Protection Agency, if there are any questions regarding this submittal, please contact R. Stols at 708/515-7283.
Sincerley,
\\
Rita Stols Nuclear Licensing Administrator cc: A.B. Davis, Regional Administrator T.E. Taylor, Resident inspector, Quad Cities l
l l
I
^r rn t-y9
-t<
y t
I ['[:
}
/964:109 d,f'U y j'l{ Kf g g g
r Commonwealth Edison Cad Cftet toWr Ni Sutat 227to 2N Aved Nom Cemovt. Ilho's C9242 9?40 nwoe.s mess.ust RLB-91 195 August 13, 1991 Illincic Environmental Protection Agency Division of Water Pollution Control Compliance Management Unit 2400 Churchill Road Springfield, Illinois f2?O6 U.S, Environmental Protection Agency Region V. Enfoteenent Division Attention:
Chief, Compliance Unit 230 South Learbo:n Street Chicage, Illinoic 60604 Eubject:
NsDES Non-Complisnees for Quad-Cities Generating Station IL-0005037 Dear Sirst In accordance with Standard Ccndition 12 we wish to submit the following notice of non-compliancast DISCHARGE:
004: Miscellaneous Wastewster Treatment Syritem PARAMETER AND PERMIT LIMIT:
Total Suspended Solida - Limit 30mg/ liter daily max.
NOS-COMPLIANCE AND DATL:
TSS daily maximum concentratien of 46mg/L on 7/31/91 from a cenposite sLmple 9 0700.
A grab eample @ 1215 TSS was 25cg/L on 7/31/?l.
Tne ec=posite sampic taken on 8/1/91 for TSS was 9mg/L.
CAUSE:
The air ccmpressor was inoperable and it is suspected that a filter outlet valve did not c1cse properly during a filter backwash, allowing filter backwash te flow into the clear water reservoir resulting in high effluent TSS.
The other pessibility is that the filter media did not perform its function properly.
CORRECTIVE ACTIC41:
The air compressor nas been repaired.
Work requests have been written te inspect and repair both filter outlet valves.
New filter media has been cbtained and work requents have been submitted to replace the media in both filters.
If there are any question, please call Ray Moora of my staff at 309-654-2241, extension 2731 Sincerely, M
R.L. Bax Station Manager Qued Cities RLB/RH/ dis cc: