33!4P EST JLA. 25 72 DEB 297 DE DEB 430( 1>24)( 1-0164120207)PD 07/25/72 T437 g
N, f,,
ICS IPMJLI 7
ZCZC 18 2 J PD
' JL MORRIS ILL 25 218P CDT N /n "0;nh) n PMS BOYCE mIER DIR FDIVN OF COMPLIANCE REGION 3 US ATOMIC ENGY COMM 799 ROOSEVELT RD GLEN ELLYN ILL 60137 SUBJECTJ DPR-25 DRESDEN NUCLEAR POWER STATION UNIT 3 THIS IS TO CONFIRM A CONVERSATION WITH MR H DANCE OF YOUR OFFICE AT 1345 HOURS THIS DATE CONCERNING A DRIFT BEYOND THE LIMITS 0F INSTRUMENT ACCURACY IN THE CALIBRATION OF A HIGH REACTOR 2
'I' E s
PRESSURE SCRAM SWITCH THAT RESLLTED IN A SET POINT BE ALLOVED IN SECTION 3 10F THE TECHNICAL SPECIFICATIONS.
DURING ROUTINE CALIBRATION ON JULY 18 1972 SWITCH PS-3-263-55A WAS FOUND SET AT A VALUE CORRESPONDING TO 1075 PSIG COMPARED TO THE LIMITS OF 1060 PSIG INCREASINGING. THE SWITCH, A MELETRON, MODEL sr.mi met JUL 2 81977 u
_m_
372-oSSd49A, WAS IMMEDIATELY RECALIBRATED AND A INVESTIGATION WASBEGUN TO DETERMINE THE CAUSE OF THE DRIFT.
A REVIEW OF THE CALIBRATION HISTORY OF THESE SWITCHES SHOWED A TENDEN CY FOR THE SET POINT TO DRIFT UPUARD DURING THE SUMMER MONTHER AND DOWNWARD IN THE WINTERMONTHS.
UtRIL THE CAUSE OF THIS BEHAVIOR IS DISCOVERED THE SWITCHES WILL BE CALIBRATED MONTHLY DURING THE SUMMER MONTHS. A FURTHER INVESTIGATION WILL BE BEGUN TO DETERMINE THE CAUSE OF THIS SET PINT SHIFT AND VILL BE REPORTED AS RECUIRED BY SEC 6.B.2 0F THE TECHNICAL SPECIFICATIONS.
W P WORDEN SUPT DRESDEN NUCLEAR POWER STATION.