l N

_.- 7 3 - 3,q,; a -.

ny- ~ _. - - - -

..?

. ; y _, ~~

_-? ;~; z. ; '-

3 ;.

,y-v sv Q.. '.3 3, 3 g;;y -

q 3 ;,

1.

!N I.)

n VEB209 ( l 702) ( l-025113C07 8) PD 03/19/73 1659 J((/

ICS IPMVEIB MVN Z CZC 0?.088 MORR IS ILL 166 034 & 247P CST 3

l

~

,f,

PMS MR BOYCE GRIER DIRECTOR DIV 0F COM?LI ANCE REGION 3 7

US ATOMIC ENERG Y COMMISSION 799 ROOSEVELI HD GLENELLYt1 ILL SU3 JECT DPR-25 DRESDEN NUCLEAR POWER STATION UNIT 3

/

i THIS WILL CONFIRM A CONVHSATION WITH MR H DANCE OF YOUR 0FFICE CONCERNING HPCI ROOM TEMPERATURES SWITCHES OUT OF CALIBRAT10N.

WHILE CONDUCT ING REFUELING O UT AGE C AL IB RA110M, 15 0F THE 16 HPCI ROOM TEMPER ATURE SWITCHES WERE FOUND

.f f

AB0VE THE TECHNIC AL SPECIFICATION LIMITS. THESE SWITCHES ARE' DEISGNED TO SENSE HIGH TEMPERATUHE IN THE HPCI ROOM IN THE EVENT O

n OF A PIPliiG BRAKE AND ISOLATE THE HPCI STEAM SUPPLY.

TABLE 3.2.1 0F THE TECHNICAL SPECIFICATION REQUIRES THAT THE S F. ? 2C 1 r RS f 9; TRIP SETTING BE LESS THAN OR EQUAL TO 200 DEGHEE FAHRENHEIT DURING CALIBRATION, 3 SWITCHES TRIPPED AT 202 DEGREES FAHRENHEIT ONE AT 203 DEGREES FAHRENHEIT I AT 20b DEGhEES FAHRENHEIT I AT 208 DEGREES FAHRENHEIT 3 AT 210 DEGREE 5 FAHRENHEIT AND'!

AT 212 DEGREES FAHRENHEIT 3 SWITCHES DID NOT TRIP eELOW 212 I)

DEGREES FAHRENHEIT THE MAXIMUM TEMPERATURE UTILIZED IN THE CAllBRATION PROCEDURE. ALL SWITCHES WRE RESET TO i

TRIP AT 190 TO 195 DEGREES FAHRENHEIT W P WORCEN SUPERINDENET CO MMNWE ALTil EDISON DRESDEN NUCLEAR P04ER STATION RURAL ROUTE 1 MORHIS ILL 1

8306160436 730330 PDN ADDCH 0 5 0 0 0 ? 4 c; PDR u,.