ICS IPI3NGZ CSP 8159424449 TmN MORRIS IL 66 04-25 0449P EST PMS J F O' LEAR 4 -BIRECTOR, DIRECTORATE OF LICENSING, U.S. NUCLEAR REGULAIORY COMMISSION, WUX WASHINGTON DC 20555 SUBJ EC T: DPR-25, DRESDEN N UCLEAR P OWER STATI ON, UllIT 3.
THIS WILL CONFIRM A CONVERSATION WITH MR TA!'3 LING OF YOUR OFFIC E 1550 HOURS THIS DATE CONCBNING EXCESSIVE LEAKAGE THROUGH TORUS TO DRYWELL VACUUM BR EAKER 3-1601-323 DURING REFUEL OUTAGE LOCAL LEAK RA TE T ES TI NG. LEAKAGE FROM THE VALVE EXHIBITED 113.6 SCFH, PRIMARILY THRO'U3H TH E VA LVE SH AFT SEALS. THE VALVE WILL BE INSPECTED AND REPAIR ED D!BING THIS OUTAGE B B STEPHE>iSON SUPERINTENDENT DRESDEN NUCLEAR POWER STATION COMI40NWEALTH EDISON COMPANY RURAL ROUTE 1 MORRIS ILLIN0IS 60450 1901 EST